Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP18-0247
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/12/2018 | ALEXANDRA HINES | START | PLANS SUBMITTED | Completed | |
| 10/12/2018 | ALEXANDRA HINES | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | Agency notified for information only. |
| 10/12/2018 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Passed | Agency notified for information only. |
| 10/12/2018 | ALEXANDRA HINES | OTHER AGENCIES | U. S. POST OFFICE | Passed | Agency notified for information only. |
| 10/12/2018 | ALEXANDRA HINES | UTILITIES | SOUTHWEST GAS | Passed | Agency notified for information only. |
| 10/18/2018 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Reqs Change | November 2, 2018 ACTIVITY NUMBER: DP18-0247 PROJECT NAME: Abrazo Micro Hospital PROJECT ADDRESS: 7401 S Wilmot PROJECT REVIEWER: Zelin Canchola TDOT Resubmittal Required: The following items must be revised and added to the Development Package 1. Refer to all new work within the right of way with PAG standard details, not COT STD 2. A private improvement agreement (PIA) will be required for work within the right of way, to include the deceleration lane and the left turn lane. https://www.tucsonaz.gov/tdot/private-improvement-agreement 3. Show driveways across the road (Wilmot) to ensure there are no left turn conflicts. If you have any questions, I can be reached at 520 837 6659 or zelin.canchola@tucsonaz.gov |
| 10/18/2018 | MASHFOR1 | COT NON-DSD | FIRE | Approved | Deferred Submittal will need to be supplied to TFD for Sprinkler System |
| 10/31/2018 | NROSS1 | OTHER AGENCIES | TUCSON AIRPORT AUTHORITY | Approv-Cond | October 29, 2018 Alexandra Hines Lead Planner City of Tucson Public Works Buildings - 201 North Stone Avenue Tucson, AZ. 85701 RE: DP18-0247 Abrazo Micro Hospital / 1st Submittal, Received October 12, 2018 Dear Ms. Hines, Thank you for the opportunity to comment on DP18-0247, Abrazo Micro Hospital; 1st Submittal, a development package application for an approximately 3.5 acre site, located southeast of the intersection of East Los Reales Road and Interstate 10. The land use is Planned Area Development (PAD) 7 with the proposed development being a hospital. This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace. The Tucson Airport Authority conditionally approves the subject request contingent upon the following condition of approval, as noted below. This condition shall be identified in the general notes of the revised development plan. Condition of approval: 1. "According to the FAA Notice Criteria Tool, this project is located in proximity to a navigation facility and could impact navigation signal reception. The applicant shall file Form 7460 with the FAA at least 45 days before construction activities begin for the project. It is highly recommended that the applicant file earlier than 45 days to provide the applicant with sufficient time to respond to any concerns which are identified by the FAA. Any cranes used which are used must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp" Although this project does not propose a change in plan designation or zoning the Tucson Airport Authority highly recommends the City of Tucson consider requiring the applicant to add the following note into the general notes of the revised development plans. This project is located approximately 4 miles northeast of Tucson International Airport and is within FAA traffic pattern airspace, an area which would be subject to aircraft overflight and noise due to being in close proximity to Tucson International Airport. The proposed note would provide a means of assuring that future owners and tenants of the property are aware they are near an airport and further assures the continued right of the City of Tucson, Tucson Airport Authority, and all persons lawfully utilizing the Tucson International Airport the right to utilize the airspace above or near the property. This would be accomplished through requiring the property owner to record the Avigation Easement. The Tucson Airport Authority believes this proposed note help to support the City of Tucson Airport Environs Overlay Zone and supports Plan Tucson - Regional and Global Positioning policy 4 (RG-4). 1. "That prior to the City's approval of any construction permit for a permanent building, the property owner shall record the Avigation Easement which discloses the existence, and operational characteristics of the Tucson International Airport to future owners or tenants of the property and further conveys the right to the public to lawfully use the airspace above the property. The Avigation Easement shall be recorded in a manner with the Pima County recorder which shall document it as having title liability. The content of such documents shall be according to the form and instructions provided." The current property owner or person authorized to sign on behalf of the current property owner shall complete, sign, and record the Avigation Easement. Please record the Avigation Easement with the Pima County Recorder's Office. Once the Avigation Easement is recorded please send a complete copy of the recorded easement document to Tucson Airport Authority by either email (send to srobidoux@flytucson.com) or to the mailing address provided below. Scott Robidoux Senior Airport Planner Tucson Airport Authority 7250 South Tucson Boulevard Suite 300 Tucson, AZ 85756 Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811. Respectfully, Scott Robidoux, Senior Airport Planner |
