Permit Number: DP18-0239
Parcel: 113071300

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP18-0239
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2018 ALEXANDRA HINES START PLANS SUBMITTED Completed
11/13/2018 AHINES2 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Needs Review
11/13/2018 ALEXANDRA HINES ZONING REVIEW Needs Review
11/13/2018 AHINES2 WWM REVIEW Passed
11/14/2018 LOREN MAKUS ENGINEERING REVIEW Denied 1. The application indicates this is for a site plan. The cover sheet is titled "Grading Plan." Please indicate all reviews being requested on the application.
2. Include cut and fill quantities for the grading
3. Include a drainage statement or report addressing floodplain encroachment and water harvesting or retention and detention.
4. Provide water surface contours for the floodplain.
5. All pages in the package must be labelled sequentially as 1 of 5, 2 of 5 and so forth.

I recommend you meet with a representative of the Engineering Section before submitting the plans.