Permit Number: DP19-0085
Parcel: 117022020

Address:
930 N STONE AV

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP19-0085
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2019 SBEASLE1 START PLANS SUBMITTED Completed
04/18/2019 MARTIN BROWN COT NON-DSD FIRE Reqs Change Insufficient information. Need location of existing and/or proposed fire hydrants, with dimensions to property lines.
Need square footage of building. Need proposed occuancy classification and occupant load. If classified as an A-2, occupant load greater than 100 will require fire sprinklers.
04/26/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site drawing to include the following existing utility information:
a. The location of water lines and fire hydrants.
b. The location and size of sanitary sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
c. The points of connection to existing public sewers.
d. Any existing or proposed utility easements
e. The first floor elevation for the building
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2018.
05/06/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL
SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS
4.1 Identification and Descriptive Data

If landscaping is proposed the following applies:

A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Package will contain the following identification in the lower right corner of each sheet:
Any relevant case numbers for reviews or modifications that affect the site.

The site is within:

5.12.16 STONE/SIXTH AREA (SSA)
Infill Incentive District / DOWNTOWN LINKS SUBDISTRICT / Stone Sub-Area

Stone Sub-Area (STS)

The intent of the Stone Sub-Area is to promote higher density mixed use development along the Stone corridors. Benefits of this development include reduction in parking, zero lot lines and increases in allowable building heights.

Indicate graphically, where possible, compliance with Overlay zone.

SPECIFIC REQUIREMENTS

Adequate shade shall be provided for sidewalks and pedestrian pathways, using shade structures or vegetation.


If applicable, show compliance with landscaping by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required. In accordance with Section 2-10.0.0, Landscape Plan Requirements.

Note: Use of the Public Right-of-Way

Landscaping may be placed in the public right-of-way, if the following standards are met:

1. The landscaping is approved by the City Engineer or designee and complies with the City Engineer's standards on construction, irrigation, location, and plant type;

2. All vegetation complies with the standards of Section 7.6.4, Landscaping Standards; and,


3. The landscaping does not interfere with the use of the sidewalk.

Ensure that all Engineering and Zoning comments and concerns are addressed.

Additional comments may apply.
05/07/2019 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Provide a site plan/Development Package meeting the requirements of the minor change policy.
2. Include the Development Package activity number on each sheet near the title block. (DP19-0085)
05/08/2019 EHAMBLI1 ZONING HC REVIEW Reqs Change See Zoning Review comments.
05/08/2019 ELISA HAMBLIN ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Elisa Hamblin, AICP; Principal Planner

PROJECT: Bawker Bawker Beverages, 930 N Stone Av
Development Package (1st Review)
DP19-0085

TRANSMITTAL DATE: May 8, 2019
DUE DATE: May 7, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is March 6, 2020.

1. This submittal is lacking in required formatting and content. The next submittal must conform to administrative manual section 2-06. Additional formatting and content standards will be reviewed with the next transmittal. Additional comments forthcoming. Comments included in this transmittal are limited to development standards which may or may not be modified per the Infill Incentive District. Applicant assumes a certain amount of risk proceeding with the IID process with an incomplete development package.

2. 2-06.4.7.A.8.a - Provide the floor area for each building. This is used to determine several development standards. Approximate square footage of 2,719 was included with the application, but not on the plan set and is used for comments in this transmittal. Please verify accuracy of this number and include all buildings on site, including storage. Additional comments may be forthcoming.

3. 2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. As dimensions are not provided, it is unclear whether standards are met with this proposal.

4. 2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. The use proposed for this site is Alcoholic Beverage Service, with a Microbrewery as an accessory use. Vehicle parking is required at a ratio of 1:50 sq ft of gross floor area, totaling 54 spaces required. The submitted plan indicates 13 existing spaces provided on site. The most recent aerial imagery indicates 11 space located on site. Clarify the number provided on site in order to proceed with an IID modification. One accessible parking space is required, which must also meet van accessibility standards. Please note, accessible parking and routes are mandated by the building code and cannot be modified through the IID process.

5. 2-06.4.9.H.5.b - If any of the required parking is located off-site as permitted by the UDC, a drawing of that parking area is to be provided, together with the city's required parking agreement (include a copy of the lease agreement if applicable) must be provided. Please remember that in these situations, if the off-site parking location is a new parking area, it must comply with all parking area requirements and must be allowed as a principal use by the zoning classification of that property. If the off-site parking area location is an existing parking lot, the parking spaces utilized for the proposed land use must be non-required parking for the existing use for which the parking area was established.

6. 2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided. Bicycle parking for Alcoholic Beverage Service is required at a ratio of 1:2,000 sq ft of gross floor area, minimum 2 spaces, for short-term bike parking. For long-term parking the ratio is 1:12,000 sq ft gross floor area, minimum 2 spaces. This site would require 2 short-term and 2 long-term bike parking spaces.

7. 2-06.4.9.O - All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown. The building setbacks on this site are as follows: front/west is 21' or the height of the structure from the back of future curb. North and south setbacks are 0'. The rear/east setback is 1.5 times the height of the structure due to adjacency to a residential zone. Front and rear setbacks are not being met with existing structures on site.

8. 2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual. A sidewalk is required from the street to the front entrance of the building. Internal pedestrian circulation is also required. An accessible route must be provided from the accessible parking space to the front entrance of the building. Please note, accessible parking and routes are mandated by the building code and cannot be modified through the IID process.

9. 2-06.4.9.T - Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm.

10. 2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required.

If you have any questions about this transmittal, please contact me at Elisa.Hamblin@tucsonaz.gov or (520) 837-4966.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
05/09/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The reviews have been completed and a resubmittal is required.
Activity Number: DP19-0085
Project Description: SITE - Bawker Bawker Cider House, install bathroom, tap room, beer & wine bar.
To view review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number. (If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.) After all corrections are made, name your 2nd submittal documents accordingly, for example: 2_Plan_Set.
Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, include the Activity Number.
1) Comment Response Letter (lists changes made to the Plan and which reviewer comments you are responding to)
2) Corrected Plan Set (all pages, full set)
3) Items requested by review staff
After resubmittal, the plans will re-enter the standard 20-working-day review cycle. Prior to the completion of the next review, we require payment of the total fees (or the Review fees at a minimum). You can either pay in person at the permit counter or mail a check payable to the City of Tucson (address is below). Include the Activity Number on your check stub. The fee balance is $181.50 (activity# DP19-0085) + $66.50 for the Floodplain Use Permit (activity# T15OT00921). See the Balance columns in the images below.
NOTE: This development package cannot be issued a permit without payment of the Flood Use Permit fees.
The Project Manager can be reached via email or phone: Andrew.Connor@TucsonAz.gov, (520) 837-4950.
Thank you.
Sharon Beasley

City of Tucson
Planning and Development Services
Attn: Permit Counter
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
05/09/2019 SBEASLE1 OUT TO CUSTOMER Completed