Permit Number: DP18-0211
Parcel: 11942006F

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP18-0211
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2018 ALEXANDRA HINES START PLANS SUBMITTED Completed
11/06/2018 MARTIN BROWN FIRE REVIEW Reqs Change All parts of the building must be within 600' of a fire hydrant. Please provide an additional hydrant and locate on plans.
11/27/2018 ANDREW CONNOR LANDSCAPE REVIEW Approved
11/27/2018 SBEASLE1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Approved November 27, 2018

Alexandra Hines
Lead Planner
City of Tucson
Public Works Buildings – 201 North Stone Avenue
Tucson, AZ. 85701

RE: DP18-0211 Rincon Country West RV Resort / 2nd Submittal, Received November 2, 2018

Dear Ms. Hines,

Thank you for the opportunity to comment on DP18-0211, Rincon Country West RV Resort; 2nd Submittal, a development package application for an approximately 0.24 acre site, located approximately 0.25 miles southeast of the intersection of South Mission Road and West Via Ingresso. The land use is recreational vehicle (RV), with the proposed development being a wood shop building.

This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.

The Tucson Airport Authority is satisfied with the 2nd submittal of this project and has no additional comments to submit.

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.

Respectfully,
Scott Robidoux,
Senior Airport Planner

cc file
11/29/2018 DAVID RIVERA ZONING HC REVIEW Approved
11/29/2018 DAVID RIVERA ZONING REVIEW Approved
11/30/2018 JOHN VAN WINKLE ENGINEERING REVIEW Approved
12/03/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Revise the site drawing to include the pipe diameter of the sanitary sewers and the invert and rim elevations of all manholes and cleanouts. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2012.]
2. Comment not addressed. [Initial comment: Where the finished floor elevation is less than 12 inches above the elevation of the next upstream manhole in the public sewer or private sewer collection system, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor. Floors discharging from above that reference point shall not discharge through the backwater valve. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson.]
12/04/2018 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change 12/04/18

Plans Returned for Corrections (RFC) Notice: DP18-0211
Project Description: E SITE/GRADING - RINCON COUNTRY WEST RV RESORT

The review has been completed and a resubmittal is required. To see review comments about the plans, visit PRO at www.tucsonaz.gov/PRO, then search by activity number. (If new comments aren't shown yet, please check back later as data flows to PRO at periodic intervals throughout the day.)
Prepare a Comment Response Letter for the reviewers detailing changes to the plan and which review comments are being addressed. After the necessary corrections have been made to the plans, please submit the following items to PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd. The plans will then re-enter the 20 working day review cycle.
1) Comment Response Letter
2) Corrected plan set
3) Items requested by review staff
Please type the activity number in the Project Description and name the files as described on the PDSD Filedrop web page. The current fee balance is $0 (zero). Thank you.

Sharon Beasley
City of Tucson
Planning and Development Svcs. Dept.
201 N. Stone Ave, 1st Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2018 SBEASLE1 OUT TO CUSTOMER Completed