Permit Number: DP19-0144
Parcel: 117140870

Address:
341 S STONE AV

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP19-0144
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2019 SBEASLE1 START PLANS SUBMITTED Completed
06/13/2019 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed Review not required. This agency was notified for their information only.
06/13/2019 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Passed Review not required. This agency was notified for their information only.
06/13/2019 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed Review not required. This agency was notified for their information only.
06/13/2019 SBEASLE1 UTILITIES SOUTHWEST GAS Passed Review not required. This agency was notified for their information only.
06/19/2019 SBEASLE1 COT NON-DSD ENVIRONMENTAL SERVICES Reqs Change The Environmental & General Services Department has completed our review of the Development Package for the 375 South Stone property.
The applicant shall provide the following additional information concerning solid waste management for this site:
- A note on the plan set specifying the anticipated method of collection and collection frequency. Section 8-01.4.0 B of the UDC.
- Calculations for the anticipated waste generation. Section 8-01.4.0 B of the UDC.
- A figure showing construction details for the enclosure including the design of the enclosure walls, interior bollards, gates, and other details of the enclosure as specified in Section 8 of the UDC.

We can provide more detailed review comments after review of the above information. Thanks.

Tom Ryan, P. E.
City of Tucson - Environmental & General Services Department
06/25/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/26/2019 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Reqs Change June 25, 2019
Sharon Beasley, Permit Technician
City of Tucson
201 North Stone Avenue, First Floor
Tucson, AZ. 85701
RE: DP19-0144 375 South Stone / 1st Submittal, Received June 13, 2019
Dear Ms. Beasley,
Thank you for the opportunity to comment on DP19-0144, 375 South Stone; 1st Submittal, a development package application for an approximately 0.76 acre site, located southeast of the intersection of East 14th Street and South Stone Avenue. The property is zoned Commercial Zone 3 (C-3) and Historical Commercial Zone 3 (HC-3), with the proposed development being a mixed use building, which would contain both residential and commercial uses.
This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.
The Tucson Airport Authority conditionally approves the subject request contingent upon the following conditions of approval, as noted below. These conditions shall be identified in the general notes of the revised development plan.
Conditions of approval:
1. "According to the Federal Aviation Administration (FAA) Notice Criteria Tool, this project area is located in proximity to a navigation facility and could impact navigation signal reception. The project applicant shall file FAA Form 7460 with the FAA at least 45 days before construction activities begin unless FAA staff, with the Obstruction Evaluation / Airport Airspace Analysis (OE/AAA), provides the project applicant with written communication that filing FAA Form 7460 is not required. It is highly recommended that the applicant file earlier than 45 days to provide the applicant with sufficient time to respond to any concerns which are identified by the FAA. Any cranes which are used must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp"

Although this project does not propose a change in plan designation or zoning the Tucson Airport Authority highly recommends the applicant add the following two notes into the general notes of the revised development plan. This project is located approximately 6 miles northwest of Tucson International Airport and is within FAA traffic pattern airspace, an area which would be subject to aircraft overflight and noise due to being in close proximity to Tucson International Airport.

The first proposed note would provide a means of assuring that future owners and tenants of the property are aware they are in proximity an airport and further assures the continued right of the City of Tucson, Tucson Airport Authority, and all persons lawfully utilizing the Tucson International Airport the right to utilize the airspace above or near the property. This would be accomplished through the property owner recording the Avigation Easement. The second proposed note is meant to be a second method of notification, but only for residential related uses, that future property owners and tenants are living near an airport. The Tucson Airport Authority believes the proposed notes help to support the City of Tucson Airport Environs Overlay Zone and supports Plan Tucson - Regional and Global Positioning policy 4 (RG-4).
1. "That prior to the City's approval of any construction permit for a permanent building, the property owner shall record the Avigation Easement which discloses the existence, and operational characteristics of the Tucson International Airport to future owners or tenants of the property and further conveys the right to the public to lawfully use the airspace above the property. The Avigation Easement shall be recorded in a manner with the Pima County recorder which shall document it as having title liability. The content of such documents shall be according to the form and instructions provided."
The current property owner or person authorized to sign on behalf of the current property owner shall complete, sign, and record the Avigation Easement. Please record the Avigation Easement with the Pima County Recorder's Office. Once the Avigation Easement is recorded please send a complete copy of the recorded easement document to Tucson Airport Authority by either email (send to srobidoux@flytucson.com) or to the mailing address provided below.
Scott Robidoux, Senior Airport Planner
Tucson Airport Authority
7250 South Tucson Boulevard, Suite 300, Tucson, AZ 85756
2. For only residential uses - "The developer shall provide the Airport Disclosure Statement form, at time of sale, to the new property owners with new unit purchases. In the event the development of any residential uses does not involve the sale of new units, but is instead offering rental residential units to the public, the new tenant of the rental unit shall be provided a copy of the Airport Disclosure Statement form. The intent of the Airport Disclosure Statement form is to educate and notify the new residents that they are living near an airport. The content of such documents shall be according to the form and instructions provided."

