Permit Review Detail
Review Status: Completed
Review Details: DEV PKG
Permit Number - DP17-0144
Review Name: DEV PKG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2017 | ARUIZ1 | START | PLANS SUBMITTED | Completed | |
| 06/21/2017 | ALEXANDRA HINES | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | Notification sent ot agency for information only. No response needed. |
| 06/21/2017 | ALEXANDRA HINES | UTILITIES | SOUTHWEST GAS | Passed | Notification sent ot agency for information only. No response needed. |
| 06/21/2017 | ALEXANDRA HINES | OTHER AGENCIES | U. S. POST OFFICE | Passed | Notification sent ot agency for information only. No response needed. |
| 06/27/2017 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Reqs Change | Associated Documents Located on PRO. Regional Traffic Engineering has one comment on this submittal; have the developer or his representative evaluate ADOT TGP 240 and submit the last page, 240-14, to Regional Traffic for review. The PAD’s distance from the I-10 frontage road and Craycroft rd. intersection may have some impact on intersection’s operation. These could be identified and be presented in a traffic document, to ADOT, for future mitigation. Thank you. |
| 07/05/2017 | SSHIELD1 | ZONING HC | REVIEW | Reqs Change | See Zoning comments |
| 07/05/2017 | ALEXANDRA HINES | OTHER AGENCIES | TUCSON AIRPORT AUTHORITY | Approv-Cond | Thank you for the opportunity to comment on DP17-0144, Los Reales Landfill Phase II; 1st Submittal, a development package application for an approximately 12.28 acre site located south of South Craycroft Road. This project site is specifically located north of the active Los Reales Landfill. The proposed land uses are industrial and utility; establishing an industrial processing and cleaning facility and a sanitation system for household hazardous waste. This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace. The applicant shall file Form 7460 with the FAA at least 45 days before construction activities begin. Any cranes used for the project must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp The Tucson Airport Authority recommends that the property owner record the Avigation Easement document which is included with this comment letter. This document discloses the existence and operational characteristics of the Tucson International Airport to future owners or tenants of the property and further conveys the right to the public to lawfully use the airspace above the property. The Tucson Airport Authority has future long term plans to develop a third far parallel runway at Tucson International Airport, approximately 2 miles southwest of the project site. The instructions included below are in the event that the property owner records the Avigation Easement. The current property owner or person authorized to sign on behalf of the current property owner shall complete, sign, and record the Avigation Easement. Please record the Avigation Easement with the Pima County Recorder's Office. Once the Avigation Easement is recorded please send a copy of the recorded easement to Tucson Airport Authority by either email (send to srobidoux@flytucson.com) or to the mailing address provided below. Scott Robidoux Senior Airport Planner Tucson Airport Authority 7250 South Tucson Boulevard Suite 300 Tucson, AZ 85756 Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811. Respectfully, Scott Robidoux, Senior Airport Planner cc file |
| 07/05/2017 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Principal Planner PROJECT: Los Reales Landfill Phase II Development Package (1st Review) DP17-0144 TRANSMITTAL DATE: July 5, 2017 DUE DATE: July 20, 2017 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is June 2, 2018. 2-06.4.0 CONTENT REQUIREMENTS 1. 2-06.4.3 - Provide the development package case number, DP17-0 144, adjacent to the title block on all sheets. 2. 2-06.4.3 - Adjacent to the title block you show two (2) reference case numbers, D-07-0037 & D-08-0055, revise these numbers as follows "D07-0037 & D08-0055". 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes 3. 2-06.4.7.A.3 - Provide the PAD case number, C9-06-05, adjacent to the title block on all sheets. 2-06.4.7.A.8 - For development package documents provide: 4. 2-06.4.7.A.8.c - Provide a building expansion calculation on the plan. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 5. 2-06.4.9.H.5 - Sheet 4 north end of the proposed vehicle parking provide an access lane width dimension. 6. 2-06.4.9.H.5.a - Sheet 3 the proposed accessible vehicle parking space is required to be a van accessible space, see 2012 IBC Chapter 11Section 1106.1 & 1106.5. Additional comments; 7. Sheet 1 General Note 15 remove the reference to the 2009 ICC A117.1 as it is not applicable for this site and provide the reference to the 2010 ADA Standards for Accessible Design. 8. Sheet 4 Keynote 30 references "DETAIL O, SHEET 6" but there are not details on sheet 6. Once the above comments are addressed Zoning is willing to provide an over-the-counter review. Call or email to schedule an appointment for this review. If you have any questions about this transmittal, please Name, (520) 837-PHONE or email@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 07/06/2017 | ALEXANDRA HINES | PIMA COUNTY | ADDRESSING | Reqs Change | THe attachment is in the Documents folder on PRO. DP17-0144 Los Reales Landfill Phase II / 1st Submittal is being Returned for Corrections by Pima County Addressing. The attached pdf contains Addressing’s comments. Please let me know if you have any questions. Thank you, Robin Freiman Addressing Official Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-7570 |
| 07/10/2017 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Approved | |
| 07/10/2017 | MARTIN BROWN | COT NON-DSD | FIRE | Approved | |
| 07/11/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the site drawings to include the rim elevations of the manholes located upstream of the sewer connection for each building. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2012. |
| 07/12/2017 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Approved | Notification sent ot agency for information only. No response needed. |
