Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP18-0051
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/02/2018 | ALEXANDRA HINES | START | PLANS SUBMITTED | Completed | |
| 03/13/2018 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Please indicate existing and/or proposed fire hydrant location(s), with dimensions to buildings and/or property lines. Refer to the 2012 International Fire Code Section 507 for spacing and location requirements. |
| 03/27/2018 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | UNIFIED DEVELOPMENT CODE 4.1 Identification and Descriptive Data A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. The landscape plan will contain the following identification in the lower right corner of each sheet: Any relevant case number for reviews or modifications that affect the site. 2-06.3.5 - Remove Development Package PDSD approval stamp on all sheets. Reserve a three-inch by five-inch space in the lower right quadrant of each sheet for an approval stamp. The approval stamp will be applied electronically. The standards of this section apply to the entire site. 7.6. LANDSCAPING AND SCREENING Minimum Width Street landscape borders must be a minimum of ten feet wide as measured from the street property line. On streets designated as Major Streets and Routes (MS&R), the street landscape border must be measured from the future MS&R right-of-way line as determined by Section 5.4.4, Establishment of MS&R Right-of-Way Lines and Gateway Routes. Portions of the landscape buffer on Grant Rd are not 10' wide. Located on Site Street landscape borders must be located entirely on site, except that, if approved by the City Engineer or designee, up to five feet of the required ten foot width may be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets. Canopy Trees in Vehicular Use Areas General Standards Within a vehicular use area, one canopy tree is required for each four motor vehicle parking spaces or fraction thereof. (1) The canopy trees must be evenly distributed throughout the vehicular use area. Every parking space must be located within 40 feet of the trunk of a canopy tree (as measured from the center of the tree trunk). (2) Fifty percent of the trees required for landscape borders located within ten feet of the paved portion(s) of a vehicular use area may be counted towards both the minimum parking lot canopy tree standard and the landscape border canopy tree standard. (3) An unpaved planting area, which must be a minimum of 34 square feet in area and four feet in width, must be provided for each canopy tree. Provide trees for entire vehicle use area. 7.6.5. SCREENING STANDARDS When Required Screening for individual land uses and zones must be provided as determined in Table 7.6.4-1 and in addition to the required landscape borders. Screening is not required between similar uses in accordance with Table 7.6.4-1. Identify screening elements on Landscape plan. SECTION 4-01.0.0: COMMERCIAL RAINWATER HARVESTING Applicability: All new commercial development plans submitted after June 1, 2010. A separate Water Harvesting Implementation Plan shall be submitted with all applications for new commercial developments where landscaping is required. The plan shall detail the landscape water demand and the harvested water supply needed to meet 50 percent of landscape demand. Provide Water Harvesting plan for new portion of development. 7.7. NATIVE PLANT PRESERVATION Provide NPP plan or Application for Exception Ensure that all Zoning and Engineering comments and concerns are addressed prior to landscape approval. Additional comments may apply. |
| 03/28/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 03/29/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | DP18-0051 1) Per City of Tucson Administrative Manual (AM) section 7-01.3, provide a pedestrian circulation path sidewalk connection to both N 4th Av and E Grant Rd. John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
| 03/29/2018 | DAVID RIVERA | ZONING HC | REVIEW | Reqs Change | see zoning comments |
| 03/29/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: David Rivera PDSD Zoning Review Section PROJECT: Wang's Kitchen Development Package (1st Review) DP18-0051 TRANSMITTAL DATE: March 29, 2018 DUE DATE: March 30, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is February 23, 2019. 2-06.3.5 - A three-inch by five-inch space shall be reserved in the lower right quadrant of each sheet for an approval stamp. 1. COMMENT: Remove Development Package PDSD approval stamp on all sheets. Reserve a three-inch by five-inch space in the lower right quadrant of each sheet for an approval stamp. The approval stamp will be applied electronically. 2-06.3.6 - Provide a blank three-inch by five-inch block in the lower right corner of the plan adjacent to the title block on the first sheet of the development package for use by Pima County Addressing. 2. COMMENT: Provide the blank space as noted by the standard above. 2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines. 3. COMMENT: List the owner's information as noted by the standard above. 2-06.4.2 - The title block shall include the following information and be provided on each sheet: 2-06.4.2.B - A brief legal description and a statement as to whether the project is a re-subdivision are to be provided. On re-subdivisions, provide the recording information of the existing subdivision plat; 4. COMMENT: Relocate the property address outside the title block and list a brief legal description in the title block of all sheets. 