Permit Number: DP19-0041
Parcel: 128030090

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP19-0041
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2019 SBEASLE1 START PLANS SUBMITTED Completed
02/27/2019 MASHFOR1 COT NON-DSD FIRE Approved
03/18/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL
SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS
4.1

Identification and Descriptive Data

A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.

The Development Plans will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

List the DP case number DP19-0041, next to the title block.

7.6.4. LANDSCAPE STANDARDS

Street Landscape Borders

Located on Site

Street landscape borders must be located entirely on site, except that, if approved by the City Engineer or designee, up to five feet of the required ten foot width may be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets.

Obtain permission for use of ROW


SECTION 4-01.0.0: COMMERCIAL RAINWATER HARVESTING
Applicability:

All commercial development plans submitted after June 1, 2010.

A separate Water Harvesting Implementation Plan shall be submitted with all applications for new commercial developments where landscaping is required. The plan shall detail the landscape water demand and the harvested water supply needed to meet 50 percent of landscape demand.

Provide water budget data, along with the background data and assumptions used to develop it.

Ensure that all Zoning and Engineering comments and concerns are addressed.

Additional comments may apply.
03/20/2019 DAVID RIVERA ZONING HC REVIEW Reqs Change see zoning comments
03/20/2019 SBEASLE1 PIMA COUNTY ADDRESSING Reqs Change **The PDF attachment mentioned here can be viewed on PRO in the "Documents" section**

The Addressing review of DP19-0041 Jersey Mike's and Smoothie King, 1st Submittal, is being Returned for Corrections by Pima County Addressing. The attached pdf contains Addressing’s comments. Please let me know if you have any questions.
Thank you,
Robin Freiman, Addressing Official
Pima County Development Services Department
201 N Stone Ave, 4th Floor, Tucson, AZ 85701
(520) 724-7570
03/20/2019 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: Jersey Mikes and Smoothie King - Commercial Use / Food Service and Retail Use space
Development Package (1st Review)
DP19-0041 - C-1 Zoning / 5720 E. Broadway Boulevard

TRANSMITTAL DATE: March 20, 2019
DUE DATE: March 19, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is February 14, 2020.


CONTENT REQUIREMENTS

2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.

1. COMMENT: On the cover sheet, list the email address for Bruce Brown and include the registrant's information for Steve Acuña.


2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

2. COMMENT: Provide the development package case number, DP19-0041, adjacent to the title block on each sheet.


2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

3. COMMENT: Revise general note 6 to include the specific use under the Retail Use Group. Once the specific use is determined include the applicable Use Specific Standards.


2-06.4.7.A.6 - If a plan or plat is prepared in conjunction with other applications or overlays or the parcel being developed is subject to conditions of an application processed previously, additional information must be added to the plan. Such applications and overlays include, but are not limited to: annexations; rezonings; special exceptions; Board of Adjustment variances; Design Development Options; Technical Standard Modification Request; overlays (Airport Environs Zone, Environmental Resource Zone, Gateway Corridor Zone, Hillside Development Zone, Historic Preservation Zone, Major Streets and Routes, Rio Nuevo District, Scenic Corridor Zone, WASH); Modification of Development Regulations through the Downtown Area Infill Incentive District or Rio Nuevo District; Downtown Heritage Incentive Zone; or, Design Review Board. Provide the following information on the plan.

4. COMMENT: List the MS&R and Gateway Route UDC Section 5.4 and 5.5 (respectively) numbers in general note 7.


2-06.4.9.A - Draw in all proposed lot lines with approximate distances and measurements.

5. COMMENT: This site is comprised of 6 individual parcels. Prior to approval of the DP, a Parcel tax combo must be completed through the Pima County Assessor's Office. Provide the Parcel Combo documentation from Pima County.


2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

6. COMMENT: There are only 3 Recharge stations drawn on the plan. Revise the reduction calculation for the recharge station to 3, currently noted as 4. Draw and label the charging stations on the plan.

Label on the landscape plan the additional 8 canopy trees that will be planted for the reduction of 2 vehicle parking spaces. Demonstrate compliance with for the additional trees: The planting area for each tree must comply with the canopy tree in vehicular use area spatial requirements in accordance with Section 7.6.4.B.1.a.

Label the 7'-0" height from the bottom of the van sign to the top of the sidewalk.


2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

7. COMMENT: Demonstrate compliance for the long term facilities. Review section 7.4.9.D.2.b and .c; draw the location of the facility within each of the buildings.

Clarify if the long term facility within the building is going to be a box as shown on sheet 5.

2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.

8. COMMENT: Include in keynote 13 that the longitudinal slope will not exceed 5% for sidewalks.


2-06.4.9.T - Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm.

9. COMMENT: See engineering comments related to the Refuse collection area.


If you have any questions about this transmittal, Contact David Rivera on Tuesday, or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
03/21/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/26/2019 LOREN MAKUS ENGINEERING REVIEW Needs Review 1. Aerial photos of the development site show overhead utility lines in the alley. Clearly show the line locations on the plans.
2. It appears the overhead lines may interfere with trucks servicing the solid waste enclosure. Provide concurrence from Environmental Services for acceptance of this location and service area.
3. Show the proposed conditions for the east side of the eastern driveway.
03/27/2019 ALEXANDRA HINES ZONING-DECISION LETTER REVIEW Reqs Change Plans Returned for Corrections (RFC) Notice: DP19-0041
Project Description: SITE/GRADING - Jersey Mike's and Smoothie King, Food service and retail

The review has been completed and a resubmittal is required.

To see review comments about the plans, visit PRO at www.tucsonaz.gov/PRO, then search by activity number. (If new comments aren't shown yet, please check back later as data flows to PRO at periodic intervals throughout the day.)

Prepare a Comment Response Letter for the reviewers detailing what changes have been made to the plan and what review comments are being addressed. After the necessary corrections have been made to the plans, please submit the following items to PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd:
1) Comment Response Letter
2) Corrected plan set
3) Items requested by review staff

The plans will then re-enter the 20 working day review cycle.Please type the activity number in the Project Description and name the files as described on the PDSD Filedrop web page.

The current fee balance is $0.
Mark Castro, copied, is the Project Manager to contact with any questions,
email: Mark.Castro@TucsonAz.gov, or phone: (520) 837-4979.
Alexandra Hines

City of Tucson
Planning and Development Svcs. Dept.
201 N. Stone Ave, 1st Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
03/27/2019 AHINES2 OUT TO CUSTOMER Completed