Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - DP18-0296
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/10/2019 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: DP18-0296 Grading Plan for new SFR (1st Review) 8721 E. Woodland Road SR Zoning TRANSMITTAL DATE: January 10, 2019 DUE DATE: January 10, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: Zoning has reviewed the grading plan as it relates to the zoning review purview. The building location meets the building setbacks as required in the SR zone. The GP site plan will also be used as the approved site plan once the GP is approved by all reviewers. 02. COMMENT: Zoning cannot approve the Grading Plan at this time. Zoning will review the GP on the next submittal and approve it once the PDSD Engineering and Landscape Reviewer's comments have been addressed and applicable changes made to the plans. Please address all reviewers' comments, make the necessary changes to the plans and resubmit the plans for review. 03. COMMENT: Include the PDSD stamp in the lower right corner of all plan sheets. The digital copy of the PDSD stamp can be downloaded using the following link; https://www.tucsonaz.gov/pdsd/development-permits the digital stamp can be downloaded in a PDF, JPEG or DWG Format. Look under the "Preparing Your Plans for a Development Package Permit Section - Development Package Stamp. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Grading Plan |
| 01/11/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | January 11, 2019 DP18-0296 1. Include the engineering report from the engineer with the grading development plan. The engineering report must include an encroachment analysis. Since there are projects on adjacent properties with the same owners, the encroachment analysis needs to address the effects of both projects. (Tucson Code 26-11.2.a.2.e) 2. Show how fill slopes will be protected from erosion. (Tucson Code 26-5.2.12) 3. Clearly show the distance from the building to the edge of the fill slopes. The minimum distance must be 25 feet or if a lesser distance is shown, provide engineering justification. (Tucson code 26-8.d.2) |
| 12/26/2018 | ANDREW CONNOR | NPPO | REVIEW | Reqs Change | SECTION 4-02.0.0: FLOODPLAIN, WASH AND ERZ STANDARDS. 2.4 Identification of Regulated Areas and Protected Riparian Areas All tentative plats, site plans, plot plans or other plans providing for approval of development within property that includes any regulated area as defined in Section 4-02.2.2.A, ERZ Watercourses, shall identify and delineate the regulated areas and the protected riparian area on the property and shall comply with this standard. The boundary of the regulated area and the protected riparian area should be clearly depicted on applicable submittal documents. Encroachment in Regulated Areas If the project proposes encroachment within the regulated areas, it shall conform to the following. 1. Environmental Resource Report. Applicants are required to submit an Environmental Resource Report as defined in Section 11.4.6 of the UDC. The supporting material for preparation of the Environmental Resource Report is based on information from the Hydrologic Data and Wash Information maps on the Tucson Department of Transportation internet web site: The Critical and Sensitive Wildlife Habitat Map and Report, the Mayor and Council Interim Watercourse Improvement Policy and subsequent adopted policies, the Tucson Stormwater Management Study, the following Basin Management Plans: 1) West Branch, Santa Cruz; 2) Houghton East; 3) Este Wash; and 4) Arroyo Chico. the Tucson Stormwater Management Study, Phase II and field observation. An application may request that an element listed below be waived or that the report address only a specified area where a full report is not applicable to the proposed encroachment. DSD may grant such waivers where the elements or full report are not required by code. The Environmental Resource Report must include: Information indicated 4-02.2.5B a-x. Submit ERR for review. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/05/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 02/05/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 02/05/2019 | QJONES1 | REJECT SHELF | Completed |