Permit Number: DP18-0016
Parcel: 13624446A

Review Status: Completed

Review Details: DEV PKG

Permit Number - DP18-0016
Review Name: DEV PKG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2018 KROBLES1 START PLANS SUBMITTED Completed
01/26/2018 KELLY LEE UTILITIES SOUTHWEST GAS Passed
01/26/2018 KELLY LEE OTHER AGENCIES PIMA ASSN OF GOVTS Passed
01/26/2018 KELLY LEE OTHER AGENCIES U. S. POST OFFICE Passed
01/31/2018 ALEXANDRA HINES COT NON-DSD REAL ESTATE Approved Real Estate has no comments.

Jim Rossi
Jim.Rossi@tucsonaz.gov
02/05/2018 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702

February 2, 2018



WR# 6220702

DSD_CDRC@tucsonaz.gov
thadley@cypresscivil.com
richardgs@elrio.org

Dear Theresa

SUBJECT: El Rio Southeast Exp - 1st Submittal
6940 E Golf Links Rd
DP18-0016

Tucson Electric Power Company has reviewed and approved the development plan.

The new proposed building is in conflict with the existing TEP easement, primary cable, and transformer. The total cost of relocating the transformer and easement is the customers responsibility.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.

If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Rich Harrington
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8726

Should you have any technical questions, please call the area Designer, Roger Asplin @ 918-8258.

Sincerely,
Beth Shelton
Elizabeth "Beth" Shelton
Admin Assistant, Design
02/13/2018 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved No existing or proposed Tucson Parks and Recreation facilities are affected by this expansion.





Howard B. Dutt, RLA

Landscape Architect
Tucson Parks & Recreation
(520) 837-8040

Howard.Dutt@tucsonaz.gov
02/16/2018 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Denied PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

DP18-0016 El Rio Southeast Expansion 02/16/2018

() Final Plat
(X) Development Plan
() Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other - Elevations



SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() Approval
(X) Rezoning history on site
(X) Denied
() Annexation history on site
() No Rezoning history on site - No Resubmittal Required:
() Tentative Plat
() Landscape Plan
() Other










REVIEWER: MM DATE: 02/16/2018

COMMENTS

Site is addressed 6950 E Golf Links Road and is currently being reviewed for DP18-0016. Site has rezoning history to monitor per development package checklist, which indicates rezoning conditions do apply. El Rio southeast expansion is subject to rezoning C9-05-21. Please provide a copy of the preliminary development plan; and list all rezoning conditions for C9-05-21 verbatim on resubmittal of DP18-0016. Please contact John Beall for more information on a minor or major change.
02/16/2018 JVINCEN1 COT NON-DSD FIRE Approved
02/20/2018 MMORENO1 ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Michael Moreno
PDSD Zoning Review Section

PROJECT: El Rio Southeast Expansion
Development Package (1st Review)
DP18-0016

TRANSMITTAL DATE: January 23, 2018
DUE DATE: February 20, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is January 17, 2019.


CONTENT REQUIREMENTS

2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.



2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

1. COMMENT: Provide the development package case number, DP18-0016, adjacent to the title block on each sheet.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes



2-06.4.7.A.3 - If the plan/plat has been prepared in conjunction with a rezoning application, add the following note next to the existing zoning note: "Proposed zoning is ____." List the applicable rezoning file number and conditions of approval. Also place the C9-__-__ (if applicable) and the plan/plat file numbers in the lower right corner of each sheet.

2. COMMENT: Please provide rezoning case number C9-05-21 next to the existing zoning note.


2-06.4.7.A.8 - For development package documents provide:


2-06.4.7.A.8.c - Percentage of building, lot area, or vehicular use area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included; and,

3. COMMENT: As you are providing a new building layout and the prior buildings are not proposed to be built they do not count as existing building, please provide an expansion calculation based on the existing building and the proposed addition it appears that the calculation is about 140%.



2-06.4.8 - Existing Site Conditions

The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

4. COMMENT: Please provide the information noted by the standard.


2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.


2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

5. COMMENT: Please provide the 4' spacing between the bicycle parking racks and provide the location and drawings the for the long term bicycle parking.



2-06.4.9.U - Indicate graphically, where possible, compliance with conditions of rezoning.

6. COMMENT: Please Indicate graphically, where possible, compliance with conditions of rezoning for rezoning case C9-05-21.

2-06.4.9.W - Indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required.

7. COMMENT: All proposed and new signs will have to go through the permit process and will require a new permit.


Additional Comments:

- Please show and provide documentation of how all rezoning condition for C9-05-21 will be met, by submitting a separate letter on resubmittal of DP18-0016.

- Provide a copy of the preliminary development package and contact John Beall for information on whether this will consists of a minor or major change.

- 2-06.4.9.U Indicate graphically, where possible, compliance with conditions of rezoning.

- Please correct and flip sheets 11 & 12.

- Either combine lots or provide a recorded Covenant Regarding Development and Use of Real Property

If you have any questions about this transmittal, Contact Michael.Moreno@Tucson.az.gov at any time during the week.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
02/20/2018 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
02/21/2018 ANDREW CONNOR NPPO REVIEW Approved
02/21/2018 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change UNIFIED DEVELOPMENT CODE
4.1 Identification and Descriptive Data
A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.
The landscape plan will contain the following identification in the lower right corner of each sheet:
Any relevant case number for reviews or modifications that affect the site.
7.6.2. APPLICABILITY
Buildings Greater Than 10,000 Square Feet
On sites where the gross floor area of the existing building(s) is more than 10,000 square feet, expansion in square footage of land area, floor area, lot coverage, or vehicular use area as follows:
If the expansion is 25% or greater or if expansions as of February 15, 1991, cumulatively result in a 25% or greater expansion in land area, floor area, lot coverage, or vehicular use area, the standards of this section apply to the entire site.

7.6. LANDSCAPING AND SCREENING
Show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed for the entire site.
Planting Plan

Location, size, and name of existing vegetation to remain in place

Calculations
" Square footage of the site;
" Minimum width and square footage measured from the inside edge of tree planters in vehicular use areas;
" Length and width of landscape borders and landscape transition borders and number of canopy trees per length; and,
" Square footage of all landscaped borders and calculation of the percentage of vegetative coverage.

Screening
" Location of screening elements;
" Height of screening material and reference point for measurement;
" Nature of screening material (e.g., permanent or temporary as in phased development); and,
" Type of screening material (e.g., masonry wall, wood fence, species of plant material).
" Maintenance Schedule


Ensure that all Zoning and Engineering comments and concerns are addressed prior to landscape approval.
Additional comments may apply.
02/23/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/27/2018 MMORENO1 HC SITE REVIEW Passed
03/01/2018 JOHN VAN WINKLE ENGINEERING REVIEW Approved
03/01/2018 ALEXANDRA HINES ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:
1) Two rolled sets of the plans
2) All approved documents submitted previously
3) A disk containing all items submitted
4) All items requested by review staff
5) All items needed to approve these plans

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2018 KROBLES1 OUT TO CUSTOMER Completed