Permit Number: DP17-0137
Parcel: 133413150

Address:
45 N BROWN AV

Review Status: Completed

Review Details: DEV PKG - RESUBMITTAL

Permit Number - DP17-0137
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2017 KROBLES1 START PLANS SUBMITTED Completed
09/19/2017 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approved DP17-0137 Casitas De Cafe / 2nd Submittal is Approved by Pima County Addressing.

Thank you,



Robin Freiman

Addressing Official

Pima County Development Services Department

201 N Stone AV – 1st Floor
Tucson, AZ 85701

(520) 724-7570
09/27/2017 MARTIN BROWN COT NON-DSD FIRE Approved
10/09/2017 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change SECTION 4-02.0.0: FLOODPLAIN, WASH AND ERZ STANDARDS
2.6 Ownership of PRA
Ownership of the protected riparian area shall be provided in one or more of the methods set forth below to insure continued preservation of the area. Forms of ownership of protected riparian areas include:
Where the protected riparian area is on property that remains under the ownership of a single person or entity following the development, the protected riparian area shall be protected through a conservation or public easement or other legal restriction upon further development.
Show all easements and dedications. AM 2-06.4.9.K&L.
10/10/2017 DAVID RIVERA ZONING HC REVIEW Reqs Change see zoning comments.
10/10/2017 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera for Steve Shields - Principal Planner
PDSD Zoning Review Section

PROJECT: Casitas De Café - (Multi-Family Development)
Development Package (1st Review)
DP17-0137

TRANSMITTAL DATE: October 10, 2017
DUE DATE: October 12, 2017

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is July 25, 2018.

SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

1. Follow Up to Previous Comment 4: The second part of comment 4 was not addressed. On the cover sheet, label the "Project Address" as Administrative Address, and list the Administrative Address next the title block of all plan sheets.

2-06.4.3 - The administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

PREVIOUS COMMENT 4: Provide the development package case number, DP17-0137, adjacent to the title block on each sheet.

On the cover sheet, label the "Project Address" as Administrative Address, and list the Administrative Address next the title block of all plan sheets.


2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes


2. Follow Up to Previous Comment 5: Revise general note 30 to state the number of units allowed is 100. 36 x 2.8 ac = 110.8 RAC, density cannot be rounded up.

2-06.4.7.A.5 - On residential projects, list the total number of units/lots proposed.

PREVIOUS COMMENT 5: List as a general note the number of units proposed and allowed; include a density calculation in the general note.


2-06.4.7.A.8 - For development package documents provide:


3. Follow Up to Previous Comment 5: The comment was not addressed as requested. The coverage allowed in the zone shall be listed and the lot coverage includes all building and vehicular use areas. It does not appear that the vehicular use area was included in the lot coverage calculation.

2-06.4.7.A.8.b - Percentage and area in square feet of building and accessory building coverage;

PREVIOUS COMMENT 9: List as a general note the allowed and actual lot coverage calculation. Maximum allowed is 70%.


4. Follow Up to Previous Comment 13: The curb to property line dimensions were not labeled for Brown or Broadway, label as required. Also, label the width of the existing and future sidewalk along Broadway.

2-06.4.8.C - The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

PREVIOUS COMMENT 13: Label the recordation information for Broadway and Brown right of way, whether by plat or roadway recordation or both.

Label the dimension from the existing and future curb to property line along Broadway Boulevard and Brown Avenue. Label the width of the existing sidewalks and the future sidewalk along Broadway.


5. Follow Up to Previous Comment 15: After consultation with staff, the proposed parking structures along the Brown Avenue street perimeter will not be allowed without approval through a Board Of Adjustment variance. Detached accessory structures proposed in the street perimeter of a residential zoned development must be attached to the principal structure, meet setbacks or a B of A variance is required for the building setback if a setback of 21 feet from the nearest edge of travel lane cannot be met and for a detached accessory structure in the street perimeter yard. If applying for a variance, the variance must be approved prior to approval of the DP. Across section drawing or dimensioned detail drawing of the parking area adjacent to Brown Avenue clearly demonstrating that the parking structure meets building setbacks shall be provided.

2-06.4.9.H.5.a - Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

PREVIOUS COMMENT 15: Of the four accessible parking spaces provided one of the spaces must be a Van Accessible parking space an eight foot wide accessible aisle. Label the van accessible parking space and list under the parking calculations that four accessible parking spaces have been provided with one being a van accessible space.

(It appears that the accessible parking space along the east parking area has been designed as a van accessible space with an eight access aisle.) Include a detail drawing showing the van accessible parking space and aisle.


6. Follow Up to Previous Comment 18: Verify with COT Transportation the location of the future curb along the Broadway frontage. The plan indicates a 21-foot curb to property line for the future roadway condition. ( It is acknowledged that Broadway is wider in this area than what is listed on the MS&R map.

2-06.4.9.O - All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.

PREVIOUS COMMENT 18: Label the correct required building setbacks along the Broadway frontage which is the greatest of 21 feet or the height from the back of existing and future curb location. Label the correct building setback along the Brown Avenue frontage which is the greatest of 21 feet or the height from the nearest edge of travel lane.


7. Comment: The proposed development is a re-subdivision of the previously approved Condo Plat. List the legal description as noted on sheet under the LEGAL DESCRIPTION text block in the title block of all plan sheets. The number of units 1-34 should also be listed.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
10/11/2017 PCDS ENGINEERING REVIEW Approved CDRC TRANSMITTAL

TO: Planning and Development Services Department

FROM: Laith Alshami, P.E. - Site Project Manager, Pima County DSD

PROJECT: DP17-0137 Casitas De Cafe - Development Package (2nd Review)

TRANSMITTAL DATE: 10/10/2017

DUE DATE: 10/11/2017

Drainage Report:

The Drainage Report is acceptable and it is hereby approved.

Development Package:

The Development Package appears to be compliant and it is hereby recommended for approval pertaining to Engineering and Floodplain Review

If you have any questions about this transmittal, please contact Loren Makus, 520-837-4927 or loren.makus@tucsonaz.gov.
10/16/2017 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:

1) Two rolled sets of the plans
2) Two copies of the comment response letter
3) All items requested by review staff.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/16/2017 KROBLES1 OUT TO CUSTOMER Completed