Permit Number: DP17-0190
Parcel: 127122680

Review Status: Completed

Review Details: RESUB - SITE and/or GRADING

Permit Number - DP17-0190
Review Name: RESUB - SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Arby's @ 5759 E. Broadway Blvd
Parking reconfig
DP17-0190
Building Plan (1st Review)

TRANSMITTAL DATE: August 22, 2017

Administrative Manual 2-06

This comment was not addressed correctly. The maximum overhang is 2'-6" and the plan shows 2'-9" (18' - 15'-3"). You can make up the required distance by reducing the sidewalk width. Per TSM Section 7-01.4.3.A minimum sidewalk width is 4'-0". 2-06.4.9.H.5.a - Fully dimension the relocated accessible vehicle parking spaces to include the "C" Space depth, see UDC Article 7.4.6.D and Table 7.4.6-1 and provide a wheel stop location dimension per UDC Article 7.4.6.H.3.

Once the above comment is addressed Zoning will provide an over-the-counter review. Call or email to schedule this review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
08/22/2017 SSHIELD1 HC SITE REVIEW Reqs Change See Zoning comments