Permit Number - DP19-0101
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2019 SBEASLE1 START PLANS SUBMITTED Completed
05/01/2019 MARTIN BROWN COT NON-DSD FIRE Approved
05/20/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/21/2019 ANDREW CONNOR LANDSCAPE REVIEW Approved
05/28/2019 DAVID RIVERA ZONING REVIEW Reqs Change From: David Rivera
PDSD Zoning Review Section

Project: Dp19-0101 - Commercial Use Group / Medical Services Outpatient Use Land Use
Pkg. Lot Re-stripe, Accessible Ramp, New Sidewalk
2325 N. Wyatt Drive - OCR-2 Zoning

TRANSMITTAL DATE: May 28, 2019

DUE DATE: May 29, 2019

***Please resubmit corrected drawings and any redlined copies along with a detailed response memo, which details how the Zoning Review Comments have been addressed.

CHECKLIST FOR MINOR DEVELOPMENT CHANGES TO EXISTING
COMMERCIAL/INDUSTRIAL SITES
Purpose
This standard has been prepared for the purpose of informing applicants of the submittal and review requirements for minor changes to existing commercial sites to assure proper and adequate information is presented in a consistent manner, thereby providing the basis for an efficient and timely review. The minor revisions to existing commercial sites are prepared in support of applications for building permits and related reviews.

The information that is requested establishes the basis upon which the project will be approved and could affect what is required of the property in the future, should there be a proposal for expansion or for a different use of the property. This standard does not waive any applicable city regulations or codes. Applicability

This standard shall be used for minor changes to existing commercial sites such as but not limited to; expansions less than 25%, in square footage of land area, floor area, lot coverage, or vehicular use area, modification to accessible vehicle parking, parking area restripe, etc. Applicability is to be determined by Zoning and/or Engineering review staff.

APPLICATION SUBMITTAL REQUIREMENTS
Development Package applications are available from PDSD. Completed applications and accompanying materials shall be submitted to PDSD. Incomplete or inaccurate applications will not be accepted. The types of documents and the specific number of copies required of each of the documents are on the PDSD website or may be obtained from PDSD. Resubmittals of development packages require a comment response letter that details how all previous comments have been addressed. Provide the same number of copies of the comment response letter as plans provided.


FORMAT REQUIREMENTS

2 COMMENT: List the DP case number DP19-0101 in the lower right corner of the plan sheet.

The title block shall include the following information and be provided on each sheet: The proposed name of the project, or if there is no name, the proposed tenant's name. A brief legal description is to be provided. The page number and the total number of pages in the package (i.e., sheet xx of xx). The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.


General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

1 COMMENT: List as a general note the existing zoning of the property.

"Existing zoning is ____."


2 COMMENT: List as a general note the Gross area of the property SF and Acreage.

List the gross area of the site by square footage and acreage.


3 COMMENT: Identify the existing and proposed use of the property as classified by the UDC; include any use specific standards.

Identify the existing and proposed use of the property as classified per the UDC
List all UDC sections applicable to the proposed uses.


4 COMMENT: List the GFA of the building as a general note.

Floor area for each building.


Information on Proposed Development:
The following information on the proposed project shall be shown on the drawing or added as notes.

1 COMMENT: Label the zoning classifications adjacent to the subject parcel.

All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined.


2 COMMENT: Parking will be verified once the GFA is listed. Revise the ADA parking sign to depict the 7 foot dimension from F.G. to the bottom of the lowest sign.

Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area


7 COMMENT: Label the overall building SF and height within the building footprint.
Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).

8 COMMENT: Correct the typo on keynote four (4) .


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: as noted above
05/28/2019 DAVID RIVERA ZONING HC REVIEW Reqs Change see zoning comments
05/29/2019 LOREN MAKUS ENGINEERING REVIEW Approved
05/30/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The reviews have been completed and a resubmittal is required.
Fee Balance: $577.50 (see the Balance column in the image below).
Activity Number: DP19-0101
Project Description: SITE - Marana Health Care, HC parking and accessible route improvements.
To view review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number.
(If information isn't shown yet, check back later as data flows to PRO periodically throughout the day.
After all corrections are made, please name your 2nd submittal documents accordingly, for example: 2_Plan_Set.
Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, please include the Activity Number.
1) Comment Response Letter (lists changes made to the Plan and which reviewer comments you are responding to)
2) Complete Plan Set (all pages, full set)
3) Any other items requested by review staff
After resubmittal, the plans will re-enter the standard 20-working-day review cycle. Prior to the completion of the next review, we require payment of the total fees (or the Review fees at a minimum). You may pay in person at the City of Tucson permit counter or mail a check payable to the City of Tucson (address is below). Please include the Activity Number on your check stub.
Thank you.
Sharon Beasley

City of Tucson
Planning and Development Services
Attn: Permit Counter
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
05/30/2019 SBEASLE1 OUT TO CUSTOMER Completed