Permit Number: DP19-0057
Parcel: 10408092B

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP19-0057
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2019 SBEASLE1 START PLANS SUBMITTED Completed
05/07/2019 ANDREW CONNOR LANDSCAPE REVIEW Approved
05/13/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change 1) Add to note 26 on sheet C2 and note 14 on C4 the maximum cross slope and running slope. Add "All accessible pathways to comply with ICC A117.1"

Engineering can conduct an expedited electronic review once the above comment has been addressed. Please email to schedule
05/14/2019 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
05/29/2019 DAVID RIVERA ZONING HC REVIEW Approved
05/29/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The reviews have been completed and a resubmittal is required.
Note: This email is being sent according to our standard procedures. We just received your new resubmittal documents today. Thank you.
Activity Number: DP19-0057
Project Description: SITE/GRADING - Jim Click Chrysler Jeep - expansion, remodel, and exterior image improvements.
To view review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number.
(If information isn't shown yet, check back later as data flows to PRO periodically throughout the day.)
After all corrections are made, please name your 3rd submittal documents accordingly, for example: 3_Plan_Set.
Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, enter the Activity Number and other pertinent information.
1) Comment Response Letter (lists changes made to the Plan and which reviewer comments you are responding to)
2) Complete Plan Set (all pages, full set)
3) Any other items requested by review staff
After resubmittal, the plans will re-enter the standard 20-working-day review cycle. The fee balance is $0 (zero). The Project Manager can be reached via email or phone: Nicholas.Ross@TucsonAz.gov, (520) 837-4029.
Thank you.
Sharon Beasley

City of Tucson
Planning and Development Services
Attn: Permit Counter
201 N. Stone Avenue, First Floor
Tucson, AZ 85701
05/29/2019 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: Jim Click Chrysler - Retail - Auto Sales Use
Development Package (2nd Review)
DP19-0057 - C-3 Zoning - 701 W. Auto Mall Drive

TRANSMITTAL DATE: May 29, 2019
DUE DATE: May 30, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is March 7, 2020.


1. COMMENT: Per your response to previous comment 10, all required parking is labeled with a circle and a number. Also the response states that the PAALS where required parking is located are dimensioned. Dimension the PAALs where all required parking spaces are located.

Per our conversation on May 29, it was suggested that the parking spaces labeled as required along the south boundary of the site be changed to display vehicle spaces due to the non-compliant PAAL width.

Previous Comment 10: Clearly define the vehicle display spaces and the required parking spaces. Dimension the PAALs adjacent to the required parking spaces. Vehicle display spaces do not count towards the number of required parking spaces for the use.

2. COMMENT: The remaining comment is minor and can be reviewed via a digital over the counter review. Zoning is willing to review the changes as a over the counter review once the plans are corrected and uploaded. Please send CDRC staff an email request for the digital over the counter review.



If you have any questions about this transmittal, Contact David Rivera on Tuesday, or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package

Final Status

Task End Date Reviewer's Name Type of Review Description
05/29/2019 SBEASLE1 OUT TO CUSTOMER Completed