The new property owner or new tenant shall forward a signed copy of the Airport Disclosure Statement form to the Tucson Airport Authority, using the mailing address provided below.

Scott Robidoux, Senior Airport Planner
Tucson Airport Authority
7250 South Tucson Boulevard, Suite 300, Tucson, AZ 85756
Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.
Respectfully,
Scott Robidoux, Senior Airport Planner

email cc: GGray@miramontehomes.com
06/26/2019 MASHFOR1 COT NON-DSD FIRE Reqs Change Fire Sprinklers/ Fire Alarm monitoring & notifications will be required on this project. Emergency Responder Radio coverage will also be required.

Please also provide all current and any future Fire Hydrants on the plan set.
07/01/2019 ZELIN CANCHOLA COT NON-DSD TRAFFIC Reqs Change July 1, 2019
ACTIVITY NUMBER: DP19-0144
PROJECT NAME: New Building
PROJECT ADDRESS: 375 S. Stone Ave
PROJECT REVIEWER: Zelin Canchola TDOT

Resubmittal Required: The following items must be revised and added to the Development package.

1. A right of way permit will be required for work within the right of way.

2. New ADA pedestrian ramp (PAG standard detail) on south east corner of Stone and 14th required.

3. Show new driveway with 25 foot curb return radius.

4. Close any unused driveways on 14th and Stone Ave.

If you have any questions, I can be reached at 520 837 6659 or zelin.canchola@tucsonaz.gov
07/02/2019 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved No existing or proposed Tucson Parks and Recreation facilities are affected by this development.

Howard B. Dutt, RLA
Landscape Architect
Tucson Parks & Recreation, (520) 837-8040
Howard.Dutt@tucsonaz.gov
07/08/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change UNIFIED DEVELOPMENT CODE
4.1 Identification and Descriptive Data
A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.
The landscape plan will contain the following identification in the lower right corner of each sheet:
Cross-reference to:
a. Rezoning case;
b. Subdivision case;
c. Board of Adjustment case;
d. Design Development Option case;
e. Development Review Board (DRB) case; and/or,
f. Any other relevant case number for reviews or modifications that affect the site.
The following site is subject to the following:
5.12.9. GREATER INFILL INCENTIVE SUBDISTRICT (GIIS)
Section 7.6, Landscaping and Screening
a. Section 7.7, Native Plant Preservation may not be modified.
b. Except as required by Section 5.12.8.B, Development Transition Standards, a complete or partial exception to Section 7.6, Landscaping and Screening Standards, may be granted if shade is provided for pedestrians and customers, such as along sidewalks, pedestrian circulation paths, and outdoor patios, in accordance with Section 5.12.6.A.2. The landscaping requirement may also be waived by the PDSD Director based on a written finding that the waiver is necessary to preserve the prevailing setback.
c. Any one or more of the following types of landscaping and improvements may be used to comply with this section:
(1) Existing landscaping;
(2) Shade trees in the right-of-way;
(3) Green walls or green roofs; and/or
(4) Shade structures, such as awnings.
Provide GREATER INFILL INCENTIVE SUBDISTRICT approval or written PDSD Director waiver and any conditions imposed.
Ensure that all Zoning and Engineering comments and concerns are addressed prior to landscape approval.
Additional comments may apply.
07/11/2019 DAVID RIVERA ZONING HC REVIEW Reqs Change See zoning comments.
07/11/2019 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: 375 South Stone - Residential / Commercial (GIIS Overlay Area)
Development Package (1st Review) - 275 S. Stone Avenue
DP19-0144 - C-3 / HC3 Zoning

TRANSMITTAL DATE: July 10, 2019
DUE DATE: July 11, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is June 10, 2020.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

2-06.3.7 - A small, project-location map shall be provided in the upper right corner of the cover sheet.

