Permit Number: DP19-0136
Parcel: 13321157C

Address:
101 N JESSICA AV

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP19-0136
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2019 SBEASLE1 START PLANS SUBMITTED Completed
07/01/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL
SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS
Any relevant case numbers for reviews or modifications that affect the site.
Add Case # DP19-0136 on each sheet.

ARTICLE 7: DEVELOPMENT STANDARDS
7.6. LANDSCAPING AND SCREENING
Use of Drought-Tolerant Vegetation

1. Except as otherwise provided by this section, all plant material used for landscaping must be selected from the Arizona Department of Water Resource's Low Water Use/Drought Tolerant Plant List.

Ulmus parvifolia CHINESE ELM is not on the list. Choose appropriate substitution.

Ensure that all Zoning and Engineering comments and concerns are addressed.
Additional comments may apply.
07/03/2019 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: Kimberly Woods Apartments - Exist. Multi-family Development
Development Package (1st Review) - 6821 e Broadway Boulevard
DP19-0136

TRANSMITTAL DATE: July 3, 2019
DUE DATE: July 1, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is May 31, 2020.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

***Address the comments listed under each standard. The standard has been left in its entirety as reference for the zoning reviewer and applicant.


2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

1. COMMENT: Provide the development package case number, DP19-0136, adjacent to the title block on each sheet.


2-06.4.4 - The project-location map to be located on the first sheet of the development package in the upper right corner, shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information.

2-06.4.4.A - Show the subject property approximately centered within the one square mile area;

2-06.4.4.B - Identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and,

2-06.4.4.C - Section, township, and range; section corners; north arrow; and the scale will be labeled.

2. COMMENT: Revise the location map on the cover sheet to include the information noted in the standards above.



If you have any questions about this transmittal, Contact David Rivera on Tuesday, or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
07/03/2019 DAVID RIVERA ZONING HC REVIEW Approved
07/08/2019 JOHN VAN WINKLE ENGINEERING REVIEW Approved
07/09/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The reviews have been completed and a resubmittal is required.
The fee balance is $0 (zero). Thank you for the payment.
Activity Number: DP19-0136
Project Description: SITE - Kimberly Woods Apts., landscape renovations.

For review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number.
(If information isn't shown yet, check back later as data flows to PRO periodically throughout the day.)
After all corrections are made, please name your 2nd submittal documents accordingly, for example: 2_Plan_Set.
Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, please include the Activity Number.
1) Comment Response Letter (listing how all comments were addressed)
2) Complete Plan Set (all pages, full set)
3) Any other items requested by review staff
After resubmittal, the plans will re-enter the standard 20-working-day review cycle.
Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2019 SBEASLE1 OUT TO CUSTOMER Completed