Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP19-0058
Parcel: 109224470

Address:
5650 E RIVER RD

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP19-0058
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2019 SBEASLE1 START PLANS SUBMITTED Completed
03/12/2019 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Passed This agency was notified for their information only. A review is not required.
03/12/2019 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed This agency was notified for their information only. A review is not required.
03/12/2019 SBEASLE1 UTILITIES SOUTHWEST GAS Passed This agency was notified for their information only. A review is not required.
03/12/2019 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed This agency was notified for their information only. A review is not required.
03/13/2019 MASHFOR1 COT NON-DSD FIRE Reqs Change Fire Sprinklers will be required on this project if this is an S-1 for storage. Please also add fire hydrant locations to identify (water source) per the plan set.
04/04/2019 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved No existing or proposed Tucson Parks and Recreation facilities are affected by this development.

Howard B. Dutt, RLA, Landscape Architect
Tucson Parks & Recreation
(520) 837-8040
Howard.Dutt@tucsonaz.gov
04/04/2019 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
04/08/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole in the public sewer or private sewer collection system, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor. Floors discharging from above that reference point shall not discharge through the backwater valve. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.
04/09/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL
SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS
4.1 Identification and Descriptive Data
A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.
The Development Package will contain the following identification in the lower right corner of each sheet:
Any relevant case numbers for reviews or modifications that affect the site.
Indicate graphically compliance with conditions of PAD-22 document.
Ensure that all Zoning and Engineering comments and concerns are addressed.
Additional comments may apply
04/10/2019 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Reqs Change 1. The Rio Verde Village Planned Area Development states that under Section III, L. of the Design Review Committee on Pg. 96 states the following: The DRC shall review all proposed architectural plans. Through a self-certification process, the DRC will provide a letter of approval to the city at the time of plan submittal. The applicant must provide a letter of approval from the Design Review Committee for all proposed architectural plans, at the time of plan resubmittal. Please Submit required DRC letter for plan review.

Alexandra Hines
837-6975
04/18/2019 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: Arizona Self Storage at Rio Verde Village - Storage Use / Personal Storage
Development Package (1st Review) 5650 E. River Road
DP19-0058 - PAD-22 Zoning

TRANSMITTAL DATE: April 17, 2019
DUE DATE: April 10, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is March 7, 2020.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section


2-06.3.5 - A three-inch by five-inch space shall be reserved in the lower right quadrant of each sheet for an approval stamp.

1. COMMENT: Assure that there is a 5"x3" blank space next to the lower right corner of each sheet for the PDSD digital stamp.


2-06.3.10 - A legend that shows and describes all symbols used on the drawing is to be provided, preferably on the first sheet.

2. COMMENT: Include a legend on the cover sheet that describes the symbols and line work used on the drawings.


2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

3. COMMENT: Provide the development package case number, DP19-0058, adjacent to the title block on each sheet.

List the administrative address next to the title block of sheets 5 through 14.


2-06.4.4 - The project-location map to be located on the first sheet of the development package in the upper right corner, shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information.
2-06.4.4.A - Show the subject property approximately centered within the one square mile area;
2-06.4.4.B - Identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and,
2-06.4.4.C - Section, township, and range; section corners; north arrow; and the scale will be labeled.

4. COMMENT: Revise the location map to include the information listed in sections 2-06.4.4 - 2-06.4.4.C


2-06.4.6 - If the project is located within the boundaries of a Planned Area Development (PAD) zone, include a reduced-scale map of the PAD on the first sheet, indicating the location of the portion being developed.

5. COMMENT: Draw on the first sheet the overall PAD area as noted by the standard above.


2-06.4.7.A.1 - List as a general note: "Existing zoning is ____."

6. COMMENT: List under the site data text blocks on sheets 1 and 2, existing zoning is PAD 22.


2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

7. COMMENT: List on sheet one and two under the Site Data the applicable use specific standard for this use as listed in the PAD document and the UDC equivalent.


2-06.4.7.A.6 - If a plan or plat is prepared in conjunction with other applications or overlays or the parcel being developed is subject to conditions of an application processed previously, additional information must be added to the plan. Such applications and overlays include, but are not limited to: annexations; rezonings; special exceptions; Board of Adjustment variances; Design Development Options; Technical Standard Modification Request; overlays (Airport Environs Zone, Environmental Resource Zone, Gateway Corridor Zone, Hillside Development Zone, Historic Preservation Zone, Major Streets and Routes, Rio Nuevo District, Scenic Corridor Zone, WASH); Modification of Development Regulations through the Downtown Area Infill Incentive District or Rio Nuevo District; Downtown Heritage Incentive Zone; or, Design Review Board. Provide the following information on the plan.

8. COMMENT: Include a general note that states that his development has been designed to comply with the Adopted Major Streets and Routes Plan UDC Section 5.4 or as allowed by the PAD.

This project is proposed within an ERZ overlay area and is subject to compliance with the requirements of the Environmental Resource Zone Regulations. Add a general note that states that this project has been designed to comply with the regulations of the ERZ overlay UDC Section 5.7 or as allowed by the PAD.

Demonstrate on the DP, compliance with the SCZ requirements allowed within the PAD document.


2-06.4.7.A.6.a - List additional applications and overlays, by case number (if applicable), in lower right corner of each sheet. As a general note provide the type of application processed or overlays applicable, a statement that the project meets the criteria/conditions of the additional application or overlay, the case number, date of approval, what was approved, and the conditions of approval, if any.

