Permit Number: DP17-0240
Parcel: 12905132L

Address:
1923 E 17TH ST

Review Status: Completed

Review Details: DEV PKG - OK TO SUBMIT

Permit Number - DP17-0240
Review Name: DEV PKG - OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2018 ARUIZ1 START PLANS SUBMITTED Completed
11/01/2018 KLEE1 WWM REVIEW Passed Good morning Frank,



The attached plans are identifying a proposed private 4” bcs that runs through the site and stops at the property line. This new connection will be made into the 8” existing public sewer line I-620 in 17th St. Since you are not proposing any new public infrastructure, a preliminary sewer layout review and approval from Pima County Development Services on behalf of Pima County Regional Wastewater Reclamation Department is not required. Please note that during the building permit process a review by Pima County Development Services will be required for the connection permit of the proposed onsite office building and capacity analysis. Please submit to sewer@pima.gov attention Gerry Koziol at that point in time.



Best Regards,

Joseph




Joseph Godoy

Site Division Manager

Pima County Development Services

201 N. Stone Ave

Tucson, AZ 85701

joseph.godoy@pima.gov

(520) 724-6756
11/01/2018 KELLY LEE ZONING REVIEW Needs Review x
11/01/2018 JOHN VAN WINKLE ENGINEERING REVIEW Denied DP17-0240 (ok to submit)

1) Provide grading cut/fill quantities on plans
2) Provide a drainage statement/report for review that support the proposed grading plan. Report should describe pre-existing water shed and compare to proposed development water shed points of discharge, showing no adverse impact to the surrounding area. Reference City of Tucson Standards Manual for Drainage Design section 2.3.2
3) These are preliminary review comments. This information is needed to enter the project into 1st review

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
11/01/2018 NROSS1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Passed Good Afternoon,

DP17-0240 TI at 1923 E 17th St does not require review by Pima County Addressing.

Thank you,

Robin Freiman

Addressing Official

Pima County Development Services Department

201 N Stone AV – 1st Floor
Tucson, AZ 85701

(520) 724-7570