Permit Number: DP18-0229
Parcel: 14021002B

Address:
5489 S PARK AV

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP18-0229
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2019 SBEASLE1 START PLANS SUBMITTED Completed
01/30/2019 MASHFOR1 COT NON-DSD FIRE Reqs Change **This project will require sprinklers per TFD conversation with Eric from PDSD and as such will require changes:

**Per section 903.2.8 Group R. An automatic sprinkler system installed in accordance with section 903.3 shall be provided throughout all buildings with a Group R fire area.

Fire Sprinklers will be required on this project.
02/14/2019 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: Rio Madera Apartments - Multi Family Residential Development
Development Package (3rd Review)
DP18-0229 - C-2 Zoning - 5489 S. Park Avenue

TRANSMITTAL DATE: February 14, 2019
DUE DATE: February 19, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is September 12, 2019.

1. COMMENT: List the TSMR case number next to the title block of all plan sheets.

List as a general note the TSMR case number, the date of approval, and the approved modifications.


2. COMMENT: Include a copy of the TDOT memo from Fred Felix related to the requirement of a street sidewalk, access ramps, and curbs along Minorka Road.



If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
02/15/2019 ZELIN CANCHOLA COT NON-DSD TRAFFIC Denied February 15, 2019
ACTIVITY NUMBER: DP18-0229
PROJECT NAME: Rio Madera apartments
PROJECT ADDRESS: 5489 S Park Av
PROJECT REVIEWER: Zelin Canchola TDOT

Resubmittal Required: The following items must be revised and added to the Development Package

Comment response "(per diana Alarcon) is not to require curb and sidewalks, ramps ect along Minorka" is not acceptable.

TDOT recommends a TSMR for further review and direction from TDOT director.
02/19/2019 ANDREW CONNOR LANDSCAPE REVIEW Approved
02/21/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The review has been completed and a resubmittal is required.
Activity Number: DP18-0229
Project Description: E SITE/GRADE/SWPPP - RIO MADERA APTS
To see review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number. (If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.)
Prepare a Comment Response Letter detailing changes to the plan and which review comments are being addressed. After the necessary corrections have been made, submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd. Enter the Activity Number in the Project Description field and name the file as directed, for example, fourth submittal: 4_Plan_Set.pdf. The plans will then re-enter a 20-working-day review cycle.
1) Comment Response Letter
2) Corrected plan set with all documents
3) Items requested by review staff
Please pay the assessed fees at the permit counter or mail a check (payable to City of Tucson – address is shown below) prior to the completion of the next review. Include the Activity Number on your check stub. The fee balance is $ 82.50.
Loren Makus, copied, is the Project Manager to contact with any questions, email: Loren.Makus@TucsonAz.gov or phone (520) 837-4927. Thank you.

Sharon Beasley
City of Tucson
Planning and Development Services
201 N. Stone Avenue, First Floor
Tucson, AZ 85701
02/21/2019 JOHN VAN WINKLE ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/21/2019 SBEASLE1 OUT TO CUSTOMER Completed