Permit Review Detail
Review Status: Completed
Review Details: DEV PKG - RESUBMITTAL
Permit Number - DP16-0156
Review Name: DEV PKG - RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/19/2016 | KROBLES1 | START | PLANS SUBMITTED | Completed | |
12/19/2016 | DAVID RIVERA | ZONING HC | REVIEW | Reqs Change | see zoning comments. |
12/19/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
12/19/2016 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera for Steve Shields - Principal Planner PDSD Zoning Review Section PROJECT: U-Haul Facility - 1265 E Benson Hwy. Zoning C-2 Development Package (1st Review) DP16-0156 TRANSMITTAL DATE: December 7, 2016 DUE DATE: December 20, 2016 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is August 30, 2017. SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS) Section 1. Follow Up To Previous Comment 14: The location or detail drawing of the long term bicycle facility could not be verified on the DP site plan sheet 2 or detail drawing on sheet 6. Draw and label the location of the long term facility within the building footprint. Review section 7.4.9.D demonstrate how compliance with the 7.4.9.D will be accomplished. 2-06.4.9.H.5.d - Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided. PREVIOUS COMMENT 14: The Retail use is Vehicle Rental and Sales and has a bicycle parking requirement as follows, 2 Short Term spaces and 1 space per 12,000 sq. ft. of gross floor area or minimum of 2 spaces. Revise the bicycle parking calculation accordingly and include fully dimensioned detail drawings of the short and long term bicycle facilities. The locations of the short and long term facilities must be drawn and labeled on the site plan sheet. Short term facilities must be within 50 feet of the main entrance. 2. Comment: Zoning is willing to review the DP over the counter once the changes requested have been made to the DP. Unfortunately I am in the office only two days a week but I am available to review the DP plans over the counter due to the minor changes needed. If the applicant wishes to have zoning review the plans over the counter call in advance for an appointment for either Tuesday or Wednesday between the hours of 8:00 and 4:00 either day. My number is 837-4957 or you can email me at David.Rivera@tucsonaz.gov. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package |
12/19/2016 | PGEHLEN1 | OTHER AGENCIES | TUCSON AIRPORT AUTHORITY | Approv-Cond | Avagtion Easement is located in SIRE/PRO. Follow the link below and look under documents and plans. https://www.tucsonaz.gov/PRO/Command?mode=permit&firstTime=true&number_key=dp16-0156&command=InitialProcess&SearchButton=Search December 16, 2016 Dear Ms. Hines, Thank you for the opportunity to comment on DP16-0156, U-Haul; 2nd Submittal, a development package application for an approximately 3.69 acre site located on the northeast corner of East Ajo Way and East Benson Highway. The proposed land use is commercial. This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace. The applicant shall file Form 7460 with the FAA. Any cranes used for the project must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp. The Tucson Airport Authority conditionally approves the subject request contingent upon the following condition of approval, as noted below. This condition should be identified in the general notes of the approved development plan. Conditions of approval: "That prior to the City's approval of any construction permit for a permanent building, the property owner shall record the Avigation Easement prior to the subdivision process which discloses the existence, and operational characteristics of the Tucson International Airport to future owners or tenants of the property and further conveys the right to the public to lawfully use the airspace above the property. The content of such documents shall be according to the form and instructions provided." "That development shall not cause or potentially affect aviation in the vicinity of the site, including but not limited to, physical obstructions to aircraft operations, interference with operations by way of electrical static, visual obstructions through emissions or glare, and/or the open storage of petroleum products, explosive materials, or materials which attract or lead to the concentration of wildlife." The current property owner or person authorized to sign on behalf of the current property owner shall complete, sign, and record the Avigation Easement. The Avigation Easement shall be recorded with the Pima County Recorder's Office. Once the Avigation Easement is recorded please send a copy of the recorded easement to Tucson Airport Authority by either email (send to srobidoux@flytucson.com) or to the mailing address provided below. Scott Robidoux Airport Planner Tucson Airport Authority 7250 South Tucson Boulevard Suite 300 Tucson, AZ 85756 Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811. Respectfully, Scott Robidoux, Airport Planner cc file |
12/19/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the rim elevation of the next upstream manhole. [Initial comment: Revise the site drawing to include the rim elevation of the next manhole to which the building sewer will be connecting. Determine if a backwater valve will be needed per Section 715.1, IPC 2012, as amended by the City of Tucson. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2012.] |
12/19/2016 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | The existing fire hydrant is too far away to meet the distance requirements. TFD is requesting two additional fire hydrants to be installed at each new driveway entrance. Please show these new fire hydrants on Utility plan. |
12/20/2016 | JOE LINVILLE | LANDSCAPE | REVIEW | Reqs Change | 1) Revise the plans to provide screening per UDC Table 7.6.4-I. A six foot high screen is required for RV Storage, Outdoor Storage, and Billboards. 2) Provide canopy trees per UDC 7.6.4.B.1.a.(1). One tree per every four spaces and each space must be within 40 feet of a tree. |
12/20/2016 | TIM ROWE | PIMA COUNTY | WASTEWATER | Reqs Change | We haven’t received 2nd submittal From: DSD_CDRC DSD_CDRC [DSD_CDRC@tucsonaz.gov] Sent: Monday, December 19, 2016 9:02 AM To: Hussein Al Zubaidi <Hussein.AlZubaidi@pima.gov>; Thomas Porter <Thomas.Porter@pima.gov> Subject: Fwd: Re: DP16-0156 U-Haul / 2nd Submittal Morning: Review is due today. Thanks >>> DSD_CDRC 11/29/2016 9:34 AM >>> Dear Reviewers: This is the second (2nd) review of the proposed DP16-0156 UHAUL. For the plans, please refer to the paper copy in the plans room or the electronic copy at http://www.tucsonaz.gov/PRO/Command?mode=permit&firstTime=true&number_key=DP16-0156&command=InitialProcess . Please provide comments based on all applicable codes and ordinances. Should you deny the review, you will receive the resubmittal of this plan for further review and comment. The review comments are due by Monday, December 19, 2016. Please post your comments in Permits Plus as you normally do or send the comments to: DSD_CDRC@tucsonaz.gov. Scott-- The proposed development is within the Avigation Easement and Disclosure Areas. The proposed use is for a U-Haul Facility. This is the second submittal. Would you like the applicant to add a general note? Thank you, Alexandra Hines and Kelly Lee |
12/21/2016 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Reqs Change | This review has been completed and resubmittal is required. Please resubmit the following items: 1) Two rolled sets of the plans 2) All approved documents submitted previously 3) A disk containing all items submitted 4) All items requested by review staff 5) All items needed to approve these plans |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/25/2017 | LBOJORQ1 | OUT TO CUSTOMER | Completed |