Review Details: DEV PKG - REVISION
Permit Number - DP18-0071
Review Name: DEV PKG - REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2019 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 02/14/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved | |
| 03/07/2019 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 03/19/2019 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | REVISION PLAN RETURNED FOR CORRECTIONS NOTICE The reviews have been completed and a resubmittal is required. Activity Number: DP18-0071 Project Description: E SITE/GRADE/SWPPP - Mountain Adelaide FLD Multi-family To view revision review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number. (If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.) After the necessary corrections have been made, name your documents in the following manner - a 2nd submittal document (first revision) would be titled: REV-1_2_Plan_Set. Submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd. In the Project Description field, enter the Activity Number. 1) Comment Response Letter (lists changes to the Plan and which review comments are being addressed) 2) Corrected plan set with all documents (the full set) 3) Items requested by review staff After resubmittal, the plans will re-enter the standard 20-working-day review cycle. The fee balance is $0 (zero). The Project Manager can be reached via email: Maria.Gayosso@TucsonAz.gov or phone: (520) 837-6972. Thank you. City of Tucson Planning and Development Services Attn: Sharon Beasley 201 N. Stone Avenue, First Floor Tucson, AZ 85701 |
| 03/19/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the site utility drawing to indicate that backwater valves will be required for buildings 1, 2, 4, 5, 7, and 10 because the rem elevation of the upstream manholes are less than 12" below the proposed first floor elevations. Floors discharging from above that reference point shall not discharge through the backwater valve. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/18/2019 | SBEASLE1 | OUT TO CUSTOMER | Completed |