Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2019 SBEASLE1 START PLANS SUBMITTED Completed
01/17/2019 MASHFOR1 COT NON-DSD FIRE Approved
02/04/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the site drawing to show the point of connection of the building sewer to the public sewer. Reference Section 107.2.1, IBC 2018.
2. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
02/07/2019 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: Flooring Systems of Arizona - General Manufacturing Use
Development Package (1st Review)
DP19-0004 - I-1 Zoning / 3501 E. Golf Links Road
1848 SF Addition Less than 25% expansion / New parking lot design


TRANSMITTAL DATE: February 7, 2019
DUE DATE: February 12, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is January 1, 2020.


2-06.3.5 - A three-inch by five-inch space shall be reserved in the lower right quadrant of each sheet for an approval stamp.

1. COMMENT: Remove the Development Package PDSD approval stamp from all sheets. Reserve a three-inch by five-inch space in the lower right quadrant of each sheet for an approval stamp. The approval stamp will be applied electronically by PDSD staff.


2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.

2. COMMENT: On the cover sheet: List the contact person's name, telephone number, and email address for the Owner's information. List the name and email address for the Landscape architect information.


2-06.4.2 - The title block shall include the following information and be provided on each sheet:
2-06.4.2.B - A brief legal description and a statement as to whether the project is a re-subdivision are to be provided. On re-subdivisions, provide the recording information of the existing subdivision plat;

3. COMMENT: Include a brief legal description in the title block of all plan sheets. The description shall be consistent on all sheets.


2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

4. COMMENT: Provide the development package case number, DP19-0004, adjacent to the title block on each sheet.


2-06.4.4 - The project-location map to be located on the first sheet of the development package in the upper right corner, shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information.

5. COMMENT: Draw and label the jurisdictional limits.


2-06.4.7.A.6 - If a plan or plat is prepared in conjunction with other applications or overlays or the parcel being developed is subject to conditions of an application processed previously, additional information must be added to the plan. Such applications and overlays include, but are not limited to: annexations; rezonings; special exceptions; Board of Adjustment variances; Design Development Options; Technical Standard Modification Request; overlays (Airport Environs Zone, Environmental Resource Zone, Gateway Corridor Zone, Hillside Development Zone, Historic Preservation Zone, Major Streets and Routes, Rio Nuevo District, Scenic Corridor Zone, WASH); Modification of Development Regulations through the Downtown Area Infill Incentive District or Rio Nuevo District; Downtown Heritage Incentive Zone; or, Design Review Board. Provide the following information on the plan.

6. COMMENT: This site is within the Davis Monthan AEZ Overlay Area and is subject to compliance with the applicable performance standards. The site is located within the ADC-1 and NCD-A and AHD 140-160 Height limits.

Label the MSL elevation of the site. Include a height calculation between the MSL elevation of the end of DM NW runway 2590 and the MSL of the site. Refer to UDC section 5.6.11 for information on the calculation.

Add a note that the addition will meet the noise decibel 65-70 Ldn for uses other than for places of public accommodation or Administrative and professional Office use which must meet a 4-45 Ldn.

Add a general note that the project has been designed to comply with the UDC Section 5.6 AEZ requirements


2-06.4.7.A.8.b - Percentage and area in square feet of building and accessory building coverage;

7. COMMENT: Under the UDC there is no lot coverage maximum and therefore the lot coverage calculation is not required. There is also no more floor area ratio maximum requirement in the UDC tables for commercial uses, except if the project is within the Airport Environs overlay. As noted in comment six, this site is within the DM AEZ ADC-1 and one of the performance criteria is a maximum of .50 Floor area ratio allowed. Revise the lot coverage note and calculation to a FAR calculation.


2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided.

8. COMMENT: Label the recordation of the 10' easement.


2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

9. COMMENT: Label the recordation data for Golf Links Road.


2-06.4.9.H.3 - Indicate fire circulation, including accessibility and vehicle maneuverability.

10. COMMENT: Clarify how accessibility to the refuse area is to be provided when parking spaces are directly in front the refuse location.


2-06.4.9.H.4 - Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned.

11. COMMENT: Label Golf Links Road as "Public".


2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

12. COMMENT: Label the width of the driveway entrance, the PAAL width between the east side parking spaces and the extruded curbing for the landscape island.


2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

13. COMMENT: The three parking spaces along the south property line include a 2'-6" overhang dimension that is only 1'-6". Revise the design to clearly show a 2'-6" overhang.


