Review Details: DEV PKG - RESUBMITTAL
Permit Number - DP19-0100
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2020 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
| 01/08/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved, show the existing utility information. [Initial comment: Revise the site drawing to include the following existing utility information: a. The location of water lines and fire hydrants. b. The location and size of sanitary sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number. c. The points of connection to existing public sewers. d. The locations of gas lines, electric and telephone lines, poles, and communications cables, on-ground junction boxes, and street lights. e. Any existing or proposed utility easements f. The first floor elevation for the building Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018.] |
| 01/10/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | DP19-0100 1) Previous Comment 1: Provide on plans waste stream calculations per City of Tucson (COT) Technical Standards Manual (TSM) section 8-01.8.0 showing that the existing service is sufficient for the building expansion 2) Previous Comment 2: Provide cumulative expansion calculations according to COT Unified Development Code (UDC) section 7.4.3.E |
| 01/10/2020 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | PLAN RETURNED FOR CORRECTIONS NOTICE A resubmittal with a Comment Response Letter is required. Description: SITE - Moose Lodge # 2475, tenant improvements and expansion. Restaurant/bar/private club. Permit/Activity Number: DP19-0100 Please include this number on all future correspondence. Project Manager: Nicholas.Ross@TucsonAz.gov, (520) 837-4029 Fee Balance: $0 (zero) View documents and reviewer's comments on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, left side, Activity Search, enter the Activity Number - Permits section, click on blue tab - Documents section, click on blue icon to the right of each document - Reviews section, click on Review Details YOUR NEXT STEPS: Submit the following items to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd - In the Project Description field, enter the Activity Number - Name your 3rd submittal documents accordingly, for example: 3_Plan_Set 1) Comment Response Letter (your response to the reviewer's Requires Change comments) 2) Plan Set (all pages, full set) 3) Any other documents requested by review staff Thank you. Sharon Beasley, Permit Specialist City of Tucson Planning and Development Services Attn: Permit Counter/Payments 201 N. Stone Avenue, 2nd Floor Tucson, AZ 85701 email: COTDSDPermits@TucsonAz.gov |
| 12/09/2019 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 12/13/2019 | MASHFOR1 | COT NON-DSD | FIRE | Approved | Note: A riser room has been added to the plan set to add fire srpinklers to the building as indicated by the comments. ***Fire Sprinkler deferred submittal shall be submitted to TFD for review. |
| 12/19/2019 | DAVID RIVERA | ZONING HC | REVIEW | Approved | |
| 12/19/2019 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: David Rivera PDSD Zoning Review Section PROJECT: Moose Lodge #2475 - Civic Use Group (Membership Organization) Development Package (2nd Review) - 2442 S. Harrison Road DP19-0100 - C-1 Zoning TRANSMITTAL DATE: December 19, 2019 DUE DATE: January 08, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is April 23, 2020. SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS) 2-06.3.0 FORMAT REQUIREMENTS CONTENT REQUIREMENTS 2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines. 1. COMMENT: 2-06.4.1 - List the Owner/developer's Contact name, phone number and email address. 2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses. 2. COMMENT: 2-06.4.7.A.4 - Revise general note 5 as follows; "The existing and proposed is Civic Use Group - Membership Organization subject to UDC Section 4.9.13.0." 2-06.4.7.A.8.c - Percentage of building, lot area, or vehicular use area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included; and, 3. COMMENT: 2-06.4.7.A.8.c - Include a building expansion calculation under general note 2. 2-06.4.9.H.4 - Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned. 4. COMMENT: 2-06.4.9.H.4 - Label Harrison Road and Golf Links Road as "Public Street". 2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided. 5. COMMENT: 2-06.4.9.H.5.d - Show the locations of the long and short term Facility locations. See UDC section 7.4.9 for specifics on the requirements such as location, security, design, and lighting. 2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s). 6. COMMENT: 2-06.4.9.Q - Label the use of the building within the building footprint. ***For additional information on the any standard presented in this memo, please refer to the City of Tucson "Unified Development Code" - Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations If you have any questions about this transmittal, Contact David Rivera on Tuesday, or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development pa |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/10/2020 | SBEASLE1 | OUT TO CUSTOMER | Completed |