Review Status: Completed

Review Details: DEV PKG

Permit Number - DP19-0031
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2019 SBEASLE1 START PLANS SUBMITTED Completed
02/12/2019 NICHOLAS ROSS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Nick Ross
Lead Planner

PROJECT:
Development Package (1st Review)
DP19-0031

TRANSMITTAL DATE: March 18, 2019

DUE DATE: March 11, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is March 18, 2020.

1. Include "DP19-0031" on every sheet of the plans

2. 2-06.4.7.A.8.a - Floor area for each building;

Comment: Include SF within the building footprint on the plans.

3. 2-06.4.7.A.8.c - Percentage of building, lot area, or vehicular use area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included; and,

Comment: See Comment 7 and address accordingly.

4. 2-06.4.9.A - Draw in all proposed lot lines with approximate distances and measurements.

Comment: Please identify all parcels associated with the site on the plans.

5. 2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

Comment: A pedestrian refuge area/sidewalk adjacent to the new building is required. See Section 7-01.4.0 for specifics. Please provide the PAAL width adjacent to the required pedestrian refuge area on north side of the new addition.

6. 2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

Comment: Parking Calculations do not seem to accurately match Building Area Calculations. Please revise and ensure no additional parking will be required.

If you have any questions about this transmittal, please contact me at Nicholas.Ross@tucsonaz.gov or (520) 837-4029.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
02/12/2019 NROSS1 ZONING HC REVIEW Reqs Change
02/26/2019 MASHFOR1 COT NON-DSD FIRE Approved If modifications to the existing Fire Sprinkler/Alarm system occur during the TI please provide the deferred submittal to Tucson Fire Dept
03/06/2019 ANDREW CONNOR LANDSCAPE REVIEW Approved
03/11/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Remove the COMcheck Envelope Compliance Certificate from the development plan. An approved development plan is not to be used for construction or modification of on-site utilities (e.g. water service to buildings, building sewers, site lighting, electrical service to buildings, etc.).
2. Revise the site drawing to include the following existing utility information:
a. The location and size of public water lines,
b. The location and size of sanitary and storm sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number.
c. The points of connection to existing public sewers.
d. The first floor elevation for the building
Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2012.
03/18/2019 LOREN MAKUS ENGINEERING REVIEW Approved
03/19/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The reviews have been completed and a resubmittal is required.
Activity Number: DP19-0031
Project Description: SITE - Chapman Used Cars Speedway, enclose existing canopy, demo existing 68sf, add new 668sf, remove asphalt.
To view review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number. (If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.)
After the necessary corrections have been made, name your documents accordingly - a 2nd submittal document would be titled: 2_Plan_Set.
Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd. In the Project Description field, enter the Activity Number.
1) Comment Response Letter (lists changes to the Plan and which review comments are being addressed)
2) Corrected plan set with all documents (the full set)
3) Items requested by review staff
After resubmittal, the plans will re-enter the standard 20-working-day review cycle. The fee balance is $0 (zero). The Project Manager can be reached via email: Andrew.Connor@TucsonAz.gov or phone: (520) 837-4950.
Thank you.
City of Tucson
Planning and Development Services
Attn: Sharon Beasley
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2019 SBEASLE1 OUT TO CUSTOMER Completed