Permit Number: DP18-0198
Parcel: 11618434A

Address:
425 N GRANDE AV

Review Status: Completed

Review Details: GRADING

Permit Number - DP18-0198
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/06/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP18-0198

1) Per City of Tucson Administrative Manual (AM) section 2-06.4.7.B add the required hold harmless note
2) Per City of Tucson Stormwater Detention/Retention Manual section 3.4.2 provide a grade control marker for the proposed basin. On the plans please also provide the coordinates of the grade control marker so that they can be easily located in the future
3) Detail A/C5 shows the perimeter sidewalk sloping away from the water harvesting area. On sheet 3, immediately adjacent to the location of detail A/C5 the sidewalk is shown sloping towards the water harvesting area. Confirm if this is intentional and modify the standard detail if needed
4) PAG standard detail 204 shows that the bottom of the scupper is to be 1" above grade. Provided spot grades indicate that the bottom of the scupper is below grade on both sides. Provide additional spot grades to show that the scuppers directed towards the proposed retention basin drain properly.
5) Engineering can conduct an expedited electronic review once all outstanding department review comments have been addressed, the revised plans are resubmitted and a new work flow has been opened. Call or email to schedule.

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
09/06/2018 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: Menlo Park Apartments - Grading plan for Pool and Clubhouse Area.
Development Package (1st Review) - Related to DP18-0084
DP18-0198

TRANSMITTAL DATE: September 6, 2018
DUE DATE: September 18, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is August 15, 2019.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

2-06.3.6 - Provide a blank three-inch by five-inch block in the lower right corner of the plan adjacent to the title block on the first sheet of the development package for use by Pima County Addressing.

1. COMMENT: 2-06.3.5 - Remove the Development Package PDSD approval stamp on all sheets. Reserve a three-inch by five-inch space in the lower right quadrant of each sheet for an approval stamp. The approval stamp will be applied electronically.

As of this zoning review of the grading plan the DP18-0084 has been approved but has not been issued. The grading plan cannot be issued until the DP is issued. The applicant of the DP application must pick up the approved DP before the grading plan is issued or at the same time.



If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
09/18/2018 ANDREW CONNOR NPPO REVIEW Approved
09/18/2018 ALEXANDRA HINES ZONING-DECISION LETTER WRITE DECISION LETTER Reqs Change Plan Returned for Corrections Notice: DP18-0198Project Description: E GRADE - MENLO PARK APT- NEW POOL & COMM. CENTER
This review has been completed and resubmittal is required. To see reviewer's comments about your plans, please visit https://www.tucsonaz.gov/pro/pdsd/activity_search. You will need to enter the activity number shown above to see comments about the plan.
Prepare a Comment Response Letter which tells the reviewers what changes have been made to the plan and what comments are addressed. When you have made the necessary corrections to the plans, please resubmit the following items to PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd and the plans will re-enter the 20 working day review cycle:1) Corrected plan set2) Items requested by review staff
Please remember to name your files appropriately, for example: second (2nd) submittal,2_plan_set.pdf2_response_letter.pdf
Alexandra Hines, AICP
Lead Planner at Planning and Development Services, City of Tucson
201 N Stone Ave 1st Floor, Tucson, AZ 85701
(520) 837-6975 - alexandra.hines@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/18/2018 AHINES2 OUT TO CUSTOMER Completed