Permit Number: DP18-0239
Parcel: 113071300

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP18-0239
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2020 SBEASLE1 START PLANS SUBMITTED Completed
02/26/2020 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approved DP18-0239 / Hedrick / 2nd Submittal is Approved by Pima County Addressing.

Thank you,
Robin Freiman, Addressing Official
Pima County Development Services Department
201 N Stone AV – 1st Floor Tucson, AZ 85701
(520) 724-7570
03/10/2020 LSHAMIS1 ZONING REVIEW Approved
03/16/2020 ANDREW CONNOR LANDSCAPE REVIEW Approved
03/20/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The first floor elevations have been provided but nothing indicates which units need a backwater valve. The site plan shows the building sewer connecting to the 21" public sewer located in Hedrick Drive. Unless there is an existing HCS, it is doubtful that Pima County would allow you to connect to that sewer. If there is an existing HCS, the upstream manhole has a rim elevation of approximately 2380 feet which means that the first floor of each unit will require a backwater valve. The waste from the second-story units may not pass through a backwater valve. [Initial comment: Provide the first floor elevation for each building. Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole in the public sewer system, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor. Floors discharging from above that reference point shall not discharge through the backwater valve. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson.]
2. Comment not addressed. [Initial comment: Determine the design daily sewer flow for the development.]
03/24/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: Resubmittal with a Comment Response Letter

DESCRIPTION: SITE/GRADING - Hedrick Development.
PERMIT: DP18-0239
FEE BALANCE: $0 (zero)

SEE REVIEWER'S COMMENTS and your submitted documentson PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Reviews section, click on Review Details
- Documents section, click on blue icon to the right of each document

YOUR NEXT STEPS: Submit the following items to the Filedrop- https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set)
3) Any other documents requested by review staff

- Name your 3rd submittal documents to start with the submittal number, for example: 3_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
Attn: Permit Counter
201 N. Stone Avenue, 2nd Floor
Tucson, AZ 85701
email: COTDSDPermits@TucsonAz.gov

NOTE:
The City of Tucson's Permit Counter at 201 N. Stone Avenue (the physical office) is closed to the public until further notice. In the meantime, our office is still fully staffed but all communications will be via telephone or email.

City of Tucson updates: https://www.tucsonaz.gov/manager/covid-19-updates
03/24/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Correct instances of text layering, for example sheet 6.
2. Clearly indicate adequate wall openings.
3. Check plans for typographical errors.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/24/2020 SBEASLE1 OUT TO CUSTOMER Completed