Permit Number: DP18-0183
Parcel: 11106157A

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP18-0183
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2018 ALEXANDRA HINES START PLANS SUBMITTED Completed
08/15/2018 DAVID RIVERA ZONING REVIEW Approved
08/16/2018 ANDREW CONNOR NPPO REVIEW Approved
08/21/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP18-0183

1) Per City of Tucson Administrative Manual (AM) section 2-06.4.7.B add the required hold harmless note
2) Provide a drainage/hydrology report for review
3) Show site visibility triangles at the intersection of E Monte Vista Dr and N Dantes Ct
4) Per City of Tucson Stormwater Detention/Retention Manual section 3.4.2 provide a grade control marker for each proposed basin. On the plans please also provide the coordinates of the grade control markers so that they can be easily located in the future
5) Per City of Tucson Standards Manual for Drainage Design manual add the Inspection and Maintenance notes found in section 14.03 policy 2.
6) Proposed Basin Depths are over 2' and the side slope of the basin is greater than 4:1. Per City of Tucson Storm Water Detention/Retention Manual, pages 81,82, a minimum 42" tall security barrier is required. The barrier should be placed to prevent access. For example where a sidewalk runs adjacent to a basin. Provide barrier detail. Suggest using PAG standard detail 105, see following link http://apps.pagnet.org/StandardSpecifications/Documents/Drawings/PAGStdDtl-105.pdf

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
08/29/2018 ALEXANDRA HINES ZONING-DECISION LETTER REVIEW Reqs Change Plan Returned for Corrections Notice: DP18-0183
This review has been completed and resubmittal is required. View the comments on www.tucsonaz.gov/pro and search by activity number. Prepare a Comment Response Letter which tells the reviewer what changes have been made to the plan and what comments are addressed. When you have made the necessary corrections to the plans, please resubmit the following items to PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd:1) Revised Plan Set2) All items requested by review staff3) All items needed to approve these plans
Please remember to name your files appropriately, for example: Example second submittal:2_plan_set.pdf2_comment_response _letter.pdf
Zoning Letter Review Comment: Remove the development package stamp from all sheets and leave a blank 3" x 5" space in the same lower right hand corner on all sheets for the electronic stamp.
Thank you,
Alexandra Hines

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2018 AHINES2 OUT TO CUSTOMER Completed