Permit Number: DP19-0065
Parcel: 141366750

Review Status: Completed

Review Details: GRADING

Permit Number - DP19-0065
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2019 ANDREW CONNOR NPPO REVIEW Approved
04/23/2019 DAVID RIVERA ZONING REVIEW Approved
04/29/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0065

1) Add DP19-0065 to all sheets
2) Remove the Development Package PDSD approval stamp and reserve the space for placement of a digital approval stamp
3) Add the required hold harmless note found in City of Tucson (COT) Administrative Manual (AM) 2-06.4.7
4) Show on plans the SWPPP number under which this work will operate. Provide a reference to the associated development that contains the overall SWPPP

Engineering can conduct an "over the counter" electronic review once the above comments have been addressed and a new work flow opened. Please email to schedule

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
04/29/2019 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The reviews have been completed and a resubmittal is required.
Activity Number: DP19-0065
Project Description: GRADING - La Estancia de Tucson, EPNG side channel outlets grading and common area "A" rainwater harvesting plan.
To view review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number. (If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.)
After all corrections are made, name your 2nd submittal documents accordingly, for example: 2_Plan_Set.
Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, include the Activity Number.
1) Comment Response Letter (lists changes made to the Plan and to which reviewer comments you are responding)
2) Corrected Plan Set (all pages, full set)
3) Items requested by review staff
After resubmittal, the plans will re-enter the standard 20-working-day review cycle.
Prior to the completion of the next review, we require payment of the total fees (or the Review fees at a minimum). You can either pay in person at the permit counter or mail a check payable to the City of Tucson (address is below). Include the Activity Number on your check stub.
The fee balance is $1,832.04 (see the Balance column in the image below).
The Project Manager can be reached via email or phone: Steve.Shields@TucsonAz.gov, (520) 837-4956. Thank you.
Sharon Beasley

City of Tucson
Planning and Development Services
Attn: Permit Counter
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2019 SBEASLE1 OUT TO CUSTOMER Completed