Permit Number: DP19-0130
Parcel: 130144420

Address:
4005 E JUAREZ ST

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP19-0130
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2020 SBEASLE1 START PLANS SUBMITTED Completed
03/31/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/02/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. As previously commented, TSM 7-01.4.1.E requires pedestrian routes to be maintained flood free for up to a 10-year event. Clearly show that primary roof drains will not be directed to the surface of pedestrian routes.
Loren Makus
loren.makus@tucsonaz.gov
04/03/2020 ANDREW CONNOR LANDSCAPE REVIEW Approved
04/06/2020 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Site Section Manager.

PROJECT: Carmax Auto Superstore - Retail / Auto Rental and Sales Use
Development Package (1st Review) - 4030 E. 22nd Street
DP19-0130 - C-2 / R-3 zoning

TRANSMITTAL DATE: April 6, 2020
DUE DATE: April 6, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is June 24, 2020.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.
2-06.4.7.A - Zoning and Land Use Notes

2-06.4.8 - Existing Site Conditions

2-06.4.8.A - Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system.

11. Provide documentation that this comment has been addressed. COMMENT: The site is made up of 6 individual parcels. Prior to approval of the DP a Pima County Tax Parcel Combo will have to be completed.


2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided.

12. Zoning acknowledges that TEP easements take time to complete. Show all proposed easements or easements to be abandoned to be "PER SEPARATE INSTRUMENT" that way once record easements are provided to PDSD a revision to the plan will not be required. A hold will be put on the building certificate of occupancy until the recorded documents are provided. COMMENT: The vacation of any easements must be completed prior to approval of the DP. Include in the next submittal or prior to the final submittal of the DP, any recorded documentation related to the vacation of the easements.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

16. The proposed long term bicycle parking does not meet the intent of UDC Article 7.4.9.D.2. Anyone could walk into this room and walk out with a bike. COMMENT: Two short and two2 long term bicycle parking facilities are required for this development. Add a bicycle parking calculation and draw and label the location for long term facilities. Include fully dimensioned detail drawings of the proposed long term facility.

As the short term bicycle parking detail has been changed it now does not meet the requirements. Demonstrate on the detail how UDC Article 7.4.9.B.1.e, 7.4.9.B.2.b, .c, .d, & .f

If you have any questions about this transmittal, Contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
04/06/2020 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approved DP19-0130, 2nd submittal, CarMax Superstore #6170 is Approved by Pima County Addressing.

Thank you,
Robin Freiman, Addressing Official
Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-7570
04/08/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: Resubmittal with a Comment Response Letter

DESCRIPTION: SITE/GRADING/SWPPP/FUP - Carmax Superstore #6170.
PERMIT: DP19-0130
PROJECT MANAGER: Nicholas.Ross@Tucsonaz.gov
FEE BALANCE: $0 (zero)

SEE REVIEWER'S COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back in a few days as we have recently implemented new computer software.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Reviews section, click on Review Details
- Documents section, click on blue icon to the right of each document

YOUR NEXT STEPS: Submit the following items to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff

- Name your 3rd submittal documents to start with the submittal number, for example: 3_Plan_Set

To speak with a staff member on the telephone, please sign into the Virtual Zoning Counter: https://www.tucsonaz.gov/pdsd/virtual-walk-thru. The queue is open from 8:00 am -12:00 noon, Monday-Friday. This is similar to the City’s in-person counter. The difference is after you sign up, we will give you a call back.

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov

NOTE: The City of Tucson's Permit Counter at 201 N. Stone Avenue (the physical office) is closed to the public until further notice. In the meantime, our staff is working remotely from home. All communications are by telephone or email.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2020 SBEASLE1 OUT TO CUSTOMER Completed