Permit Number: DP19-0097
Parcel: 132130670

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP19-0097
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2019 SBEASLE1 START PLANS SUBMITTED Completed
11/21/2019 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: The Bridges - Block 2 - Central Park
Development Package (1st Review)
DP19-0097 - PAD 15 Zoning

TRANSMITTAL DATE: November 21, 2019
DUE DATE: December 10, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is April 18, 2020.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section


***The remaining comments one and two were not addressed in its entirety.
Previous comment one included three parts of which one was addressed the remaining two parts were not. Address the remaining parts of previous comment one. See comment one below.

Previous comment two was not addressed in its entirety. See remaining comment two and address as required. See comment two below.


2-06.3.4 - A title block shall be provided in the lower right quadrant of each sheet.

1. Follow up to previous comment 1: The title block and info that is located in the lower right corner on sheet one shall be included on all DP sheets.

The Bridges has a running table that includes all development including development criteria that is to be included on all development packages for this Planned Area Development. Include a separate sheet with the tracking table and information. Contact Steve Shields for assistance with the table

PREVIOUS COMMENT 1: The title block in the lower right corner of the cover sheet must be provided on each sheet in the same location.

Include on a separate sheet the tracking table that includes all current developments within the PAD.


2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

2. Follow up to previous comment 2: Include a dimensioned detail drawing of the type of facilities for the bicycle parking. According to the key note M, they are noted as "Bike Racks" which typical for short term facilities. See Article 7 of the UDC section 7.4.9 for short term bicycle facility dimensions. (It is acknowledged that location has been noted on the plan per key note M.)


PREVIOUS COMMENT 2: Are there any bicycle parking facilities proposed? If so indicate on the plans the location and types as noted by the standard above.

New comment: The remaining comments are minor and zoning is willing to do an over the counter digital review once the corrected plans have been uploaded and the over the counter review requested.

If you have any questions about this transmittal, Contact David Rivera on Tuesday, or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
12/05/2019 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Approved December 5, 2019

RE: DP19-0097 The Bridges, Block 2, Central Park, portions of section 25 and section 30, Recreational park development / 2nd Submittal, Received November 8, 2019

Thank you for the opportunity to comment on DP19-0097, The Bridges, Block 2, Central Park, portions of section 25 and section 30, Recreational park development; 2nd Submittal, a development package application for an approximately 7.4 acre site, located southwest of the intersection of East 36th Street and M L King Jr Way. The property is zoned Planned Area Development 15 (PAD-15), with the proposed development being a recreational park.
This site is within the Tucson International Airport avigation easement requirements and public disclosure area, and FAA traffic pattern airspace.

The Tucson Airport Authority approves the 2nd submittal of this project and has no additional comments to provide.

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.
Respectfully, Scott Robidoux, Senior Airport Planner

cc: jkuklinski@norris-design.com
12/05/2019 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved Previous Tucson Parks and Recreation Department comments have been adequately addressed. Tucson Parks and Recreation recommends approval of this development.
Howard B. Dutt, RLA
Landscape Architect
Tucson Parks & Recreation, (520) 837-8040
Howard.Dutt@tucsonaz.gov
12/09/2019 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approved Bridges, block 2 / DP19-0097 / 2nd submittal is Approved by Pima County Addressing.
Thank you,
Robin Freiman, Addressing Official
Pima County Development Services Department
201 N Stone AV – 4th Floor Tucson, AZ 85701, (520) 724-7570
12/09/2019 ANDREW CONNOR LANDSCAPE REVIEW Approved
12/19/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0097

1) Previous comment 2. 2) Please remove from the plans sheets E-0 thru E-6, these are electrical plan sheets and will need to be submitted and reviewed under a separate building permit. No electrical plan review will occur or has occurred under the development package
2) Figure 29 of the bridges Planned Area Development shows a 10' wide asphalt path on the west and east sides. The proposed plan shows an 8' wide path. Update path width as needed. A 8' wide path is still shown on the eastern side of the park. Update to show a 10' wide path as shown in the PAD

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
12/19/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
See details below - a resubmittal is required.

Permit/Activity Number: DP19-0097
Include this number on all future correspondence.

Project Description: SITE/GRADING/SWPPP - The Bridges, Block 2, Central Park, portions of section 25 and section 30. Recreational park development.

Fee Balance: $0 (zero)
To view documents and Reviewer's comments: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Documents section, click on blue icon to the right of each document
- Reviews section, click on "Review Details"

Submit the following items to the Filedrop.
In the Project Description field, enter the Activity Number.
PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff
4) Name your 3rd submittal documents accordingly, for example: 3_Plan_Set

HOLIDAY SCHEDULE, Dec. 23-27 (Mon-Fri): All City of Tucson Planning and Development permitting services and Cashier Services at the Public Works Building, 201 N. Stone Ave., (first floor) will be closed.
Beginning Dec. 30 (Mon), they will reopen at their new location on the second floor.

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, 3rd Floor
Tucson, AZ 85701
email: COTDSDPermits@TucsonAz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/19/2019 SBEASLE1 OUT TO CUSTOMER Completed