| 07/12/2017 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Approved | SEE FACILITIES MAP ON PRO UNDER DOCUMENTS. 4350 E. Irvington Road, Tucson, AZ 85714 Post Office Box 711, Tucson, AZ 85702 July 12, 2017 WR# 6195292 DSD_CDRC@tucsonaz.gov vinnie.hunt@tucsonaz.gov Dear Vinnie SUBJECT: Los E Reales 5300 E Los Reales DP 17-0144 Tucson Electric Power Company has reviewed and approved the development plan. There are no existing facilities in conflict. Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Billiable relocation will require easements. Service at existing phase and voltage can only be relocated overhead. In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to: Tucson Electric Power Company Attn: Rich Harrington New Business Project Manager P. O. Box 711 (DB-101) Tucson, AZ 85702 520-917-8726 Should you have any technical questions, please call the area Designer, Carlos Nunez @ 918-8310. Sincerely, Beth Shelton Elizabeth "Beth" Shelton Admin Assistant, Design |
| 07/14/2017 | JOE LINVILLE | LANDSCAPE | REVIEW | Approved | |
| 07/14/2017 | JOE LINVILLE | NPPO | REVIEW | Approved | |
| 07/18/2017 | PCDS | ENGINEERING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Planning and Development Services Department FROM: Laith Alshami, P.E. - Site Project Manager, Pima County Development Services PROJECT: DP17-0144, Los Reales Landfill Phase II - Development Package (1st Review) TRANSMITTAL DATE: 06/22/2017 DUE DATE: 07/19 /2017 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Engineering review comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the: City of Tucson Unified Development Code (UDC) Article 5, 7 & 8; the UDC Technical Standards Manual (TSM) Section 2, 4, 7, 8, 9, 10 & 11; Tucson Code Chapter 25, 26 & 29; Access Management Guidelines; City of Tucson Standards Manual for Drainage Design and Floodplain Management; Pima County Detention/Retention Manual; Water Harvesting Guidance Manual; and, Drainage Design Manual and Stormwater Retention Detention Manual. SECTION 2-06.0.0 - DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS) Drainage Report Comments: 1. The subject project has been assigned the following Activity Number: DP17-0144. Provide this number on the first page of the Report. 2. The proposed rip rap shall be installed over filter fabric to minimize scour. 3. Clarify the grouted riprap east of the proposed Household Hazardous Waste Facility. Is it proposed on the side of a basin? How does the water get to this basin? Does the basin retain or detain runoff? What is the percolation rate? Is the grouted rip rap proposed to protect a steep slope? What are the top and toe elevations of this slope? IF the grouted rip rap is protecting the side of a basin, why does not the basin bottom have a slope to drain the ponding water? 4. Address onsite water harvesting. The site must be designed to maximize water harvesting. (UDC 7.6.6.C.2) 5. The velocities in Channels A and B are higher than 4 fps, which are considered erosive velocities. Address this issue and clarify how channel erosion can be controlled and minimized. Development Package Comments: 1. The subject project has been assigned the following Activity Number: DP17-0144. Provide this number on all sheets. 2. The proposed rip rap shall be installed over filter fabric to minimize scour. Revise the appropriate details accordingly. 3. Revise Keynote #30, on Sheet 4, to reference Sheet 9. 4. Revise the Plan in accordance with the revision in the Drainage Report. 5. Add the following note: "This project is affected by the City of Tucson Floodplain Regulations." (Ref. 2-06.4.7.B.2.a). 6. Add the following note if applicable: "A floodplain use permit is required for any work proposed in the regulatory floodplain. (Ref. 2-06.4.7.B.2.b). 7. Provide the dimensions and cross sectional details of the regional detention basin and any other proposed basins (Ref.2-06.4.9.N.3). SWPPP Comments: 1. BMP's should be installed at all site discharge points including the basins outlets Additional review comments may be forthcoming due to response to engineering review comments or other review agency comments including owner driven changes to the plan. If you have any questions about this transmittal, please contact Loren Makus,520.837.4927 or loren.makus@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package and Drainage Report. |
| 07/19/2017 | GLENN HICKS | COT NON-DSD | PARKS & RECREATION | Approved | No existing or proposed Tucson Parks and Recreation facilities are affected by this development. Howard B. Dutt, RLA Landscape Architect Tucson Parks & Recreation (520) 837-8040 Howard.Dutt@tucsonaz.gov |
| 07/19/2017 | JOHN BEALL | COT NON-DSD | COMMUNITY PLANNING | Approved | |
| 07/20/2017 | ALEXANDRA HINES | ZONING-DECISION LETTER | REVIEW | Reqs Change | This review has been completed and resubmittal is required. Please resubmit the following items: 1) Two rolled sets of the plans 2) All approved documents submitted previously 3) A disk containing all items submitted 4) All items requested by review staff 5) All items needed to approve these plans |
| 07/20/2017 | ALEXANDRA HINES | COT NON-DSD | ENVIRONMENTAL SERVICES | Approved | The Environmental and General Services Department (EGSD) has completed our review of the DP17-0144 Los Reales Landfill Phase II / 1st submittal. This Development Package includes the construction of the Container Maintenance facility and the Household Hazardous Waste facility at the new landfill entrance area at the Los Reales landfill site. The new landfill entrance area is an 80 acre parcel located immediately north of the Los Reales landfill site. The Planned Area Development -14 for the Los Reales landfill site was adopted by the City of Tucson Mayor and Council in June of 2006. The Planned Area Development -14 included the actual landfill area as well as the new landfill entrance area. General Note No. 20 on Sheet 1 of 24 of the Development Package stated that "Containerized Waste Requirements Per PAD - 14 Document C 6e. No waste bins are required. The uses of the new development includes waste management." Document C 6e states that PAD 14 will comply with the City of Tucson Development Standard 6-01. The Development Standards were replaced in January of 2013 by the Technical Standards Manual. EGSD infers that the Development Package will comply with Section 8 of the Technical Standards Manual. Therefore, EGSD does not have any objections to the solid waste and recycling material management plans for this facility. Please call me if there are any questions concerning this review. Tom Ryan, P. E. City of Tucson - Environmental and General Services Department |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/07/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |