Permit Number: DP19-0153
Parcel: 11522129A

Address:
1601 W EL RIO DR

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP19-0153
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2019 SBEASLE1 START PLANS SUBMITTED Completed
07/17/2019 MASHFOR1 COT NON-DSD FIRE Approved
08/08/2019 DAVID RIVERA ZONING REVIEW Reqs Change From: David Rivera
PDSD Zoning Review Section

Project: DP19-0153 - Greenview Apartments Parking Lot Shade Structures
Site Review (1st Review) - Related to T19CM04344
1601 W. El Rio Drive - R-2 Zoning

TRANSMITTAL DATE: August 7, 2019

DUE DATE: August 13, 2019

***Please resubmit corrected drawings and any redlined copies along with a detailed response memo, which details how the Zoning Review Comments have been addressed.

CHECKLIST FOR MINOR DEVELOPMENT CHANGES TO EXISTING
COMMERCIAL/INDUSTRIAL SITES
Purpose
This standard has been prepared for the purpose of informing applicants of the submittal and review requirements for minor changes to existing commercial sites to assure proper and adequate information is presented in a consistent manner, thereby providing the basis for an efficient and timely review. The minor revisions to existing commercial sites are prepared in support of applications for building permits and related reviews.

The information that is requested establishes the basis upon which the project will be approved and could affect what is required of the property in the future, should there be a proposal for expansion or for a different use of the property. This standard does not waive any applicable city regulations or codes. Applicability

This standard shall be used for minor changes to existing commercial sites such as but not limited to; expansions less than 25%, in square footage of land area, floor area, lot coverage, or vehicular use area, modification to accessible vehicle parking, parking area restripe, etc. Applicability is to be determined by Zoning and/or Engineering review staff.

APPLICATION SUBMITTAL REQUIREMENTS
Development Package applications are available from PDSD. Completed applications and accompanying materials shall be submitted to PDSD. Incomplete or inaccurate applications will not be accepted. The types of documents and the specific number of copies required of each of the documents are on the PDSD website or may be obtained from PDSD. Resubmittals of development packages require a comment response letter that details how all previous comments have been addressed. Provide the same number of copies of the comment response letter as plans provided.


The following documents and information shall be submitted upon application:

1. - COMMENT: A completed application signed by the property owner or authorized designee.

2. - COMMENT: A development package must be prepared to the format and content requirements described herein.


FORMAT REQUIREMENTS


1. - COMMENT: All mapped data shall be drawn at an engineering scale having no more than 50 feet to the inch. This scale is the minimum accepted to assure the plan will be legible during review and when digitized and/or reduced for record-keeping purposes. The same scale shall be used for all sheets within the set. Smaller scales (60:1 or greater) may be used for some or all of the sheets with the prior approval of PDSD when it is determined legibility and the ability to be digitized and/or reduced for archiving will not be affected.


2- COMMENT: Draw the Vicinity map per the following information in Comment A and B below:
A small, project-location map shall be provided in the upper right corner of the cover sheet. This map shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information;

a. - COMMENT: Show the subject property approximately centered within the one square mile area. Identify major streets within the square mile area and all streets that abut the subject property. Section, township, and range, north arrow, and the scale will be labeled.

b. - COMMENT: The north arrow, and scale as applicable to each sheet should be placed together in the upper right corner of each sheet.


3. - COMMENT: A legend that shows and describes all symbols used on the drawing is to be provided, preferably on the first sheet.

4. - COMMENT: An index of sheets in the development package shall be provided on the first sheet.


CONTENT REQUIREMENTS

1. - COMMENT: List the Email addresses and contact names for each of the project team listed on the cover sheet.

2. - COMMENT: The title block shall include the following information and be provided on each sheet:

a. - A brief legal description: EL RIO ESTATES LOT A & ELY PTN OF LOT B, M/P Bk 7 at PG 43, Section 3 of T14S, R13 E.

b. - The page number and the total number of pages in the package (i.e., sheet xx of xx),

c. - The development package case number: DP19-0153,

d. - If applicable the case number of any of the following processes if required: Board of adjustment or Design Development Option, shall be provided adjacent to the title block on each sheet.


General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

1. - COMMENT: Add the following note: "Existing zoning is R-2."

