Permit Number: DP19-0004
Parcel: 13013042A

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP19-0004
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2019 SBEASLE1 START PLANS SUBMITTED Completed
06/25/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The site plan shows the building sewer connecting to the public sewer downstream of manhole 1769-01 but you are providing the rim elevation for manhole 9838-01. Determine to which public sewer the building sewer is connected and provide the appropriate manhole rim elevation. [Second comment: Provide the rim elevation of the upstream manhole; it appears to be manhole 1769-01.] [Initial comment: Revise the site drawing to show the point of connection of the building sewer to the public sewer. Reference Section 107.2.1, IBC 2018.]
07/05/2019 DAVID RIVERA ZONING REVIEW Approved
07/05/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The reviews have been completed and a resubmittal is required.
The fee balance is $0 (zero).
Activity Number: DP19-0004
Project Description: SITE - Flooring Systems of Arizona, building addition.
For review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number.
(If information isn't shown yet, check back later as data flows to PRO periodically throughout the day.)
After all corrections are made, please name your 4th submittal documents accordingly, for example: 4_Plan_Set.
Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd.
In the Project Description field, please include the Activity Number.
1) Comment Response Letter (listing how all comments were addressed)
2) Complete Plan Set (all pages, full set)
3) Any other items requested by review staff
After resubmittal, the plans will re-enter the standard 20-working-day review cycle.
Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
07/05/2019 SBEASLE1 OUT TO CUSTOMER Completed