Permit Number: DP17-0102
Parcel: 14032100A

Address:
6133 S ANTRIM LP

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Permit Number - DP17-0102
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2017 ARUIZ1 START PLANS SUBMITTED Completed
05/02/2017 KELLY LEE UTILITIES SOUTHWEST GAS Passed Informational only.
05/02/2017 KELLY LEE OTHER AGENCIES U. S. POST OFFICE Passed Informational only.
05/02/2017 KELLY LEE OTHER AGENCIES PIMA ASSN OF GOVTS Passed Informational only.
05/03/2017 KLEE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved Ray Water Assurance Letter in PRO/SIRE
05/08/2017 ED ABRIGO PIMA COUNTY ASSESSOR Reqs Change Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR

TO: CDRC Office
Subdivision Review
City of Tucson


FROM: Ada Griffin
GIS Cartographer
Pima County Assessor's Office


DATE: May 8, 2017


RE: Assessor's Review and Comments Regarding:

DP17-0102 TENTATIVE PLAT DESERT POINT 2

_

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Plat meets Assessor's Office requirements.
___X___ Plat does not meet Assessor's Office requirements.

COMMENTS:


" RE: THE TITLE BLOCK IN THE LOWER RIGHT HAND CORNER. THE REQUIRED INFORMATION IS ALL THERE, HOWEVER THE NUMBER OF LOTS & COMMON AREA INFORMATION SHOULD IMMEDIATELY FOLLOW THE SUBDIVISION NAME. THE RESUBDIVISION INFORMATION SHOULD FOLLOW NEXT, THEN THE SECTION INFORMATION.

" GENERAL NOTES #11 STATES PARCEL ID NUMBERS, HOWEVER THEY APPEAR TO BE INCORRECT. (THE LISTED PARCEL NUMBERS WITHIN THE GENERAL NOTES NO LONGER EXHIST. OWNERSHIP IS CORRECT AS TO THE PARCELS LISTED BELOW)

OUR RECORDS INDICATE UPDATED PARCELS ARE:

140-32-085A, 140-32-086A, 140-32-087A, 140-32-097A, 140-32-098A,
140-32-099A, 140-32-100A

NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
05/09/2017 ALEXANDRA HINES PIMA COUNTY ADDRESSING Reqs Change See attachments in documents folder on PRO.

DP17-0102 Desert Point 2 Subdivision / 1st Submittal is being Returned for Corrections by Pima County Addressing.

The attached pdf contains Addressing’s comments.

Please let me know if you have any questions.

Thank you,

Robin Freiman
Addressing Official
Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-7570
05/11/2017 ALEXANDRA HINES OTHER AGENCIES TUCSON AIRPORT AUTHORITY Approv-Cond May 10, 2017

Thank you for the opportunity to comment on DP17-0102, Desert Point 2 Subdivision; 1st Submittal, a tentative plat subdivision application for an approximately 8.37 acre site located east of South Alvernon Way, north of East Valencia Road, and south of East Benson Highway. This project site is specifically located north of the intersection of East Spring Water Drive and South Antrim Loop. The proposed land use is residential.

This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.

The applicant shall file Form 7460 with the FAA at least 45 days before construction activities begin. Any cranes used for the project must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp.

The Tucson Airport Authority conditionally approves the subject request contingent upon the following condition of approval, as noted below. This condition should be identified in the general notes of the approved development plan.

Conditions of approval:

"That prior to the City's approval of any construction permit for a permanent building, the property owner shall record the Avigation Easement prior to the subdivision process which discloses the existence, and operational characteristics of the Tucson International Airport to future owners or tenants of the property and further conveys the right to the public to lawfully use the airspace above the property. The content of such documents shall be according to the form and instructions provided."

The current property owner or person authorized to sign on behalf of the current property owner shall complete, sign, and record the Avigation Easement. Please record the Avigation Easement with the Pima County Recorder's Office. Once the Avigation Easement is recorded please send a copy of the recorded easement to Tucson Airport Authority by either email (send to srobidoux@flytucson.com) or to the mailing address provided below.

Scott Robidoux
Airport Planner
Tucson Airport Authority
7250 South Tucson Boulevard
Suite 300
Tucson, AZ 85756

The developer shall provide the Airport Disclosure Statement form, at time of sale, to the new property owners with new unit purchases. In the event this proposed project does not involve the sale of new units, but is instead offering rental residential units to the public, the new tenant of the rental unit shall be provided a copy of the Airport Disclosure Statement form. The intent of the Airport Disclosure Statement form is to educate and notify the new residents that they are living near an airport. The new property owner or new tenant shall forward a signed copy of the Airport Disclosure Statement form to:

Scott Robidoux
Airport Planner
Tucson Airport Authority
7250 South Tucson Boulevard
Suite 300
Tucson, AZ 85756

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.

Respectfully,

Scott Robidoux,
Airport Planner

cc file
05/11/2017 ALEXANDRA HINES PIMA COUNTY WASTEWATER Reqs Change May 11, 2017

To: Paul Nzomo
Coronado Engineering & Development, Inc.
____________________________________
From: Hussein Al Zubaidi, RWRD (520) 724-6404


Subject: DESERT POINT 2 LOTS 1-42
P17WS00042
PSL-1ST Submittal

The Pima County Regional Wastewater Reclamation Department (PCRWRD) has reviewed the proposed sewer design for the above-referenced project. The Pima County Regional Wastewater Reclamation Department has found the following deficiencies in the above referenced submittal of the Preliminary Sewer Layout (PSL), based upon PCRWRD Engineering Design Standards (EDS) 2016.

1- Sheet #1: call out General public sewer notes.

GENERAL SEWER NOTES

1. ON-SITE SANITARY SEWERS, EXCEPT PUBLIC SEWERS WITHIN PUBLIC SEWER EASEMENTS OR RIGHTS- OF-WAY, WILL BE PR/VA TE AND WILL BE CONSTRUCTED, OPERA TED AND MAINTAINED ON A PRIVATE BASIS. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY REGIONAL WASTEWATER RECLAMATION DEPARTMENT.

2. THE REQUIRED OFF-SITE PUBLIC SANITARY SEWER LINE WILL BE DESIGNED AND CONSTRUCTED TO PIMA COUNTY REGIONAL WASTEWATER RECLAMATION DEPARTMENT STANDARDS.

3. ANY WASTEWATER DISCHARGED INTO THE PUBLIC SANITARY SEWERAGE SYSTEM SHALL MEET THE REQUIREMENTS OF THE INDUSTRIAL WASTE ORDINANCE (PIMA COUNTY ORDINANCE NO. 1991-140, AS AMENDED).

4. MAINTENANCE AND OPERATION OF THE PRIVATE SANITARY SEWER TO ITS POINT OF CONNECTION TO THE PUBLIC SANITARY SEWER IS THE RESPONSIBILITY OF THE PROPERTY OWNER.

5. ON-SITE SANITARY SEWERS, EXCEPT PUBLIC SEWERS WITHIN PUBLIC SEWER EASEMENTS OR RIGHTS- OF-WAY, WILL BE PR/VA TE AND WILL BE CONSTRUCTED, OPERA TED AND MAINTAINED ON A PR/VA TE BASIS, AND IN ACCORDANCE WITH AN APPROVED OPERATION AND MAINTENANCE PLAN, IF REQUIRED. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTYWASTEWA TER MANAGEMENT DEPARTMENT.

6. A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM PIMA COUNTY REGIONAL WASTWATER RECLAMATION DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT.

7. CONSTRUCTION AUTHORIZATION FROM THE PIMA COUNTY DEPARTMENT OF ENVIROMENTAL QUALITY IS REQUIRED BEFORE BEGINNING ANY WORK ON THIS PROJECT. APPROVAL OR THIS DEVELOPMENT PLAN DOES NOT CONSTITUTE CONSTRUCTION AUTHORIZATION.

This office will require a revised set of plans, and a response letter, addressing these comments. Additional comments may be made during the review of these documents. All comments cited in this letter are based upon PCRWRD Engineering Design Standards 2016 and PCRWRD Standard Specifications and Details for Construction 2016.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the Preliminary Sewer Layout. The fee for the first submittal is $166 plus $50 per Sheet. For the second submittal, the review fee is $50.00 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next plan submittal will require a review fee of $50.00 made payable to Pima County Treasurer.

If you have any questions regarding this matter please contact me at your convenience.

Cc. Lorenzo Hernandez, P.E., RWRD
Tom Porter, P.E., RWRD
Francisco Galindo, P.E., RWRD
05/11/2017 JVINCEN1 COT NON-DSD FIRE Reqs Change Unable to locate all fire hydrants. Please clearly delineate all proposed and existing hydrants. Refer to section 507 of the International Fire Code for spacing quidelines.
05/17/2017 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved Regional Traffic Engineering has comments on this submittal and supports its acceptance.

The location of the subdivision will have no impact to any ADOT facilities because of the proposed location. Thank you.
05/18/2017 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
05/22/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Based on the proposed first floor elevation of lot 20 and the rim elevation of manhole 7, a backwater valve will be required for lot 20. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson.
08/04/2017 AHINES2 LANDSCAPE REVIEW Needs Review
08/04/2017 AHINES2 ENGINEERING REVIEW Needs Review
08/04/2017 AHINES2 H/C SITE REVIEW Needs Review
08/04/2017 PATRICIA GEHLEN ZONING REVIEW Needs Review
08/04/2017 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Needs Review
08/04/2017 GLENN HICKS COT NON-DSD PARKS & RECREATION Needs Review
08/04/2017 AHINES2 NPPO REVIEW Needs Review
08/04/2017 ALEXANDRA HINES ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:
1) Two rolled sets of the plans
2) All approved documents submitted previously
3) A disk containing all items submitted
4) All items requested by review staff
5) All items needed to approve these plans
08/04/2017 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2017 QJONES1 APPROVAL SHELF Completed
09/26/2017 QJONES1 OUT TO CUSTOMER Completed
09/26/2017 QJONES1 REJECT SHELF Completed