2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

14. COMMENT: Draw the location of the long term bicycle parking facilities. Include a dimensioned detail drawing of the specific location. See UDC section 7.4.9.D for Long Term facility design requirements.


2-06.4.9.O - All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.

15. COMMENT: The building setbacks for this development are based on the greatest of 20 feet or 1.5 times the height from the property line. Label the building setback from the property line to the addition.


2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).

16. COMMENT: Clarify if a portion of the second story will be cantilevered? Include a detail of the south elevation of the new addition. (Just for clarification, does the 1848 sf include the second story?) Dimension the addition first and second floors.


2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.

17. COMMENT: Add to note 12 on sheet 2 that the longitudinal slope will not exceed 5%.


2-06.4.9.T - Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm.

18. COMMENT: See engineering review comments related to the refuse design requirements.


2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required.

19. COMMENT: If applicable indicate the location of any proposed signage. If no signage is proposed under this plan add a general note that states that signage will be permitted under separate permit.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
02/07/2019 DAVID RIVERA ZONING HC REVIEW Reqs Change see zoning comments.
02/08/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP19-0004

1) Clarify if accessible parking space is flush with the curb or below the curb. If so the accessible loading zone should need a curb access ramp to get onto the sidewalk. Provide detail on plans for the missing curb access ramp, including detectable warnings
2) Add note to plans that all curb access ramps/accessible paths are to comply with ICC A117.1
3) Show on plans the location of the entrance to the proposed addition
4) If possible with existing grades, provide curb cuts into the proposed landscape areas to allow rain water to enter
5) Provide top/bottom spot grades for all proposed water harvesting areas to show that an effective ponding depth is maintained. Note that the spot grades should take into account any mulch or ground cover that is used
6) Provide on plans waste stream calculations per City of Tucson (COT) Technical Standards Manual (TSM) section 8-01.8.0 to confirm that the proposed addition has the necessary service
7) It's not clear how the existing dumpster will be serviced since it is blocked by parking spaces. The parking spaces need to be moved or a new trash enclosure/service area be provided
8) Provide dimensions for the Parking Area, depth, width, including the entry

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
02/11/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The review has been completed and a resubmittal is required.
Activity Number: DP19-0004
Project Description: SITE - FLOORING SYSTEMS OF AZ, building addition
To see review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number. (If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.)
Prepare a Comment Response Letter detailing changes to the plan and which review comments are being addressed. After the necessary corrections have been made, submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd. Please enter the Activity Number in the Project Description field and name the file as directed, for example, second submittal: 2_Plan_Set.pdf. The plans will then re-enter a 20-working-day review cycle.­
1) Comment Response Letter
2) Corrected plan set with all documents
3) Items requested by review staff
The current fee balance is $ 495.00 (see image below). Review fees must be paid prior to the next submittal review. Please include the Activity Number on your check stub.
Thank you.

Sharon Beasley
City of Tucson
Planning and Development Services
201 N. Stone Avenue, First Floor
Tucson, AZ 85701
02/11/2019 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL
SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS
4.1 Identification and Descriptive Data
A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.
The landscape plan will contain the following identification in the lower right corner of each sheet:
Any relevant case numbers for reviews or modifications that affect the site.
5.4. MAJOR STREET AND ROUTES SETBACK ZONE (MS&R)
5.4.2. APPLICABILITY

The MS&R standards apply to the following uses on property, any portion of which abuts or is adjacent to a street designated on the City's or County's MS&R Plan:
A. New structures;
B. Changes of use, including new structures occurring on vacant land;
C. Uses of land or structures legally existing as of June 27, 1988, that are expanded in floor area, lot coverage, parking, seating capacity, or any other expansion of use, as listed below. Exception. An expansion of off-street parking for a nonconforming existing use that increases the number of spaces to the minimum required by the UDC for that use is exempt from counting toward the 25% expansion: (See Figure 5.4-A.)
1. If the expansion is less than 25%, the MS&R applies to the proposed expansion. The remainder of the use or structure shall be governed by provisions in force at the time of initial approval for the use or structure;
2. If the expansion is 25% or more, the MS&R applies to the proposed expansion and to the parking and landscaping standards that apply to the overall development; or,
3. Expansions that occur after the effective date of the MS&R shall be cumulated in determining the 25% expansion.

Dimension the addition first and second floors. Clarify that the 1848 sf includes the second story.

Ensure that all Zoning and Engineering comments and concerns are addressed.

Additional comments may apply

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2019 SBEASLE1 OUT TO CUSTOMER Completed