Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - DP18-0304
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/20/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/25/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Keynote #76 calls for the installation of a backwater valve at the south end of the new Welcome Building. The building has an FFE of 2362.7 and what appears to be the next upstream manhole (9895-17) has a rim elevation of 2358.0. Since the FFE is more than 12" above the manhole rim, a backwater valve is not allowed. Reference: Section 714.1, IPC 2018. |
12/02/2019 | SBEASLE1 | ZONING-DECISION LETTER | WRITE DECISION LETTER | Reqs Change |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/02/2019 | SBEASLE1 | OUT TO CUSTOMER | Completed |