1. COMMENT: Remove the references to the M/P number as they are not required on the DP location map.

Remove the line work for the lots and leave only the street center lines on the location map.


CONTENT REQUIREMENTS

2-06.4.2 - The title block shall include the following information and be provided on each sheet:

2-06.4.2.B - A brief legal description and a statement as to whether the project is a re-subdivision are to be provided. On re-subdivisions, provide the recording information of the existing subdivision plat;

2. COMMENT: Include the "SE QTR of the NW QTR" as part of the brief legal description in the title block of all plan sheets.


2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

3. COMMENT: Provide the development package case number, DP19-0144, adjacent to the title block on each sheet.


2-06.4.4.B - Identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and,

4. COMMENT: Label the following major streets on the location map; 6th Ave, Granada Ave., Cushing St., Toole Ave., Church Ave., and Main Ave..


2-06.4.7.A - Zoning and Land Use Notes

2-06.4.7.A.2 - List the gross area of the site/subdivision by square footage and acreage.

5. COMMENT: The overall area is made up of three parcels. Per the plan it appears that a lot reconfiguration is proposed and two parcels will be the end result. It is also my understanding that the proposed design may change due to a rezoning possibility or HPZ amendment to the Armory Park Historic Boundary. Additional comments may be forthcoming on the next review of the DP. At a minimum a lot reconfiguration application must be processed PDSD and the documents recorded.


2-06.4.7.A.3 - If the plan/plat has been prepared in conjunction with a rezoning application, add the following note next to the existing zoning note: "Proposed zoning is ____." List the applicable rezoning file number and conditions of approval. Also place the C9-__-__ (if applicable) and the plan/plat file numbers in the lower right corner of each sheet.

6. COMMENT: If a rezoning is processed to revise the historic boundary, add the rezoning case number next to the tile block of all plan sheets. Add a general note that includes the rezoning case number, date of effectuation and any rezoning conditions.


2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

7. COMMENT: Clarify if retail uses may be included in this development, if so, list retail as a use. List the specific commercial and retail uses proposed, see the use list in UDC article 5, section 5.12.9 table 5.12-GIIS-1.

It is not clear on DP if the existing development will be included in the GIIS review and approval process.


2-06.4.7.A.5 - On residential projects, list the total number of units/lots proposed.

8. COMMENT: If the existing Brady Court residential use is a standalone development annotate it on the DP. In the C-3 Zone, lot coverage is not applicable for multifamily development. Multifamily development with three or more units is considered a commercial use for application of the dimensional standards. Lot coverage does not apply to the existing Brady Court residential development or the new residential component of the new development. Revise General Site Note 14.



2-06.4.7.A.6 - If a plan or plat is prepared in conjunction with other applications or overlays or the parcel being developed is subject to conditions of an application processed previously, additional information must be added to the plan. Such applications and overlays include, but are not limited to: annexations; rezonings; special exceptions; Board of Adjustment variances; Design Development Options; Technical Standard Modification Request; overlays (Airport Environs Zone, Environmental Resource Zone, Gateway Corridor Zone, Hillside Development Zone, Historic Preservation Zone, Major Streets and Routes, Rio Nuevo District, Scenic Corridor Zone, WASH); Modification of Development Regulations through the Downtown Area Infill Incentive District or Rio Nuevo District; Downtown Heritage Incentive Zone; or, Design Review Board. Provide the following information on the plan.

9. COMMENT: As this project is within the IID - GIIS overlay area and the applicant is or will be processing and IID application for review and approval of multiple modifications, additional review will be required to assure compliance with the IID conditions. List as reference the IID case number in the lower right corner of all DP sheets. Under general site notes 8, list the IID case number, date of approval, and any conditions of approval associated with the Directors decision.