2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet. 5. COMMENT: Provide the development package case number DP18-0051 adjacent to the title block on each sheet. List the administrative address next to the title block of all plan sheets. 2-06.4.7.A - Zoning and Land Use Notes 2-06.4.7.A.6 - If a plan or plat is prepared in conjunction with other applications or overlays or the parcel being developed is subject to conditions of an application processed previously, additional information must be added to the plan. Such applications and overlays include, but are not limited to: annexations; rezonings; special exceptions; Board of Adjustment variances; Design Development Options; Technical Standard Modification Request; overlays (Airport Environs Zone, Environmental Resource Zone, Gateway Corridor Zone, Hillside Development Zone, Historic Preservation Zone, Major Streets and Routes, Rio Nuevo District, Scenic Corridor Zone, WASH); Modification of Development Regulations through the Downtown Area Infill Incentive District or Rio Nuevo District; Downtown Heritage Incentive Zone; or, Design Review Board. Provide the following information on the plan. 6. COMMENT: Add a general on sheet one that this site has been designed to comply with the requirements of UDC Section 5.4, Major Street and Routes. 2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided. 7. COMMENT: If applicable provide the information related to easements as noted by the standard above. 2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks. 8. COMMENT: Provide the recordation information for Grant Road and 4th Avenue as noted by the standard above. 2-06.4.9.A - Draw in all proposed lot lines with approximate distances and measurements. 9. COMMENT: Clarify if the two parcels deeded to the owner have been combined into one parcel whether by Pima County Tax Parcel Combo or a new metes and bounds recorded survey, legal description and deed? 2-06.4.9.F - All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. If the property is being rezoned, use those boundaries and classifications. The basis for this requirement is that some zoning requirements on a project are based on the zoning classification of adjacent property. Also, in some instances, each zone has to be taken into consideration on property that is split by two or more zoning classifications, as each may have different requirements. 10. COMMENT: Review the City Of Tucson GIS map and revise the zoning boundary lines along the south side of the parcels. A portion of east parcel is zoned R-2 along the south 16 feet extending out to 4th avenue property line. 2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. 11. COMMENT: A four foot sidewalk adjacent to the building along the One-Way access lane is required. The minimum width of the one-way access lane is 10 feet unless it is proposed as a fire-lane. 2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC. 12. COMMENT: 2 Accessible parking spaces are required when providing 1 -50 vehicle parking spaces. One of the accessible spaces must be a van accessible space. Annotate the van accessible space on the plan. Revise the parking calculations to reflect the correct number of accessible spaces required and the number and type provided. 2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided. 13. COMMENT: Keynote 25 on sheets 2 and 3 needs to be revised to state that the short term bicycle parking detail 6 is on sheet 4. Provided a detail drawing of the long term facility location and demonstrate compliance with UDC section 7.4.9.D.1-.5. 2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s). 14. COMMENT: Label the use (Food Service) of the building and building height within the building footprint as noted by the standard above. 2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual. 15. COMMENT: Provide a sidewalk in front of the parking spaces along the east side of the building. The minimum width of the sidewalk is four feet clear unless the parked cars overhang the sidewalk area, in which case the sidewalk must be a minimum of six and one-half feet wide. 7-0.4.1.A - At least one sidewalk is required to a project from each street on which the project has frontage, unless there is no vehicular access from a street because of a physical barrier, such as a drainage-way or an unbroken security barrier (e.g., a wall or fence). The sidewalk should be located to minimize any conflict with vehicular access to the project; this project is fronting on two streets. Pedestrian connections via onsite sidewalks connecting to public sidewalks on Grant Road and Fourth Avenue must be provided. The minimum width for these sidewalks is four feet. One of the sidewalks to one of the streets must be noted as the accessible route and meet the minimum 5% running and 2% cross slopes. A pedestrian connection must also be provided to the dumpster location. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 04/02/2018 | KELLY LEE | ZONING-DECISION LETTER | REVIEW | Reqs Change | This review has been completed and resubmittal is required. Please resubmit the following items: 1) Two rolled sets of the plans 2) All approved documents submitted previously 3) A disk containing all items submitted 4) All items requested by review staff 5) All items needed to approve these plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/29/2018 | AHINES2 | OUT TO CUSTOMER | Completed |