2. - COMMENT: List the gross area of the site by square footage and acreage.

3. - COMMENT: Identify the existing and proposed use of the property as classified per the UDC
List all UDC sections applicable to the proposed uses: "Existing Use is Residential Use Group, Multifamily use Subject to UDC sections 4.9.7.B.6, .9, & .10


Existing Site Conditions:

1. - COMMENT: Provide site boundary information, including bearing in degrees, minutes, and seconds, together with distances in feet, to hundredths of a foot, or other functional reference system.

2. - COMMENT: All existing easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated.

3. - COMMENT: The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks. The street, curb and sidewalks shall be clearly defined, labeled and dimensioned.


Information on Proposed Development:
The following information on the proposed project shall be shown on the drawing or added as notes.

1. - COMMENT: All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing (Sheet 2) with zoning boundaries clearly defined.


Design Criteria, of the UDC.

1. - COMMENT: On Sheet 3, provide a perpendicular dimension from the property line to the carport structures adjacent to El Rio Drive. The minimum building setback must be the greatest of 20 feet or 1.5 times the height of the carport structures. In addition the carport structures are not allowed to be placed in the required front street perimeter yard setback of the existing buildings. Draw a line that is parallel to the property line that represents the building setbacks of the apartment buildings facing El Rio Drive. The two carport structures adjacent to El Rio Drive must behind the building setbacks of the existing apartment structures.

The two carport structures facing Mohave shall be setback a minimum of 10 feet from the property line. The carport structure adjacent to building 1623 does not meet the required building setback. It is proposed at 4'-4".

All carports depicted on the plans must be setback a minimum of 1 foot from the edge of the PAALS (back of the parking spaces).

2. - COMMENT: Provide the height of each carport canopy. If the height is typical of all structures list the height as typical for the three types in the carport summary table on sheet one.

3. - COMMENT: Show the refuse collection areas, including locations of dumpsters.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: as noted above
08/12/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
- The reviews have been completed
- A resubmittal is required

Permit/Activity Number: DP19-0153
Description: SITE - Greenview Apts, solar, parking shade structures.
The fee balance is $0 (zero). Thank you for the payment.
To view the review comments: www.tucsonaz.gov/PRO, enter Activity Number.
(If information isn't shown yet, check back later as data flows to PRO periodically throughout the day.)
Name your 2nd submittal documents accordingly, for example: 2_Plan_Set.
Submit the following items to the PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, please include the Activity Number.
1) Comment Response Letter (listing your response to reviewer's comments)
2) Plan Set (all pages, full set)
3) Any other items requested by review staff
Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, First Floor
Tucson, AZ 85701
08/12/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS

The Development plan will contain the following identification in the lower right corner of each sheet:

Cross-reference to:

Any relevant case numbers for reviews or modifications that affect the site.

Indicate Case # DP19-0153 on each sheet.

7.7. NATIVE PLANT PRESERVATION

7.7.3. APPLICABILITY

The provisions of this section apply to all development as listed below.

A. New Development

All new development proposed in the City of Tucson shall comply with the standards of this section.

7.7.4. GENERAL PROVISIONS AND STANDARDS

A. Submittal Requirements

A Native Plant Preservation Plan in accordance with Section 2-11.0.0 of the Administrative Manual is required for all projects under the applicability of this section according to the methodology selected by the applicant as outlined in Section 7.7.5, Plant Preservation Standards.

Submit NPP Plan or Application for Exception.

https://www.tucsonaz.gov/files/pdsd/forms/NPPOapp.pdf.



SECTION 4-02.0.0: FLOODPLAIN, WASH AND ERZ STANDARDS


Encroachment in Regulated Areas

If the project proposes encroachment within the regulated areas, it shall conform to the following.

1. Environmental Resource Report. Applicants are required to submit an Environmental Resource Report as defined in Section 11.4.6 of the UDC.

DSD may grant waivers where the elements or full report are not required by code.


Portion of the site is within a FEMA floodplain and encroachment is proposed. Verify with Landscape and Engineering sections if ERR report is required.


Ensure that all Zoning comments are addressed.


Additional comments may apply.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2019 SBEASLE1 OUT TO CUSTOMER Completed