This parcel is within the Armory Park Historic District and a portion of the site is zoned HC-3. A separate HPZ review is required for the proposed development; contact Michael Taku 837-4963 for information on the HPZ review process. List as reference the HPZ case number next to the title block of all DP sheets and add a general note with the HPZ case number date of approval and any conditions associated with the review and approval of the HPZ application.


2-06.4.7.A.6.b - If there is more than one lot within the site, the note should specify which lots are affected by the additional applications or overlay zones.

10. COMMENT: If applicable include the information as noted by the standard above.


2-06.4.7.A.8.a - Floor area for each building;

11. COMMENT: List as a general note the building square footages as noted by the standard above.


2-06.4.7.A.8.b - Percentage and area in square feet of building and accessory building coverage;

12. COMMENT: As noted in comment 8, lot coverage is not applicable for multi-family development under the UDC dimensional standards. Remove any lot coverage calculations from the cover sheet.


2-06.4.7.A.8.d - When the proposed site is part of a larger site, the calculations encompass the entire site, whether existing or proposed. If the project is being phased, calculations must show that, at each phase, requirements are being met.

13. COMMENT: Provide the information as noted by the standard above depending on what the end result or design is proposed.


2-06.4.8 - Existing Site Conditions


2-06.4.8.A - Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system.

14. COMMENT: Include the site boundary based on recorded final lot reconfiguration.


2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided.

15. COMMENT: Abandonment of easements must be completed prior to approval of the DP.


2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

2-06.4.9.H.4 - Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned.

16. COMMENT: Include on the site plan sheet the information as noted in the two standards above.


2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

17. COMMENT: Label the 2.5 foot overhang along the south parking area.

The parking requirements will be evaluated on the next submittal of the DP to assure compliance with the IID and IPP applications.


2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

18. COMMENT:


2-06.4.9.I - Show all right-of-way dedications on or abutting the site and label. If the development package documents have been prepared in conjunction with a subdivision plat or is required as a condition of approval of a review process, such as a rezoning, street dedications in accordance with the Major Streets and Routes (MS&R) Plan may be required by these processes.
Projects bounded by streets having only a portion of the right-of-way width dedicated will be required to dedicate right-of-way, up to one-half, to complete the street width.
Should there be any proposed street or alley vacation, provide this information. If vacation has occurred, include the recording information.

19. COMMENT: Per the adopted Major Streets and Routes Plan, the Stone Avenue Right of way at this location is to be a total of 90 feet. Consult with TDOT for information on whether or not additional right of way will be required for Stone Avenue. Additional right of way if required would affect the placement of the proposed building. Provide in the next DP submittal any documentation from TDOT related to future right of way.


2-06.4.9.O - All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.

20. COMMENT: To be evaluated on the next submittal assuming the IID and HPZ applications have been processed and the setbacks were addressed as part of those applications.


2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).

21. COMMENT: Label the heights and square footages of the existing Brady Court buildings.


2-06.4.9.U - Indicate graphically, where possible, compliance with conditions of rezoning.

22. COMMENT: If a rezoning application is processed add the information as noted by the standard above.


2-06.4.9.V - For gang mailboxes indicate location to assure there are no conflicts with other requirements, such as pedestrian accessibility, utilities, and landscaping.

23. COMMENT: Clarify if gang mailboxes will be provided or will there be a main mail pickup location within the building for all residents and commercial tenants?


2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required.

24. COMMENT: Add a general note that states that all signage will permitted under separate review and permits.


If you have any questions about this transmittal, Contact David Rivera on Tuesday, or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
07/16/2019 SBEASLE1 PIMA COUNTY ADDRESSING Reqs Change (The "attached PDF" mentioned here can be viewed on PRO in the "Documents" section)

DP19-0144 / 1st submittal for review / 375 South Stone is being Returned for Corrections by Pima County Addressing.
Please see the attached pdf for Addressing’s comments.
Let me know if you have any questions.
Thank you,
Robin Freiman, Addressing Official
Pima County Development Services Department
201 N Stone AV, 4th Floor Tucson, AZ 85701
(520) 724-7570
07/16/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0144

1) Sheet C2. Grading note 29. The area of disturbance appears to be incorrectly shown as 8.28 acres,
2) Sheet C3. Update demolition plan to show that the Casa Vicente building ,Key Note 8, has already been demolished along with area around the building. Reference demolition permit T18BU00604
3) Provide on plans waste stream calculations per TSM section 8-01.8.0
4) Sheet C4. It appears that the roof drains on the east side of the building discharge within 10' of the existing building to the east. IBC section 1804 requires positive drainage away from building foundations for a distance of at least 10'. Please update as needed
5) Sheet C4. All curb access ramps, on or around the site, will be updated to PAG standard 207 and be in compliance with ICC A117. Including the use of detectable warnings. Please identify that the existing curb access ramp at the northwest corner of the development will be updated to current standards
6) Show on plans the dimensions for all existing sidewalks. Include the clearance between any utility poles or other obstructions that may reduce the sidewalk width. Example the western most power pole on 14th street. Show that a minimum 4' wide sidewalk is being maintained
7) Show on plans that the two current driveways along 14th street will be removed and replace with new curb and sidewalk

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
07/17/2019 SBEASLE1 COT NON-DSD TDOT Reqs Change DP19-0144 - IID - 375 South Stone:
TDOT LANDSCAPE COMMENTS:
1. Show dimensions on the Landscape Plan and Tree Planting Detail that shows the distance between curb and sidewalk.
2. The Tree Planting Detail calls out for Root Barrier, install all four sides. To be effective the root barrier must extend 2' beyond the drip edge of the mature canopy of the tree on both the curb and the sidewalk side.
3. The Tree Planting Detail shows the rootball under the sidewalk, this is not acceptable or possible when installing a root barrier.
4. Please add the Street Names and other pertinent site and surrounding site information to the landscape plan.
Thank you,
David Marhefka
da’-vid mär-hef’-ka
Landscape Architect
City of Tucson, Department of Transportation
(o) 520-837-6618, (m) 520-403-5074
07/18/2019 FRANK PODGORSKI HPZ ADVISORY BOARD HPZ ADVISORY BOARD DATE Needs Review Historic review has not happened yet.

Michael Taku, MS
Lead Planner
Planning & Development Services Dept.
City of Tucson
(520) 837-4963
07/18/2019 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved Regional Traffic Engineering has no comments on this submittal and supports its acceptance. The proposed location will have no impacts to any ADOT facilities.
Thank you.
Tom Martinez
TMartinez@azdot.gov
ADOT
07/25/2019 SBEASLE1 COT NON-DSD REAL ESTATE Approved If there are any encroachments into the City of Tucson right of way please submit a legal description of the encroachment along with an application for City's grant of easement.
Regards,
Michael J. Hollar, SENIOR PROPERTY AGENT
REAL ESTATE DIVISION
DEPARTMENT OF TRANSPORTATION
CITY OF TUCSON
201 N. Stone Ave, 6th Floor, Tucson, AZ 85701
Direct: 520-837-6784, Main: 520-791-4371
07/25/2019 NROSS1 DESIGN PROFESSIONAL REVIEW Reqs Change IID-18-06 design review is in process
07/25/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
- The reviews have been completed
- A resubmittal is required

Permit/Activity Number: DP19-0144
Description: SITE/GRADING/IID - 375 South Stone. High rise res/commercial building with new parking lot.
Project Manager: Alexandra.Hines@TucsonAz.gov, (520) 837-6975
The fee balance is $0 (zero).
Review comments: www.tucsonaz.gov/PRO, enter Activity Number.
(If information isn't shown yet, check back later as data flows to PRO periodically throughout the day.)
Name your 2nd submittal documents accordingly, for example: 2_Plan_Set.
Submit the following items to the PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, please include the Activity Number.
1) Comment Response Letter (listing your response to reviewer's comments)
2) Plan Set (all pages, full set)
3) Any other items requested by review staff
Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
07/25/2019 SBEASLE1 OUT TO CUSTOMER Completed