Permit Number: DP17-0120
Parcel: 12602006A

Review Status: Completed

Review Details: SITE and/or GRADING

Permit Number - DP17-0120
Review Name: SITE and/or GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2017 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Principal Planner

PROJECT: Speedway & Swan Site Improvemetns
Development Package (1st Review)
DP17-0120

TRANSMITTAL DATE: May 19, 2017

DUE DATE: Walk-thru

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is May 18, 2018.

CONTENT REQUIREMENTS

1. 2-06.4.2.D - As the development package is a separate submittal the page number and total number of pages should be 1 of 1.

2. 2-06.4.3 - Provide the development package case number, DP17-0120 , adjacent to the title block on all sheets. 2-06.4.7 - General Notes

The following general notes are required. Additional notes specific to each plan are required where applicable.

3. 2-06.4.7.A.4 - The use listed under project information note 4 is not correct and should be listed as Automotive Service Major subject to Use Specific Standard 4.9.13.E.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

4. 2-06.4.9.F - The zoning listed under project information note 4 is not correct and should be C-2.

5. 2-06.4.9.H.5.a - The wheel stop location dimension shown on the sidewalk detail is not correct. See UDC Article 7.4.6.H.3.

6. 2-06.4.9.Q - The use listed within the foot print is not correct and should be listed as auto repair major.
Once the above comments are addressed Zoning will provide an over-the-counter review. Call or email to schedule this review.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
05/19/2017 SSHIELD1 NPPO REVIEW Passed
05/19/2017 SSHIELD1 LANDSCAPE REVIEW Passed
05/19/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/19/2017 SSHIELD1 ENGINEERING REVIEW Passed
05/19/2017 SSHIELD1 ADA REVIEW Passed
05/19/2017 SSHIELD1 H/C SITE REVIEW Approved
05/24/2017 KROBLES1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/24/2017 KROBLES1 OUT TO CUSTOMER Completed