9. COMMENT: If applicable, list any overlay application case numbers next to the title block of all plan sheets.


2-06.4.7.A.8.a - Floor area for each building;

10. COMMENT: Clarify if there are two separate buildings or areas proposed as an office and an apartment? If so list the square footage of each under the site data text block.


2-06.4.8.A - Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system.

11. COMMENT: Label the site boundary of the parcel to be developed as noted by the standard above.


2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided.

12. COMMENT: If applicable, to this parcel include in the DP the easement information as noted by the standard above.


2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

13. COMMENT: Label the width of the existing sidewalk along the River Road ROW.


2-06.4.9.A - Draw in all proposed lot lines with approximate distances and measurements.

14. COMMENT: Same as comment 11.


2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. If the property is being rezoned, use those boundaries and classifications. The basis for this requirement is that some zoning requirements on a project are based on the zoning classification of adjacent property. Also, in some instances, each zone has to be taken into consideration on property that is split by two or more zoning classifications, as each may have different requirements.

15. COMMENT: Label the existing zoning classifications adjacent to the subject parcel and across River Road.


2-06.4.9.H.2 - Show future and existing sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section.

16. COMMENT: Include the SVT information as noted by the standard above.


2-06.4.9.H.5.c - Show all loading zones, vehicle maneuverability fully dimensioned, and access route. Provide as a note the number of loading spaces required, the number provided, whether the loading space is a Type A or B as provided in UDC Section 7.5.4.

17. COMMENT: On sheet 2, label the southern loading area.


2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

18. COMMENT: This project must be provided with a minimum of 2 Short term bicycle parking facilities. Draw and label the short term facilities. Include a bicycle parking calculation under the site data text block and a fully dimensioned detail drawing. The facilities must be within 50 feet of the public entrance to the storage facility.


2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).

19. COMMENT: Label the building height within the building footprint as noted by the standard above.


2-06.4.9.S - Show existing or proposed pedestrian circulation along abutting rights-of-way. Such sidewalks must comply with accessibility requirements for the physically disabled and the design criteria in Section 10-01.0.0, Street Technical Standards, of the Technical Standards Manual.

20. COMMENT: Label the width of the existing public sidewalk on River Road.

Label the cross and horizontal slopes for all sidewalks adjacent to the proposed building.


2-06.4.9.V - For gang mailboxes indicate location to assure there are no conflicts with other requirements, such as pedestrian accessibility, utilities, and landscaping.

21. COMMENT: Clarify if there is main mailbox location for all the developments within this PAD or is mail provided to each development? If there is a gang mailbox location indicate it on the plan.


2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required.

22. COMMENT: Clarify if there are freestanding monument signs proposed for this project. If so draw and label the location and include a note that the signage will be permitted under separate permit.



If you have any questions about this transmittal, Contact David Rivera on Tuesday, or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
04/18/2019 DAVID RIVERA ZONING HC REVIEW Reqs Change See zoning comments
04/18/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0058

1) Provide a cover sheet that includes all standard applicable details and notes found in the City of Tucson (COT) Administrative Manual (AM) section 2-06, including but not limited to the hold harmless note in AM 2-06.4.7
2) Provide a SWPPP manual and include and add a SWPPP plan sheet into the drawing package upon next submittal
3) It is not clear if bank protection for the no-name wash is being proposed. Show how this development meets the requirements of Tucson City Code Chapter 26-7. Erosion Setbacks apply to the supporting foundation elements. Also reference City of Tucson Drainage manual section 7.4. Foundation elements may not be placed within the erosion hazard setback
4) Sheet 2 of 14. Note, "BUILDING BUILT ON PIERS TO ACCOMMODATE DRAINAGE BELOW". Show the location of all foundation elements in relation to the wash channel and the erosion hazard setback
5) Show how bank protection along the no-name wash will be utilized to reduce the erosion hazard setback
6) There appears to be highly localized scour immediately south of the culvert crossing the onsite private drive which appears to be the result of a Channel Drop. Include a scour analysis for this referencing Standards Manual for Drainage Design section 6.6.6 in any bank protection design
7) Sheet 4. Callout Q is not identified in the Keynotes, update as needed
8) Sheet 3. Accessible parking detail. Minimum clearance to lowest site is 7'. Update as needed
9) Provide a trash enclosure detail to meet TSM section 8
10) Sheet 3. Assessable Stall detail references Detail 8A/Sp-2. This detail cannot be found. Add note to plans that all curb access ramps will comply with ICC A117.1
11) Provide grading cut/fill quantities in cubic yards
12) Provide on plans waste stream calculations per TSM section 8-01.8.0

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
04/19/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The reviews have been completed and a resubmittal is required.
Activity Number: DP19-0058
Project Description: SITE - Arizona Self Storage at Rio Verde Village - 3 above ground stories and one basement level story. A portion of Block "4" of Rio Verde Village, Blocks 1-9.
To view review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number. (If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.)
After all corrections are made, name your 2nd submittal documents accordingly, for example: 2_Plan_Set.
Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, include the Activity Number.
1) Comment Response Letter (lists changes made to the Plan and to which reviewer comments you are responding)
2) Corrected Plan Set (all pages, full set)
3) Items requested by review staff
After resubmittal, the plans will re-enter the standard 20-working-day review cycle. The fee balance is $0 (zero).
The Project Manager can be reached via email or phone: John.VanWinkle@TucsonAz.gov, (520) 837-5007.
Thank you.
Sharon Beasley

City of Tucson
Planning and Development Services
Attn: Permit Counter
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
04/19/2019 SBEASLE1 OUT TO CUSTOMER Completed