| 11/05/2018 | NROSS1 | COT NON-DSD | PARKS & RECREATION | Passed | No existing or proposed Tucson Parks and Recreation facilities are affected by this development. Howard B. Dutt, RLA Landscape Architect Tucson Parks & Recreation (520) 837-8040 Howard.Dutt@tucsonaz.gov |
| 11/06/2018 | DAVID RIVERA | ZONING HC | REVIEW | Reqs Change | See Zoning comments. |
| 11/06/2018 | NROSS1 | PIMA COUNTY | ADDRESSING | Reqs Change | DP18-0247 is being returned for corrections. Please see the attached plan for comments. Feel free to contact me if you have any questions. Nicholas Jordan Addressing Specialist Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-9623 |
| 11/06/2018 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | LANDSCAPE PLAN REQUIREMENTS 4.1 Identification and Descriptive Data A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. The landscape plan will contain the following identification in the lower right corner of each sheet: 1. Cross-reference to: a. Rezoning case: Indicate graphically, where possible, compliance with conditions of PAD-7 and if necessary any amendments required. Any other relevant case number for reviews or modifications that affect the site. La Estancia Planned Area Development Landscape Plan Landscape areas proposed within public rights-of-way will require an agreement between the Department of Transportation and the developer to allow this installation. Provide written permission from TDOT for landscape within ROW. Conflicts with Utilities Trees and shrubs must be selected and located so that, at maturity, they do not interfere with existing on-site or off-site utility service lines or utility easements. When Required Screening for individual land uses and zones must be provided as determined in Table 7.6.4-1 and in addition to the required landscape borders. Provide the following on landscape plans: Screening a. Location of screening elements; b. Height of screening material and reference point for measurement; c. Nature of screening material and, d. Type of screening material (e.g., masonry wall, wood fence, species of plant material). SECTION 4-01.0.0: COMMERCIAL RAINWATER HARVESTING Note: Organic mulch is appropriate for reducing evaporation, controlling dust and increasing soil quality in Water Harvesting Infiltration Areas in those locations where the vegetation, water collection, erosion conditions, and slope characteristics are amenable to its use. Indicate spot elevations for the bottoms of water harvesting structures, at spillways, and to define other grades as needed. Show location where any sensors that control the irrigation system will be placed Add the following notes to the Rainwater Harvesting Plan: MAINTENANCE MAINTENANCE REQUIREMENTS: All Passive Water Harvesting components, Water Harvesting Infiltration Areas, and other site improvements necessary for the water harvesting system to function properly, should be regularly inspected and maintained. The following maintenance requirements should be addressed on the Implementation Plan. Passive Systems. In addition to requirements for all systems, to ensure proper functioning of Passive Water Harvesting Systems, periodically inspect and maintain Sub-watershed surfaces and infrastructure associated with the system such as French drains, spillways, scuppers and other elements. Repair and correct problems as needed. " Monitoring of water use and related information at the site shall be the responsibility of the property owner. " Monitoring is required to verify compliance with the approved Water Harvesting Implementation Plan. Ensure that all Zoning and Engineering comments are addressed Additional comments may apply. |
| 11/06/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: David Rivera PDSD Zoning Review Section PROJECT: Abrazo Micro Hospital - (Commercial - Major Medical Use) Development Package (1st Review) (Rezoning C9-99-SP-7) DP18-0247 - PAD 7 Zoning &401 S Wilmot Road TRANSMITTAL DATE: November 6, 2018 DUE DATE: November 7, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is October 3, 2019. SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS) Section 2-06.3.0 FORMAT REQUIREMENTS 2-06.3.5 - A three-inch by five-inch space shall be reserved in the lower right quadrant of each sheet for an approval stamp. 1. COMMENT: Remove the Development Package PDSD approval stamp from all sheets. Reserve a three-inch by five-inch space in the lower right quadrant of each sheet for an approval stamp. The approval stamp will be applied electronically by PDSD staff. 2-06.3.7 - A small, project-location map shall be provided in the upper right corner of the cover sheet. 2. COMMENT: The project location map shall be revised to comply with the Standards DS 2-06.4.4 through 2-06.4.4.C. 2-06.3.12 - An index of sheets in the development package shall be provided on the first sheet. 3. COMMENT: The sheet index on the cover sheet shall include the Landscape/Irrigation sheets. The sheet numbers will be listed accordingly from 1 through 30. CONTENT REQUIREMENTS 2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines. 4. COMMENT: List the email address for the Land Surveyor and Geotechnical Engineer. 2-06.4.2 - The title block shall include the following information and be provided on each sheet: 2-06.4.2.A - The proposed name of the project or subdivision, or if there is no name, the proposed tenant's name; 2-06.4.2.B - A brief legal description and a statement as to whether the project is a re-subdivision are to be provided. On re-subdivisions, provide the recording information of the existing subdivision plat; 2-06.4.2.D - The page number and the total number of pages in the package (i.e., sheet xx of xx). 5. COMMENT: Include within the title block of all plan sheets the information as noted by the standards 2-06.4.2 through 2-06.4.2.D above. It appears that a lot split is proposed. Clarify if this is the case and whether or not a lot split or a minor subdivision has been processed? If so provide the approved documents with the next submittal and list any applicable case number next to the title block of all plan sheets related to the land division. 2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet. 6. COMMENT: Provide the development package case number, DP18-0247, adjacent to the title block on each sheet. If a lot split or minor subdivision has been processed and approved through PDSD, list the case number next to the title block of all DP plan sheets. 2-06.4.4 - The project-location map to be located on the first sheet of the development package in the upper right corner, shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information. 2-06.4.4.A - Show the subject property approximately centered within the one square mile area; 2-06.4.4.B - Identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and, 2-06.4.4.C - Section, township, and range; section corners; north arrow; and the scale will be labeled. 7. COMMENT: Revise the location map on the cover sheet to include the information as noted by the above standards 2-06.4.4 through 2-06.4.4.C. 2-06.4.6 - If the project is located within the boundaries of a Planned Area Development (PAD) zone, include a reduced-scale map of the PAD on the first sheet, indicating the location of the portion being developed. 8. COMMENT: Provide the map of PAD 7 as noted by the standard above. 2-06.4.7.A.3 - If the plan/plat has been prepared in conjunction with a rezoning application, add the following note next to the existing zoning note: "Proposed zoning is ____." List the applicable rezoning file number and conditions of approval. Also place the C9-__-__ (if applicable) and the plan/plat file numbers in the lower right corner of each sheet. 9. COMMENT: On Sheet 4, revise the proposed zoning note to state "No Change" 2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses. 10. COMMENT: There appears to be two principal uses proposed and integrated within the proposed hospital building. Revise the proposed use names to Commercial - Major Medical (Micro-Hospital) and Medical Outpatient uses. 2-06.4.7.A.6 - If a plan or plat is prepared in conjunction with other applications or overlays or the parcel being developed is subject to conditions of an application processed previously, additional information must be added to the plan. Such applications and overlays include, but are not limited to: annexations; rezonings; special exceptions; Board of Adjustment variances; Design Development Options; Technical Standard Modification Request; overlays (Airport Environs Zone, Environmental Resource Zone, Gateway Corridor Zone, Hillside Development Zone, Historic Preservation Zone, Major Streets and Routes, Rio Nuevo District, Scenic Corridor Zone, WASH); Modification of Development Regulations through the Downtown Area Infill Incentive District or Rio Nuevo District; Downtown Heritage Incentive Zone; or, Design Review Board. Provide the following information on the plan. 11. COMMENT: Add a general note on sheet four that states that this project has been designed to comply with the "UDC Section 5.4 Major Streets and Routes Setback requirements". A design review is required per the PAD document; include any documentation from the review board stating the proposed project is in compliance with the PAD 7 La Estancia Design Guidelines. 2-06.4.7.A.6.a - List additional applications and overlays, by case number (if applicable), in lower right corner of each sheet. As a general note provide the type of application processed or overlays applicable, a statement that the project meets the criteria/conditions of the additional application or overlay, the case number, date of approval, what was approved, and the conditions of approval, if any. 12. COMMENT: This area is within the Airport Avigation easement. A review by Scott Robidoux Airport Planner is required. Contact Kelly Lee PDSD Lead Planner at Kelly.Lee@tucsonaz.gov for more information on the Avigation easement requirements. 2-06.4.7.A.7 - If the property is part of a subdivision plat that is being reviewed or has been recorded, provide the case number in the lower right corner of each sheet. As a general note, indicate whether the project is part of a Flexible Lot Development (FLD), condominium, or another similar type project. 13. COMMENT: As noted in comment 6, list the case number associated with any land division of this parcel. 2-06.4.7.A.8.a - Floor area for each building; 14. COMMENT: List the building GFA under the Project information. Also list the allowed and proposed Floor Area ratio. 2-06.4.8 - Existing Site Conditions 2-06.4.8.A - Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system. 15. COMMENT: The site boundary information cannot be verified until the approved and recorded documentation for the land division is provided for review. 2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided. 2-06.4.9.L - All proposed easements (utility, sewer, drainage, access, etc.) are to be dimensioned and labeled as to their purposes and whether they will be public or private. The easements may have to be recorded and the recordation information added to the development package prior to approval. 16. COMMENT: All proposed easements must be recorded and labeled on the DP. All proposed easements must be recorded by separate instrument unless they have been recorded as part of the land division. 2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks. 17. COMMENT: Label the recordation data for Wilmot Road. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 2-06.4.9.E - Proposed land splits or existing lot lines shall be drawn on the plan with dimensions and the identification number and approximate square footage of each lot. (Please be aware that, if land division occurs and the number of lots falls within the definition of subdivision, a subdivision plat is required.) Land splits require a separate permit and review. 18. COMMENT: Documentation for the land division must be included with the next submittal. 2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. If the property is being rezoned, use those boundaries and classifications. The basis for this requirement is that some zoning requirements on a project are based on the zoning classification of adjacent property. Also, in some instances, each zone has to be taken into consideration on property that is split by two or more zoning classifications, as each may have different requirements. 19. COMMENT: Label on the site sheets the zoning classification adjacent to the subject parcel. 2-06.4.9.H.4 - Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned. 20. COMMENT: Label Wilmot Road as a "Public" road. 2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. 21. COMMENT: Clarify on the site plan sheets if the areas under the north and south of the building canopy are a one-way lane for drop off. Label the direction of travel in this area label and delineate the drop off area. 2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. 22. COMMENT: In order to verify that the correct number of motor vehicle parking spaces required has been provided, include the square footage areas other than the outpatient areas. If the outpatient area is separate from the inpatient area, be specific with the SF. (The motor vehicle parking will be reviewed again on the next submittal but based on the information as of this review there is excess parking. However only 84 spaces could be verified on the site plan sheet; it appears that the number of required spaces has been listed as 52 for the outpatient when it should be 51.) List the number of van accessible spaces provided. A minimum of two spaces is required. Label on the which are proposed van accessible spaces. Draw and dimension the overhang for the four parking spaces next to the accessible spaces on the north side of the building. Where wheel stops have been provided label the distance from the front wheel stop the front of the parking spaces. 2-06.4.9.H.5.c - Show all loading zones, vehicle maneuverability fully dimensioned, and access route. Provide as a note the number of loading spaces required, the number provided, whether the loading space is a Type A or B as provided in UDC Section 7.5.4. 23. COMMENT: Include in the parking criteria that one loading zone has been provided. While the code does not require a loading zone for this use one has been provided. 2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided. 24. COMMENT: Review the short and long term bicycle parking requirements for both uses and revise the bicycle parking calculations accordingly. Include a dimension from edge of the 2.5' vehicle overhang to the doors of the long term lockers. 2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual. 25. COMMENT: Clarify if the drop areas on the primary and secondary entrance points are flush with the pavement? If so what type of barrier is being provided to prevent vehicles from driving up on the pedestrian areas? Label the widths of the sidewalk along the north side of the building. Not all portions of the sidewalks have been dimensioned. The minimum clear width shall be four feet at all location where vehicles that abut the sidewalks and are not provided with wheel stops to prevent the vehicles from overhanging onto the sidewalk. 2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required. 26. COMMENT: If applicable indicate on the site plan sheets the location of any free standing signage. Add a general note that all signage will be reviewed and approved under separate permit. 