Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: DP17-0266
Parcel: 11504329B

Review Status: Completed

Review Details: RESUB - SITE/GRADING ALL

Permit Number - DP17-0266
Review Name: RESUB - SITE/GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2018 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Principal Planner

PROJECT: University Commons at Feldman's - Phase I
Development Package (2nd Review)
DP17-0266

TRANSMITTAL DATE: January 26, 2018

DUE DATE: January 30, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is November 8, 2018.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section:

2-06.4.7.A.6 - If a plan or plat is prepared in conjunction with other applications or overlays or the parcel being developed is subject to conditions of an application processed previously, additional information must be added to the plan. Such applications and overlays include, but are not limited to: annexations; rezonings; special exceptions; Board of Adjustment variances; Design Development Options; Technical Standard Modification Request; overlays (Airport Environs Zone, Environmental Resource Zone, Gateway Corridor Zone, Hillside Development Zone, Historic Preservation Zone, Major Streets and Routes, Rio Nuevo District, Scenic Corridor Zone, WASH); Modification of Development Regulations through the Downtown Area Infill Incentive District or Rio Nuevo District; Downtown Heritage Incentive Zone; or, Design Review Board. Provide the following information on the plan.

Previous comment 3. Until provided Zoning cannot approve the DP. COMMENT: The recordation information for the Speedway R/W dedication will have to be listed on the DP prior to approval by zoning.


2-06.4.7.A.6.a - List additional applications and overlays, by case number (if applicable), in lower right corner of each sheet. As a general note provide the type of application processed or overlays applicable, a statement that the project meets the criteria/conditions of the additional application or overlay, the case number, date of approval, what was approved, and the conditions of approval, if any.

Previous comment 4. As this site when fully developed will act as a single site please reference the rezoining case number, C9-17-06, adjacent to the title block on each sheet. COMMENT: If applicable to this project, add the information as noted by the standard above.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

2-06.4.9.E - Proposed land splits or existing lot lines shall be drawn on the plan with dimensions and the identification number and approximate square footage of each lot. (Please be aware that, if land division occurs and the number of lots falls within the definition of subdivision, a subdivision plat is required.) Land splits require a separate permit and review.

Previous comment 7. Until approved Zoning cannot approve the DP. COMMENT: Clarify if the lots have been combined. If not zoning is requesting that a Pima County Tax Parcel Combo be completed prior to approval of the DP.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
01/26/2018 SSHIELD1 H/C SITE REVIEW Approved
01/29/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/30/2018 ANDREW CONNOR LANDSCAPE REVIEW Approv-Cond Ensure that all Zoning and Engineering comments are addressed.
02/12/2018 JVWINKL1 ENGINEERING REVIEW Reqs Change 1: Sheet 4 Keynote 8 states 8.5' width for accessible parking. Dimensions on plan show 8'. Please clarify.

2: Sheet 6: Provide Dimension showing width of path of travel from accessible parking to ramp up - detail E

John Van Winkle
john.van-winkle@tucsonaz.gov
520-837-5007