Permit Review Detail
Review Status: Completed
Review Details: DEV PKG - OK TO SUBMIT
Permit Number - DP18-0239
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/13/2018 | ALEXANDRA HINES | START | PLANS SUBMITTED | Completed | |
| 11/13/2018 | AHINES2 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Needs Review | |
| 11/13/2018 | ALEXANDRA HINES | ZONING | REVIEW | Needs Review | |
| 11/13/2018 | AHINES2 | WWM | REVIEW | Passed | |
| 11/14/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | 1. The application indicates this is for a site plan. The cover sheet is titled "Grading Plan." Please indicate all reviews being requested on the application. 2. Include cut and fill quantities for the grading 3. Include a drainage statement or report addressing floodplain encroachment and water harvesting or retention and detention. 4. Provide water surface contours for the floodplain. 5. All pages in the package must be labelled sequentially as 1 of 5, 2 of 5 and so forth. I recommend you meet with a representative of the Engineering Section before submitting the plans. |