Permit Number: DP18-0060
Parcel: 99999999A

Address:
8525 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Permit Number - DP18-0060
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2019 SBEASLE1 START PLANS SUBMITTED Completed
01/07/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Indicate which lots will require the installation of backwater valves. [Second comment: Assuming a FFE for each lot that is 8" above the pad elevation, backwater valves are required for lots 24, 27, 31, 33, 34, 35, and 36.] [Initial comment: Based on the rim elevation of the next upstream sanitary manhole and the first floor elevation, determine the need for a backwater valve for each lot per Section 715.1, IPC 2012, as amended by the City of Tucson.]
01/14/2019 LOREN MAKUS ENGINEERING REVIEW Approved
01/15/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Plans Returned for Corrections Notice
Activity Number: DP18-0060
Project Description: E TENTATIVE PLAT/GRADE/FLEXIBLE LOT DEV. - ARROYO RESERVE

The review has been completed and a resubmittal is required.
To see review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number.
(If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.)
Prepare a Comment Response Letter detailing changes to the plan and which review comments are being addressed.
After the necessary corrections have been made, go to the PDSD Filedrop web page.
Please enter the Activity Number in the “Project Description” field and name the files as ­directed, for example, 5th submittal: 5_Plan_Set.pdf
Submit the following items to the PDSD Filedrop at www.tucsonaz.gov/file-upload-pdsd.
The plans will then re-enter a 20-working-day review cycle.­
1) Com­­ment Response Letter
2) Corrected plan set with all documents
3) Items requested by review staff

Andrew Connor is the Project Manager to contact with any questions, email: Andrew.Connor@TucsonAz.gov
or phone: (520) 837-4950. Thank you.

Sharon Beasley
City of Tucson
Planning and Development Services
201 N. Stone Avenue, First Floor­
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
01/15/2019 SBEASLE1 OUT TO CUSTOMER Completed