Permit Number: DP19-0058
Parcel: 109224470

Address:
5650 E RIVER RD

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP19-0058
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2019 SBEASLE1 START PLANS SUBMITTED Completed
06/06/2019 MASHFOR1 COT NON-DSD FIRE Approved
07/02/2019 ANDREW CONNOR LANDSCAPE REVIEW Approved
07/03/2019 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: Arizona Self Storage at Rio Verde Village - Storage Use / Personal Storage
Development Package (1st Review) 5650 E. River Road
DP19-0058 - PAD-22 Zoning

TRANSMITTAL DATE: July 3, 2019
DUE DATE: July 2, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is March 7, 2020.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

***Please address the follow up comments noted below. The standard and previous comments have been left as reference. Only address the follow up comments and any applicable new comments related to changes to the DP due to staff review.

***Please address only the follow up comments made by Zoning. The standard and previous comments have been left as reference for the reviewer and applicant responding to the responding back to the reviewers review comments.

1. Follow up to previous comment 3: The Administrative address was not added to sheets 5 through 15 as previous requested.

2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

Previous Comment 3: Provide the development package case number, DP19-0058, adjacent to the title block on each sheet.

List the administrative address next to the title block of sheets 5 through 15.

2. COMMENT: The zoning comment is minor and zoning is willing to do an over the counter digital review to assure that the remaining comments has been addressed. You can request the over the counter review once the corrected plans have been uploaded on the next submittal.

If you have any questions about this transmittal, Contact David Rivera on Tuesday, or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
07/03/2019 DAVID RIVERA ZONING HC REVIEW Approved
07/03/2019 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Reqs Change 1. Same comment from previous review: Provide a letter of approval from the PAD-22 Design Review Committee for all proposed architectural plans, at the time of development package resubmittal.

Alexandra Hines
837-6975
07/09/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0058

1) Sheet 1. Top middle of sheet "RIO VERDE VILLAGE PAD INDEX" is missing line work, only notations are called out. Add line work as needed
2) Engineering can conduct an "over the counter" electronic review once the above comment has been addressed and a new workflow opened. Please email to schedule

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
07/09/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The reviews have been completed and a resubmittal is required.
Fee Balance: $82.50 (see the Balance column in the image below). Prior to the completion of the next review, we require payment of the total fees (or the Review fees at a minimum). You may pay in person at the City of Tucson permit counter (Mon-Fri, 8:00 AM to 2:00 PM) or mail a check payable to the City of Tucson (see address below). Please write your Activity Number on the check.
Activity Number: DP19-0058
Project Description: SITE - Arizona Self Storage at Rio Verde Village - 3 above ground stories and one basement level story. A portion of Block "4" of Rio Verde Village, Blocks 1-9.
For review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number.
(If information isn't shown yet, check back later as data flows to PRO periodically throughout the day.)
After all corrections are made, please name your 3rd submittal documents accordingly, for example: 3_Plan_Set.
Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, please include the Activity Number.
1) Comment Response Letter (listing how all comments were addressed)
2) Complete Plan Set (all pages, full set)
3) Any other items requested by review staff
After resubmittal, the plans will re-enter the standard 20-working-day review cycle. The Project Manager can be contacted at: John.VanWinkle@TucsonAz.gov, (520) 837-5007.
Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter/Payments
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2019 SBEASLE1 OUT TO CUSTOMER Completed