Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP18-0164
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2018 | ALEXANDRA HINES | START | PLANS SUBMITTED | Completed | |
| 07/17/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/25/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: David Rivera PDSD Zoning Review Section PROJECT: Home Depot Tool Rental Expansion - Store #0467 Development Package (1st Review) DP18- 0164 - C-2 Zoning TRANSMITTAL DATE: July 25, 2018 DUE DATE: August 3, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is July 7, 2019. 2-06.3.0 FORMAT REQUIREMENTS 2-06.3.5 - A three-inch by five-inch space shall be reserved in the lower right quadrant of each sheet for an approval stamp. 1. COMMENT: Remove the Development Package PDSD approval stamp on all sheets. Reserve a three-inch by five-inch space in the lower right quadrant of each sheet for an approval stamp. The approval stamp will be applied electronically. 2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines. 2. COMMENT: List the owner / Developer's information as noted by the standard above. 2-06.4.2.B - A brief legal description and a statement as to whether the project is a re-subdivision are to be provided. On re-subdivisions, provide the recording information of the existing subdivision plat; 3. COMMENT: In the title block or in the lower right corner of the sheets, include the following as a brief legal description of the property; PARQUE DE SANTA CRUZ RESUB PTN LOTS 1 & 2. 2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet. 4. COMMENT: Provide the development package case number, DP18-0164, adjacent to the title block on each sheet. 2-06.4.4 - The project-location map to be located on the first sheet of the development package in the upper right corner, shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information. 2-06.4.4.B - Identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and, 5. COMMENT: Label the major street names "Irvington Rd, I-19, Called Santa Cruz and 12th Avenue" within the location map so that they are legible. 2-06.4.7.A.8.c - Percentage of building, lot area, or vehicular use area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included; and, 6. COMMENT: Include a building percent expansion calculation. 2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. 7. COMMENT: Under the parking calculations list the number of spaces that will be lost due to the expansion. Clarify if any of the spaces being removed are accessible spaces. If so, indicate the location where they will be relocated. 2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual. 8. COMMENT: Label the cross and horizontal slopes of the new sidewalk. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 07/25/2018 | DAVID RIVERA | ZONING HC | REVIEW | Reqs Change | See zoning comments |
| 07/31/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | DP18-0164 1) Show on plans that any roof drains (downspouts) scupper underneath sidewalks or pedestrian walkways. Reference City of Tucson (COT) Technical Standard (TSM) 7-01.4.1.E 2) Provide a detail showing how the proposed new sidewalk transitions to the existing pedestrian circulation path for the south-west corner of the proposed expansion. Indicate if the sidewalk is raised 6" above the existing paved area or if it is flush. If it is flush then a physical barrier is required. Reference COT TSM 7-01.4.2 3) It appears that the proposed width for the southern portion of the new sidewalk is 5', however heavy line weights block the dimension. Adjust line weights so that all dimensions/leaders are clearly visible John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
| 08/01/2018 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approv-Cond | Ensure that all Zoning and Engineering comments and concerns are addressed. |
| 08/01/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the site drawing to include the following existing utility information: a. The location of water lines, and fire hydrants. b. The location and size of sanitary and storm sewers, including the pipe diameter and the invert and rim elevations of all manholes and cleanouts; along with the Pima County Wastewater Management Department (PCWMD) reference number. c. The point of connection to the existing public sewers. d. Any existing or proposed utility easements e. The first floor elevation for the building Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2012. |
| 08/02/2018 | KELLY LEE | ZONING-DECISION LETTER | REVIEW | Reqs Change | Plan Returned for Corrections Notice: DP18-0164 This review has been completed and resubmittal is required. Please resubmit the following items to PDSD Filedrop https://www.tucsonaz.gov/file-upload-pdsd 1) Revised Plan Set 2) All items requested by review staff 3) All items needed to approve these plans Please remember to name your files appropriately, for example: Example 2 (second submittal): 2_plan_set.pdf 2_soils_report.pdf Kelly Lee Lead Planner Planning & Development Services (520) 837-6999 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/15/2018 | KLEE1 | OUT TO CUSTOMER | Completed |