Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: DP19-0075
Parcel: 11616291A

Address:
829 N MAIN AV

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP19-0075
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2019 SBEASLE1 START PLANS SUBMITTED Completed
03/28/2019 SBEASLE1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Passed Review not required for solar installations.
03/28/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: DP19-0075 - Existing Development / Community Food Bank
Solar Canopies (1st Review)
845 N. Main Avenue - C-3 Zoning

TRANSMITTAL DATE: March 28, 2019

DUE DATE: March 28, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Label the DP case number DP19-0075 next to the title block.


02. COMMENT: Label the future curb location for Main Avenue and dimension the future back of curb to future property line.


03. COMMENT: Main Avenue is a Collector Street listed on the adopted COT Major Streets and Routes Map. The future right of way is a total of 100 feet with 50 foot half right of way. The future curb location is 11 feet from the future property line. Based on the proposed building setback labeled on the site plan the solar panels will not meet the required 21 feet from the back of future curb.

Two Panels can be removed to meet the future Right of way requirements of 21 feet.

Along the street perimeter yard a solar roof overhang may project into the required perimeter up to 4 feet.


04. COMMENT: Resubmit the revised drawings for review.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Plans
03/28/2019 SBEASLE1 WWM REVIEW Passed Review not required for solar installations.
04/02/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed