Permit Review Detail
Review Status: Completed
Review Details: TENTATIVE PLAT REVIEW
Permit Number - DP17-0036
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/15/2017 | DTAKAKI1 | START | PLANS SUBMITTED | Completed | |
| 02/15/2017 | DTAKAKI1 | UTILITIES | SOUTHWEST GAS | Passed | For information purpose only |
| 02/15/2017 | DTAKAKI1 | OTHER AGENCIES | U. S. POST OFFICE | Passed | For information purpose only |
| 02/15/2017 | DTAKAKI1 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | For information purpose only |
| 02/24/2017 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Approv-Cond | Tucson Electric Power Co., (TEP) has reviewed and approves the Tentative Plat for First Five Subdivision submitted on February 14, 2017. In the title block please identify this as a resubdivision of the previous plat. If you have any questions, please contact me at 520-917-8744. Thank you, Mary Burke Right of Way Agent III Tucson Electric Power Co. Mail Stop HQE613 PO Box 711, Tucson, AZ 85702 Office - 520-917-8744 Cell - 520-401-9895 mburke@tep.com |
| 02/27/2017 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Principal Planner PROJECT: First Five Development Package (1st Review) DP17-0036 TRANSMITTAL DATE: March 01, 2017 DUE DATE: March 14, 2017 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is February 12, 2018. CONTENT REQUIREMENTS 1. 2-06.4.3 - Provide the development package case number, DP17-0036, adjacent to the title block on all sheets. 2-06.4.7 - General Notes The following general notes are required. Additional notes specific to each plan are required where applicable. 2-06.4.7.A - Zoning and Land Use Notes 2. 2-06.4.7.A.4 - General Note 4 listed the existing use as "SINGLE FAMILY" but based on current aerial photos the existing use should be vacant. 2-06.4.7.A.8 - For development package documents provide: 3. 2-06.4.7.A.8.b - Under General Note 14 you list "LOT" coverage, lot coverage is not applicable to an FLD development and should be listed as site coverage. 2-06.4.9 - Information on Proposed Development The following information on the proposed project shall be shown on the drawing or added as notes. 4. 2-06.4.9.H.5.a - Per 8.7.3.I.2 an alley abutting and existing development cannot be used to access vehicle parking. That said the proposed access off of the alley to Lots 1 & 2 is not allowed. 5. 2-06.4.9.L - There is a proposed "14' PRIVATE SEWER EASEMENT" shown on the plan. Provide documentation, addressing maintenance /repair of the proposed site walls shown within the easement if maintenance is required on the private sewer. 6. 2-06.4.9.O - The street setbacks shown under General Note 14 are not correct and should be listed as 21' or the height of the proposed exterior wall measure from the nearest edge of travel lane. 7. 2-06.4.9.O - General Note 14 under the building setbacks there is a "NOTE: SETBACKS ARE FROM THE PROPERTY LINE" this note only applies to interior lot lines and should be defined as such or removed from the plan. 8. 2-06.4.9.V - Clarify how mail service will be dealt with. 2-06.5.0 FLEXIBLE LOT DEVELOPMENT (FLD - ADDITIONAL REQUIREMENTS) 2-06.5.3 Additional Information The following are required in addition to the requirements of the tentative plat or site plan, whichever is applicable: 9. 2-06.5.3.D - Provide dimensioned building elevations of all proposed units with your next submittal 10. 2-06.5.3.G.1 - Provide three copies of the Covenants, Conditions, and Restrictions (CC&Rs) regarding the homeowner's association's responsibility for the ownership and maintenance of commonly-owned property. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 03/01/2017 | SSHIELD1 | H/C SITE | REVIEW | Approved | |
| 03/03/2017 | MARTIN BROWN | COT NON-DSD | FIRE | Approved | |
| 03/03/2017 | AHINES2 | PIMA COUNTY | ADDRESSING | Reqs Change | DP17-0036 / Algoaibi Subdivision / 1210 S 9th Av / 1st Submittal is being Returned for Corrections by Pima County Addressing. Please see the comments in the attached pdf plan set. Thank you, Robin Freiman Addressing Official Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-7570 |
| 03/03/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 03/08/2017 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Approved | |
| 03/09/2017 | KLEE1 | OTHER AGENCIES | TUCSON AIRPORT AUTHORITY | Approv-Cond | Attachments & Comment from TIA located in PRO, plans under review. https://www.tucsonaz.gov/PRO/Command?command=SearchSire&actno=DP17-0036 &sirecabinet=P&streetno=1210.0&streetdir=S &streetnm=9TH AV &struct=&floor=&unit=&SearchButton=AssociatedDocumentsandPlans February 21, 2017 Dear Mr. Takaki, Thank you for the opportunity to comment on DP17-0036, Algoaibi Subdivision, 1210 S 9th Av; 1st Submittal, a development plan application for an approximately 0.39 acre site located on the northwest corner of West 23rd Street and South 9th Avenue. The proposed land use is residential. This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace. The applicant shall file Form 7460 with the FAA at least 45 days before constructions activities begin. Any cranes used for the project must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp. The Tucson Airport Authority conditionally approves the subject request contingent upon the following condition of approval, as noted below. This condition should be identified in the general notes of the approved development plan. Conditions of approval: "That prior to the City's approval of any construction permit for a permanent building, the property owner shall record the Avigation Easement prior to the subdivision process which discloses the existence, and operational characteristics of the Tucson International Airport to future owners or tenants of the property and further conveys the right to the public to lawfully use the airspace above the property. The content of such documents shall be according to the form and instructions provided." The current property owner or person authorized to sign on behalf of the current property owner shall complete, sign, and record the Avigation Easement. Please record the Avigation Easement with the Pima County Recorder's Office. Once the Avigation Easement is recorded please send a copy of the recorded easement to Tucson Airport Authority by either email (send to srobidoux@flytucson.com) or to the mailing address provided below. Scott Robidoux Airport Planner Tucson Airport Authority 7250 South Tucson Boulevard Suite 300 Tucson, AZ 85756 The developer shall provide the Airport Disclosure Statement form, at time of sale, to the new property owners with new unit purchases. In the event this proposed project does not involve the sale of new units, but is instead offering rental residential units to the public, the new tenant of the rental until shall be provided a copy of the Airport Disclosure Statement form. The intent of the Airport Disclosure Statement form is to educate and notify the individual that they are living near an airport. The new property owner or new tenant shall forward a signed copy of the Airport Disclosure Statement form to: Scott Robidoux Airport Planner Tucson Airport Authority 7250 South Tucson Boulevard Suite 300 Tucson, AZ 85756 Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811. Respectfully, Scott Robidoux, Airport Planner cc file |
| 03/09/2017 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | Regional Traffic Engineering has no comments on this submittal and supports its acceptance. The development will have no considerable impact to any adjacent ADOT facilities. Thank you. |
| 03/10/2017 | KLEE1 | DESIGN PROFESSIONAL | REVIEW | Passed | Review not required per UDC Section 8.7.3.M |
| 03/10/2017 | KLEE1 | PIMA COUNTY | WASTEWATER | Passed | No review required per Pima County worksheet. |
| 03/10/2017 | GLENN HICKS | COT NON-DSD | PARKS & RECREATION | Approved | No existing or proposed Tucson Parks and Recreation facilities are affected by this development. Howard B. Dutt, RLA Landscape Architect Tucson Parks & Recreation (520) 837-8040 Howard.Dutt@tucsonaz.gov |
| 03/13/2017 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | UNIFIED DEVELOPMENT CODE 4.1 Identification and Descriptive Data A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan. 7.6.4. LANDSCAPE STANDARDS: 8.7.3. FLEXIBLE LOT DEVELOPMENT (FLD) Landscaping, Screening and Wall Requirements 1. FLD projects shall comply with Section 7.6, Landscaping and Screening Standards, except as otherwise provided by this section. Use of the Public Right-of-Way Required landscaping may be placed in the public right-of-way, if the following standards are met: 1. The landscaping is approved by the City Engineer or designee and complies with the City Engineer's standards on construction, irrigation, location, and plant type; 2. All vegetation complies with the standards of Section 7.6.4, Landscaping Standards; and, 3. The landscaping does not interfere with the use of the sidewalk. Obtain permission for the use of ROW and add the appropriate notes on landscape plans. Ensure that all Zoning and Engineering comments and concerns are addressed prior to landscape approval. Additional comments may apply. |
| 03/14/2017 | AHINES2 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Approved | Water Availability Letter in Documents folder on PRO. |
| 03/15/2017 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Approved | Office of the Pima County Assessor 240 N STONE AVENUE Tucson, Arizona 85701 BILL STAPLES ASSESSOR TO: CDRC Office Subdivision Review City of Tucson (FAX# 791-5559) FROM: Julieann Arechederra GIS Cartographer Pima County Assessor's Office DATE: March 15, 2017 RE: Assessor's Review and Comments Regarding Tentative plat: First Five DP17-0036 * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * X Plat meets Assessor's Office requirements. _______ Plat does not meet Assessor's Office requirements. COMMENTS: NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED. |
| 03/15/2017 | ARUIZ1 | NPPO | REVIEW | Completed | per aconnor |
| 03/17/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. The drainage statement is accepted for this tentative plat package. 2. Clearly show on the grading and drainage plan the areas of water harvesting as described in the drainage statement. 3. Once the access to lots 1 and 2 are resolved, since alley access is not allowed, I will be willing to review this at the counter. |
| 03/22/2017 | KLEE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | This review has been completed and resubmittal is required. Please resubmit the following items: 1) Two rolled sets of the plans 2) All approved documents submitted previously 3) A disk containing all items submitted 4) All items requested by review staff 5) All items needed to approve these plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/09/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |