Review Details: GRADING
Permit Number - DP19-0082
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2019 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Site Section Manager PROJECT: Wingate - Phase 1A & 1B Grading Plan (1st Review) DP19-0082 TRANSMITTAL DATE: April 29, 2019 DUE DATE: May 6, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. Zoning has reviewed the grading plan for compliance with DP19-0029 and although the grading plan appears to match the tentative plat zoning cannot approve the grading plan until the tentative plat is approved and all other Zoning comments have been addressed. 2. 2-06.4.3 - Provide the grading plan case number, DP19-0082, adjacent to the title block on all sheets. 3. Zoning cannot approve the grading plan until approved by Engineering and Landscape. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov |
| 05/03/2019 | ANDREW CONNOR | NPPO | REVIEW | Reqs Change | Landscape / NPP has reviewed the grading plan for compliance with DP19-0029 the grading plan appears to match the tentative plat but cannot approve the grading plans until the tentative plat is approved. Provide the grading plan case number, DP19-0082, adjacent to the title block on all sheets. Landscape section cannot approve the grading plan until all Engineering comments and concerns are addressed. |
| 05/07/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. Include a complete SWPPP report with the plans. 2. Incorporate the drainage report exhibits into the drainage report file to create a single document. 3. Please update the inspection information in note 26 on sheet 2: https://www.tucsonaz.gov/pdsd/scheduling-inspections. 4. On detail 13 on sheet 3, clearly show the existing and proposed grade outside of the cutoff wall. 5. Show relationship of splash pad surface to adjacent grades in detail 11/3. 6. Where PAG standard details are referenced, remove tag line indicating 2003 Edition. 7. Check page numbering for all sheets. Two sheets are marked as sheet 4. Both are marked "4 of 43." Ensure that all callouts reference the correct locations. 8. Spot grades, pad grades and detail 1/5 are not consistent. For example see the boundary between lots 101 and 73. It would help to show height of retained earth, slope grade and distance from property line to toe of slope at representative location. 9. Detail 12/3 indicates a future sidewalk. If this is to be part of Phase 1B, please indicate this. |
| 05/08/2019 | SBEASLE1 | ZONING-DECISION LETTER | WRITE DECISION LETTER | Reqs Change | PLAN RETURNED FOR CORRECTIONS NOTICE The reviews have been completed and a resubmittal is required. Activity Number: DP19-0082 Project Description: GRADING/SWPPP - Wingate, part of Lot 3, phase 1-A, an FLD subdivision. Lots 1-136, together with common areas "A" (open functional space, landscape, drainage and public and private utilities), "B" (drainage, landscape, public and private utilities). To view review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number. (If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.) After all corrections are made, name your 2nd submittal documents accordingly, for example: 2_Plan_Set. Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd. In the Project Description field, include the Activity Number. 1) Comment Response Letter (lists changes made to the Plan and which reviewer comments you are responding to) 2) Corrected Plan Set (all pages, full set) 3) Items requested by review staff After resubmittal, the plans will re-enter the standard 20-working-day review cycle. Prior to the completion of the next review, we require payment of the total fees (or the Review fees at a minimum). You can either pay in person at the permit counter or mail a check payable to the City of Tucson (address is below). Include the Activity Number on your check stub. The fee balance is $848.31 (see the Balance column in the image below). The Project Manager can be reached via email or phone: Loren.Makus@TucsonAz.gov, (520) 837-4927. Thank you. Sharon Beasley City of Tucson Planning and Development Services Attn: Permit Counter 201 N. Stone Avenue, First Floor Tucson, AZ 85701 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/08/2019 | SBEASLE1 | OUT TO CUSTOMER | Completed |