| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/10/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Reqs Change | DATE: October 11, 2016 DUE DATE: October 25, 2016 SUBJECT: Emery Park Place TO: Gregg Sasse LOCATION: 140 E Drexel Road REVIEWERS: Paul Baughman, PE, CFM ACTIVITY: DP16-0169 SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed Development Plan Package. The following items need to be addressed: 1) Please consider placing all notes not required by City code in a separate section for notes to the contractor/engineer. This will make it easier for the City inspector to only focus on enforcing City requirements during inspections. 2) Per TSM 2-01.4.1C6 and section 4.7.1 (page 14) of the geotechnical report please update General Note 17 to reflect requirement that concrete that functions as pavement (ie. cars drive over it) provide 4,000 psi compressive strength. 3) Per TSM 2-01.4.1C6 and section 4.2.3 (page 6) of the geotechnical report please update grading note 7 to require scarification of 10 inches instead of 6 inches. If you have any comments questions or wish to discuss new information, please call or email me at 520-837-5007 or paul.baughman@tucsonaz.gov. |
| 10/11/2016 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | TO: Development Services Department Plans Coordination Office FROM: David Rivera for Steve Shields - Principal Planner PDSD Zoning Review Section PROJECT: DP16-0169 - Emery Park Place Grading Plan Grading Plan (1st Review) 140 E. Drexel Road TRANSMITTAL DATE: October 11, 2016 DUE DATE: October 25, 2016 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the grading plan and compared it to the current version of the Minor Subdivision plat drawings for consistency as it relates to the zoning review purview of the grading plan. While the grading plan is consistent with the current version of the Minor Subdivision Plat zoning cannot approve the GP until it has been approved by the Engineering review section. Also approval of the GP cannot be granted until the Minor subdivision is approved and recorded. (Contact Patricia Gehlen for more information on permitting the grading plan for a subdivision with no tentative plat. 2. COMMENT: Zoning will review the grading plan on the next submittal and compare it to the approved Minor subdivision plat to assure that the GP is consistent with the Minor subdivision an as it relates to the zoning review purview. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
| 10/17/2016 | ANDREW CONNOR | NPPO | REVIEW | Reqs Change | Approval of the Grading Plan cannot be granted until the Minor subdivision is approved and recorded. Ensure that all Engineering comments are addressed. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/19/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |