Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2016 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change DATE: June 6, 2016
DUE DATE: June 27, 2016
SUBJECT: New Duplexes
TO: Scott Isles
LOCATION: 1324 to 1336 N Highland Avenue
REVIEWERS: Paul Baughman, PE, CFM
ACTIVITY: DP16-0089
SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed Development Plan Package. The following items need to be addressed:
1) Per AM 2-06.4.3 please add the case number (DP16-0089).
2) Per TSM 8-01.8.0 please provide a waste stream calculation on the plans.
If you have any comments questions or wish to discuss new information, please call or email me at 520-837-5007 or paul.baughman@tucsonaz.gov.
06/07/2016 DRIVERA1 ADA REVIEW Reqs Change See zoning comments
06/07/2016 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera for Steve Shields Principal Planner
PDSD Zoning Review Section

PROJECT: Multi-family Development - 2-Duplexes 4 bedrooms each
Development Package (1st Review)
DP16-0089

TRANSMITTAL DATE: June 7, 2016

DUE DATE:JUne 27, 2016

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is May 27, 2017.


2-06.3.6 - Provide a blank three-inch by five-inch block in the lower right corner of the plan adjacent to the title block on the first sheet of the development package for use by Pima County Addressing.

1. COMMENT: Provide on the cover sheet the 3"x5" block as noted by the standard above.

CONTENT REQUIREMENTS

2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.

2. COMMENT: List the Owner / Developer's email address on the cove sheet.

2-06.4.2 - The title block shall include the following information and be provided on each sheet:

3. COMMENT: Provide the development package case number, DP16-0089, adjacent to the title block on each sheet.



2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

4. COMMENT: Revise the use note under the Zoning Information text block to state Family Dwelling: Multifamily Use.

2-06.4.7.A.6 - If a plan or plat is prepared in conjunction with other applications or overlays or the parcel being developed is subject to conditions of an application processed previously, additional information must be added to the plan. Such applications and overlays include, but are not limited to: annexations; rezonings; special exceptions; Board of Adjustment variances; Design Development Options; Technical Standard Modification Request; overlays (Airport Environs Zone, Environmental Resource Zone, Gateway Corridor Zone, Hillside Development Zone, Historic Preservation Zone, Major Streets and Routes, Rio Nuevo District, Scenic Corridor Zone, WASH); Modification of Development Regulations through the Downtown Area Infill Incentive District or Rio Nuevo District; Downtown Heritage Incentive Zone; or, Design Review Board. Provide the following information on the plan.

2-06.4.7.A.6.a - List additional applications and overlays, by case number (if applicable), in lower right corner of each sheet. As a general note provide the type of application processed or overlays applicable, a statement that the project meets the criteria/conditions of the additional application or overlay, the case number, date of approval, what was approved, and the conditions of approval, if any.

5. COMMENT: While the property is not zoned Historic, the buildings on both lots are older than 50 years. A separate review and approval for the demolition of the structures will be required. If the HPZ demolition application has been processed, reference the case number and approval date related to the HPZ review. List if any, conditions of the HPZ review as a general note. If the demolition has occurred as a result of an approved HPZ reference the PDSD activity number of the demolition application.

2-06.4.7.A.8 - For development package documents provide:

2-06.4.7.A.8.a - Floor area for each building;

6. COMMENT: Clarify why the gross floor area of each building is noted as 2,108 and yet the square footage of buildings 32 and 36 equal 3,740 sq ft and buildings 24 and 28 equal 4,084 sq ft. If each building is 2,108 sq ft. each duplex should be 4,216 sq ft. Revise or clarify the floor area information.

2-06.4.7.A.8.b - Percentage and area in square feet of building and accessory building coverage;

7. COMMENT: Until the information requested per comment 6, the percentage information cannot be verified.

2-06.4.7.A.8.c - Percentage of building, lot area, or vehicular use area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included; and,

8. COMMENT: Until the information requested per comment 6, the percentage information cannot be verified.


2-06.4.7.C.2 - List the following note on all development package documents: "No structure or vegetation shall be located or maintained so as to interfere with the sight visibility triangles in accordance with Section 10-01.5.0, Sight Visibility, of the Technical Standards Manual."

9. COMMENT: Revise the note on sheet two to include the correct the Technical Standards section: "Section 10-01.5.0, Sight Visibility, of the Technical Standards Manual" instead of Development Standards 3-01.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

10. Include the information along the east side of the property as noted by the standard above.


2-06.4.8.A - Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system.

11. COMMENT: The Pima County Assessor's information does not indicate that the two lots have been combined. A Pima County Assessor's lot combo will be required prior to approval of the DP by Zoning. Label the recorded lot line bearings, degrees and minutes.

2-06.4.8.B - All easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided.

12. COMMENT: If applicable, draw and label all easements on the overall property.

2-06.4.9.H.5 - If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

13. COMMENT: Label the back up spur radius. Minimum radius requirement is three feet.

2-06.4.9.O - All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.

14. COMMENT: In order to verify compliance with the required building setbacks, include a copy of the building model plans with the next DP submittal.


2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).

15. COMMENT: Add the information for both buildings as noted by the standard above.

2-06.4.9.R - Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.

16. COMMENT: Label the longitudinal slopes for all sidewalks.


2-06.4.9.V - For gang mailboxes indicate location to assure there are no conflicts with other requirements, such as pedestrian accessibility, utilities, and landscaping.

17. COMMENT: Indicate the location and type of mailboxes indicate if individual mail service is to be provided, gang mailboxes, or if mail is delivered at curbside mailboxes.

2-06.4.9.X - Show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required. In accordance with Section 2-11.0.0, Landscape Plan Requirements.

18. COMMENT: See the landscape reviewer's comments related to screening and landscape buffer requirements.

19. COMMENT: As courtesy I have included a copy of the Zoning Administrator's determination related to student housing in the application packet.


If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
06/07/2016 DAVID RIVERA H/C SITE REVIEW Reqs Change See zoning comments
06/08/2016 KEN BROUILLETTE FIRE REVIEW Needs Review Please indicate location of proposed and/or existing fire hydrants, with dimensions to property lines.
Refer to 2012 International Fire Code, section 507 for spacing requirements.
06/21/2016 ANDREW CONNOR NPPO REVIEW Approved
06/22/2016 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL
SECTION 2-10.0.0: LANDSCAPE PLAN REQUIREMENTS
4.1 Identification and Descriptive Data
A. All improvements and site information, such as adjacent rights-of-way and property lines, shown on the landscape plan will be identical in size and location to those shown on the base plan (site plan or tentative plat). Should amendments be required to the base plan through the review process, the same amendments will be made to the landscape plan which will then be resubmitted along with the base plan.
B. The landscape plan will contain the following identification in the lower right corner of each sheet:
Any relevant case number for reviews or modifications that affect the site.
ARTICLE 7: DEVELOPMENT STANDARDS
7.6. LANDSCAPING AND SCREENING
Interior Landscape Borders

Interior landscape borders are required as a buffer and visual transition along the common property lines between adjacent land uses and zones as follows, except as provided in Section 7.6.4.C.4, Exceptions to the Landscape Border Standards.

One canopy tree is required for every 33 linear feet of landscape border.
5 trees would be required along the East property line
Ensure that all Zoning and Engineering comments and concerns are addressed.
Additional comments may apply
06/23/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. An approved development plan is not to be used for construction or modification of on-site utilities (e.g. water service to buildings, building sewers, site lighting, electrical service to buildings, etc.). The construction of the on-site utilities may be included with the permit for constructing the building or as a separate permit.
2. Revise the site drawing to include the location of nearest fire hydrant. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2012.
3. Manhole 1293-07 is incorrectly labeled as a clean out. Reference: Section 107.2.1, IBC 2012.
4. Verify the existence of the water meters along the northern property line; Tucson Water's data base shows only a 2" service connection and no water meter at that location.