Permit Number: DP16-0098
Parcel: 116232100

Address:
993 S FREEWAY

Review Status: Completed

Review Details: REVISION - GRADING

Permit Number - DP16-0098
Review Name: REVISION - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2018 DAVID RIVERA ZONING REVIEW Approved
06/26/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change DP16-0098

1) Sheet C4, Detail A, Basin cross section shows a slope of 2 horizontal to 1 vertical. Drainage report addendum indicates that the water depth in the basin will be 2.6'. Per the City of Tucson Storm Water Detention/Retention Manual security barriers must be provided at the top of all basin side slopes steeper than 4:1 where water depths exceed 2'. Provide and show on plans a minimum 42" tall barrier around proposed basin. Suggest using PAG standard detail 105, see following link http://apps.pagnet.org/StandardSpecifications/Documents/Drawings/PAGStdDtl-105.pdf
2) Engineering can conduct an over the counter review once the above comment is addressed and a new work flow has be opened at the permit counter

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007

Final Status

Task End Date Reviewer's Name Type of Review Description
09/12/2018 QJONES1 APPROVAL SHELF Completed
09/12/2018 QJONES1 OUT TO CUSTOMER Completed
09/12/2018 QJONES1 REJECT SHELF Completed