Permit Number: DP18-0304
Parcel: 11623063C

Address:
960 S FREEWAY

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - DP18-0304
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2019 MARTIN BROWN FIRE REVIEW Approved
11/25/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Keynote #76 calls for the installation of a backwater valve at the south end of the new Welcome Building. The building has an FFE of 2362.7 and what appears to be the next upstream manhole (9895-17) has a rim elevation of 2358.0. Since the FFE is more than 12" above the manhole rim, a backwater valve is not allowed. Reference: Section 714.1, IPC 2018.
12/02/2019 SBEASLE1 ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2019 SBEASLE1 OUT TO CUSTOMER Completed