Permit Number: DP19-0157
Parcel: 11941122A

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP19-0157
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2019 SBEASLE1 START PLANS SUBMITTED Completed
07/15/2019 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Passed
07/15/2019 SBEASLE1 WWM REVIEW Passed
07/16/2019 JOHN VAN WINKLE ENGINEERING REVIEW Denied DP19-0157

1) Previous comment. Please provide a grading plan that is in conformance with the submittal requirements found in City of Tucson Administrative Manual section 2-06 and Technical Standards Manual Section 2. In particular Technical Standard Sections 2-01.4.1.F (Regular Grading) and 2-01.7 through 2-01.11. Include all standard notes and details. Please review these sections in detail. For example, the previous plan did not show a straight 12' vertical cut. Per TSM section 2-01.7.2 The slope of cut surfaces shall be no steeper than is safe for the intended use and shall be no steeper than one unit vertical in two units horizontal (50% slope) unless the permittee furnishes a soils engineering or an engineering geology report, or both, stating that the site has been investigated and giving an opinion that a cut at a steeper slope will be stable and not create a hazard to public or private property
2) Applicant is encouraged to participate in a pre-submittal meeting. Please see following link https://www.tucsonaz.gov/pdsd/development-permits and search for "Pre-Submittal". This will provide directions how to schedule a meeting with applicable reviewers to go over the requirements prior to submitting the project for formal review
3) For questions on how to schedule a pre-submittal meeting please use the email address provided below

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
07/16/2019 STEVE SHIELDS ZONING REVIEW Denied See Engineering comments