27. COMMENT: As part of the zoning review it was found that a zoning determination was requested about a Helipad for this use. The determination stated that the proposal would be a Major Amendment to PAD 7. Zoning could not verify if the Helipad was proposed. Clarify if there is an intent to process a Major Amendment for the Helipad? If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 11/07/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | DP18-0247 1) Per City of Tucson (COT) Standards Manual for Drainage Design, a 15% reduction of the 2,10 and 100 year pre-developed flows is required. Projects final drainage report indicates that only a 10% reduction is designed for. Update drainage report and development plan as needed 2) Per COT Stormwater Detention/Retention manual, threshold retention of the difference between a pre and post 5 year event is required. Reference section 2.3 3) Per COT Stormwater Detention/Retention manual, section 3.5, maximum disposal times for stormwater runoff for detention basins is a maximum of 12 hours. Final drainage report indicates a 36 hour disposal time frame. Revise as needed to ensure a 12 hour drawdown 4) Reference COT Standards Manual for Drainage Design and Floodplain Management, include all applicable drainage maintenance responsibility notes found in section 14.3 5) Per Stormwater Detention/Retention Manual section 3.4.2 provide a grade control marker for each proposed basin over 6" in depth. On the plans please also provide the coordinates of the grade control markers so that they can be easily located in the future. 6) Sheet C4. Required turning radii for service vehicles, including fire, is 36' inside 50' outside. Revised turning radii detail as needed. Note that the trash enclosure will be fully open when determining if there is sufficient clearance. Reference COT Technical Standards Manual (TSM) Section 8 Figure 6 7) Ensure that roof drains scupper underneath sidewalks. Reference City of Tucson Technical Standards Manual (TSM) section 7-01.4.1.E 8) Sheet C5. Basin D. The spot grade at the pavement for the curb opening is 71.14 which is lower than the highwater level and the proposed drainage swale to the site outfall point. It appears that water will back out of the curb opening 9) Provide top/bottom spot grades for all proposed water harvesting areas to show that the 6" effective ponding depth is maintained 10) Show pad elevation of proposed backup generator 11) A 40' clear operating area is required for the trash enclosure. The lower 2 dumpsters appear to have this required area; however the northern most dumpster does not. Show on plans the required operating area. Also show on plans dimensions per TSM section 8 figure 3A. Enlarge to 3 dumpster enclosure using this figure 12) Pima Associations of Governments "PAG" standard details have been adopted to replace City of Tucson Standard Details. Update notes/details on all sheets to reference the appropriate "PAG" standards. See following link http://apps.pagnet.org/standardspecifications/ John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
| 11/08/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Tucson Water will not allow water meters and backflow preventers to be manifolded to achieve additional capacity. Each of the two required water sources to the building is to have a single water meter and reduced pressure principle backflow assembly capable of serving the total proposed water demand for the building. |
| 11/13/2018 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Reqs Change | Regional Traffic Engineering has comments on this submittal. The proposed development’s location lies within the vicinity of Interstate 10 and Wilmot Road which may affect its operation. A traffic document will be required, by ADOT, identifying any operational decencies and mitigation for the intersection. If a document has been submitted, ADOT would need to review and comment on it prior to any acceptance of the development. A copy of the ADOT ‘Traffic Engineering Guidelines and Processed’ (TGP), form 240, can be provided if requested. Thank you |
| 11/15/2018 | JOHN BEALL | COT NON-DSD | COMMUNITY PLANNING | Approv-Cond | PLANNING AND DEVELOPMENT SERVICES DEPARTMENT COMMENTS Regarding SUBJECT: Community Design Review Committee Application CASE NUMBER: CASE NAME: DATE SENT DP18-0247 Abrazo Micro Hospital 11/14/18 () Final Plat (X) Development Plan () Landscape Plan () Revised Plan/Plat () Board of Adjustment () Other - Elevations SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS: (x) Conditional Approval REVIEWER: KL DATE: 11/14/18 COMMENTS Site is addressed 7401 S WILMOT RD, and is currently being reviewed for DP18-0263. The site is subject to PAD-7 La Estancia Planned Area Development. According to Letter of Refinement and associated Exhibit 1-A dated July 20, 2007, the site at 7401 S Wilmot is designated MHDR. The MHDR designation permits commercial uses, suchas a micro hospital within the C-2 zone. A self-certification letter from the La Estancia Design Review Committee is required to be submitted as part of the development package. |
| 11/15/2018 | KELLY LEE | ZONING-DECISION LETTER | REVIEW | Reqs Change | This review has been completed and resubmittal is required. Please resubmit the following items: Prepare a Comment Response Letter which tells the reviewer what changes have been made to the plan and what comments are addressed. When you have made the necessary corrections to the plans, please resubmit the following items to PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd 1) Corrected plan set 2) Items requested by review staff Please remember to name your files appropriately, for example: second (2nd) submittal, 2_plan_set.pdf 2_swppp_report.pdf and the plans will re-enter the review cycle. Thank you, Kelly Lee Lead Planner Planning & Development Services (520) 837-6999 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/14/2018 | AHINES2 | OUT TO CUSTOMER | Completed |