03/25/2019 ANDREW CONNOR NPPO REVIEW Reqs Change This project is s related to DP18-0293; list this case number next to the tile block next to the other reference case numbers.

Grading plan cannot be approved until the tentative plat DP18-0293 is approved.
03/25/2019 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: DP19-0045 - Related to DP18-0293
Grading Plan (1st Review)
6995 E Camino Boleadoras

TRANSMITTAL DATE: March 21, 2019

DUE DATE: March 21, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: List next to the title block the reference case numbers listed on the tentative plat DP18-0293.

This project is specifically related to DP18-0293; list this case number next to the tile block next to the other reference case numbers.


02. COMMENT: List the email address for the Owner / Developer.


03. COMMENT: Zoning has no adverse comments related to the grading plan but cannot approve it until the PDSD Engineering and Landscape reviewers have approved the grading plan the tentative plat DP18-0293 is approved.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Grading Plan pre reviewer's comments
04/02/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0045

1) Per City of Tucson Administrative Manual (AM) section 2-06.4.7.B add the required hold harmless note and drainage will remain it is natural state note to the submitted plans
2) DP18-0293, which is the tentative plat, shows two different lot grading schemes, one based on the high side of the lot and the other based on the low side of the lot. DP19-0045 shows only one as being based on the highpoint. Please clarify which plan is applicable
3) DP18-0293 shows two retaining wall cross sections, DP19-0045 shows only one. Please clarify which is applicable
4) Engineering can conduct an over the counter electronic review once the above comment has been addressed and a new work flow opened. Please email to schedule

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
04/03/2019 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The reviews have been completed and a resubmittal is required.
Activity Number: DP19-0045
Project Description: GRADING/SWPPP - La Estancia de Tucson, Block 26, Lots 1-47, Common areas "A" and "B".
To view review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number. (If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.) After the necessary corrections have been made, name your documents accordingly - a 2nd submittal document would be titled: 2_Plan_Set. Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, enter the Activity Number.
1) Comment Response Letter (lists changes to the Plan and which reviewer comments are being addressed)
2) Corrected Plan Set (all pages, full set)
3) Items requested by review staff
After resubmittal, the plans will re-enter the standard 20-working-day review cycle. The fee balance is $0 (zero).
The Project Manager can be reached via email: Steve.Shields@TucsonAz.gov or phone: (520) 837-4956.
Thank you.
Sharon Beasley

City of Tucson
Planning and Development Services
Attn: Permit Counter
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
04/03/2019 SBEASLE1 OUT TO CUSTOMER Completed