Permit Number: DP18-0072
Parcel: 13014005A

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP18-0072
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2018 QJONES1 START PLANS SUBMITTED Completed
04/02/2018 ALEXANDRA HINES ZONING REVIEW Reqs Change FROM: Alexandra Hines, Lead Planner

PROJECT: DP18-0072 Tucson Baptist Solar PV Project (1st Review)

TRANSMITTAL DATE: April 4, 2018

COMMENTS: Please resubmit revised drawings with a detailed response letter, which states how all zoning review comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

1. 2-06.3.1 - Each sheet shall include a minimum one inch margin on left side and one-half inch margin on all other sides to facilitate efficient record keeping.

2. 2-06.3.5 - A three-inch by five-inch space shall be reserved in the lower right quadrant of each sheet for an approval stamp.

3. 2-06.4.7.A.8.b - Percentage and area in square feet of building and accessory building coverage. Lot coverage maximum is 60% per UDC Section 6.3.4.

4. 2-06.4.7.A.8.c - Percentage of building, lot area, or vehicular use area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included.

5. 2-06.4.8 - The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

6. 2-06.4.9.H.5 - Provide one (1) foot setback of structure from parking area access lanes (PAALs) per UDC Section 7.4.6 or provide fifteen (15) foot height for structure.

7. 2-06.4.9.O - Dimension all building setback lines per UDC Section 6.3.4. The minimum setback is the greater of ten (10) feet, or three-fourth (3/4) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Note, the proposed structure on the north of the property does not meet the required setback. A design development option (DDO) application is required to request a setback modification.

8. 2-06.4.9.Q - Provide the square footage and the height of each structure and the specific use proposed within the footprint of the structure(s).

9. 2-06.4.9.Q - Show location of posts for structures. Does the location impede vehicle use area or parking?

If desired, these zoning review comments can be reviewed over the counter.

If you have any questions about this transmittal, please contact Alexandra Hines at (520) 837-6975 or alexandra.hines@tucsonaz.gov.
04/02/2018 AHINES2 ENGINEERING REVIEW Needs Review
04/04/2018 AHINES2 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Passed