Permit Number: DP18-0134
Parcel: 121115330

Review Status: Completed

Review Details: GRADING

Permit Number - DP18-0134
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP18-0134

1) Previous comment 3. Please supply a copy of the SWPPP upon next submittal
2) Previous comment 8. Sheet 6 Detail J. Dimensions (6',8',6') do not add up to the supplied overall dimension of 28'6". Adjust as needed
3) Previous comment 9. Double check lot flow lines shown on sheet 6 against those shown on sheet 5. For example, Lot 3 on sheet 6 shows water flowing to the back, on sheet 5, one side drains to the back, the other side drains to the front. Lot 1 on sheet 5
4) Please transfer these comments to DP18-0186 and make sure both DP's associated with Warrior village are consistent
5) Engineering conduct an over the counter review of the plans once the above and any outstanding review comments have been addressed and a new work flow opened. Call or email to schedule

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
12/06/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: DP18-0134 - Warrior Village
Grading plan (2nd Review) - Related to DP18-0186
1185 N. Riverfront Estates

TRANSMITTAL DATE: December 06, 2018

DUE DATE: December 11, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the Grading plans for Warrior Village but cannot approve them at this time. While the grading plans is consistent with the current version of DP18-0186, and as it relates to the zoning review purview zoning will approve the grading plan once the tentative plat DP18-0186 is approved and the PDSD Engineering and Landscape reviewers have approved the grading plan.

2. COMMENT: Add the DP stamp to all grading plan sheets for plan reviewer signatures. The digital stamp can be downloaded from the PDSD web site.

3. COMMENT: List the DP case number DP18-00134 in the lower right corner next to the title block of all sheets. Reference the associated revised tentative plat and final plat case numbers DP18-0186, S18-070 next to the title block of all plan sheets.

4. COMMENT: Revise the dedication note on the cover sheet to state "Area to be dedicated to the City of Tucson per Final Plat". Verify with John Cahill if the COT will accept the proposed dedication area.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email at David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
12/06/2018 ANDREW CONNOR NPPO REVIEW Reqs Change Landscape will approve the grading plan once the tentative plat DP18-0186 is approved and the PDSD Engineering reviewers are complete.
Add the DP stamp to all grading plan sheets for plan reviewer signatures. The digital stamp can be downloaded from the PDSD web site.
Reference the associated revised tentative plat and final plat case numbers DP18-0186, S18-070 next to the title block of all plan sheets.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/19/2018 AVAUGHN1 APPROVAL SHELF Completed
12/19/2018 AVAUGHN1 OUT TO CUSTOMER Completed
12/19/2018 AVAUGHN1 REJECT SHELF Completed